Heat & Glo LifeStyle 6000ARCH, 6000XLT-CDN, 6000TR, 6000XLS manual Round & Trapezoid Termination Caps

Models: 6000TR 6000XLT-CDN 6000XLS 6000ARCH

1 48
Download 48 pages 45.62 Kb
Page 27
Image 27
Figure 25. Round & Trapezoid Termination Caps

For round cap termination:

1.Secure the 8-5/8 inch (219 mm) pipe, using the exterior pipelock hole on the round flange of the wall firestop.

For trapezoidal termination:

1.Screw the cap to the exterior wall through the flanges in the cap.

2.Seal the joint be- tween the pipe and the exterior firestop.

ROUND CAP TERMINATION

PERFORATION CANNOT BE

INSIDE THE WALL

71/2"

(191mm)

MINIMUM

TRAPEZOID CAP TERMINATION

7 1/4"

(184mm)

Figure 25. Round & Trapezoid Termination Caps

!WARNING: THE BOTTOM OF THE VENT TERMINATION CAP MUST BE A MINIMUM OF 12 INCHES (305MM)

ABOVE GROUND LEVEL (GRADE). THE TOP OF THE CAP MUST BE A MINIMUM OF 18 INCHES (457MM) BELOW COM-

BUSTIBLE MATERIAL, SUCH AS A DECK, AND THE SIDE OF THE CAP MUST BE A MINIMUM OF 6 INCHES (152MM) AWAY FROM A PARALLEL OUT-

SIDE WALL. VENTING TERMINALS SHALL NOT BE RECESSED INTO A WALL OR SIDING. SEE THE FOLLOW- ING DIAGRAM FOR VENT TERMINA- TION CLEARANCES.

27

Page 27
Image 27
Heat & Glo LifeStyle 6000ARCH, 6000XLT-CDN, 6000TR, 6000XLS manual Round & Trapezoid Termination Caps