MAJOR U.S. BUILDING CODES SPECI-

For Vertical Terminations - To locate the vent and install the vent sections:

• Locate and mark the vent centerpoint on the under- side of the roof, and drive a nail through the centerpoint.

• Make the outline of the roof hole around the centerpoint nail.

• The size of the roof hole framing dimensions depend on the pitch of the roof. There MUST BE a 1-inch (25.4 mm) clearance from the vertical vent pipe to combustible materials.

• Mark the roof hole accordingly.

• Cover the opening of the installed vent pipes.

• Cut and frame the roof hole.

• Use framing lumber the same size as the roof rafters and install the frame securely. Flashing anchored to the frame must withstand heavy winds.

• Continue to install concentric vent sections up through the roof hole (for inside vent installations) or up past the roof line until you reach the appropriate distance above the roof (for outside terminations).

 

!

WARNING:

 

MAJOR U.S. BUILDING CODES SPECI-

 

 

FY MINIMUM CHIMNEY AND/OR VENT

 

 

HEIGHT ABOVE THE ROOF TOP. THESE

 

 

MINIMUM HEIGHTS ARE NECESSARY IN

 

 

THE INTEREST OF SAFETY. SEE THE

 

 

FOLLOWING DIAGRAM FOR MINIMUM

 

 

HEIGHTS, PROVIDED THE TERMINA-

 

 

TION CAP IS AT LEAST TWO (2) FEET

 

 

FROM A VERTICAL WALL AND 2-FEET

 

 

BELOW A HORIZONTAL OVERHANG.

NOTE

 

This also pertains to vertical vent systems installed

 

on the outside of the building.