Siemens CP 343-1 manual Properties / Services

Page 6

1 Properties / Services

STime-of-day synchronization over Industrial Ethernet using the following configurable modes:

− SIMATIC mode

The CP receives MMS time frames and synchronizes its local time and the time of the CPU (accuracy approx. +/− 1 second);

or

NTP mode (NTP: Network Time Protocol)

The CP sends time-of-day queries at regular intervals to an NTP server and synchronizes its local time of day and the time of the CPU (accuracy approx. +/− 1 second).

STime of day for the diagnostic buffer

If a time master exists (using the NTP or SIMATIC mode), the time for the CP-internal diagnostic buffer is synchronized over the LAN (accuracy approx. +/− 10 ms)

SAddressing using a factory-set MAC address

The CP can be reached over the default MAC address to allow an IP address to be assigned.

SSNMP Agent

The CP supports data queries over SNMP in version V1 (Simple Network Management Protocol) according to the MIB II and LLDP MIB standard.

You will find more information on MIB in the manual “Commissioning PC Stations” on the SIMATIC NET Manual Collection or at the following SIMATIC NET Internet page:

http://support.automation.siemens.com/WW/view/en/15177711

SIP configuration

You can configure how and with which method the CP is assigned the IP address, the subnet mask and the address of a default router.

It is also possible, as an alternative, to assign the connection configuration to the CP using STEP 7 or using a block interface in the user program (FB55: IP_CONFIG) (see /Part A/).

SWeb diagnostics

With the aid of Web diagnostics, you can read out the diagnostic data from a station connected over the CP to a PG/PC with an Internet browser.

B3L−6

CP 343-1 Lean for Industrial Ethernet / Manual Part B3L

Release 03/2007

C79000-G8976-C198-04

Image 6
Contents S7-CPs for Industrial Ethernet CP 343-1 LeanPrinted Product Information Supplied with the Product Address label Unique MAC address preset for the CPProduct Names Compatibility with the Previous VersionContents B3L−46 B3L−33B3L−44 B3L−53Application Properties / ServicesServices B3L−5Properties / Services Version / NCM IE Functions of the CP ConfigurationProgramming − Using Blocks B3L−7B3L−8 Requirements for UseGeneral Operation Order NumberB3L−9 CPU 314 IFMB3L−10 Installation and Commissioning Procedure / Steps Step Explanation / MeaningGround/Chassis Ground Concept B3L−13 Acyclic data exchange, for example Send/Receive DC 5 V power supply via the backplane bus green = OKDisplays Not relevant for Profinet IO dataSFred BF red LEDs for displaying the modeCP Operating Mode GreenDisplay Meaning RX/TX green LEDs for displaying the CP communication statusB3L−16 P1 / P2Performance Data Characteristic Data for S7 CommunicationCharacteristic Explanation / Values Number of Possible Connections over EthernetCharacteristics of the SEND/RECEIVE Interface Execution Times of the FCs Agsend / AgrecvComponent Explanation / Values Characteristic Data for Profinet IO CP as Profinet IO deviceExecution times of the FCs Pniosend / Pniorecv Overview of the Preparatory Steps Configuring and Programming the CP as a Profinet IO DeviceConfigurationProgramming Intelligent Profinet IO DevicePrinciple of Data Exchange over Profinet IO Configuration Installing the CP and Specifying it as Profinet IO DeviceDownload the configuration data to the Simatic 300 station B3L−23Requirements for Configuration in Step Configuring the Profinet IO controllerProfinet IO Controller Result B3L−25Configuring the properties of the CP as Profinet IO device Properties Dialog of the Device Assigning the Device NameProgramming Interface for Programming on the Profinet IO DeviceFCs Initialization and Configuration Data consistencyInitialization Reasons for reinitialization WatchdogB3L−29 Example of Configuration and Programming Pniorecv PniosendCall interface Pniosend in the user program B3L−31Call interface Pniorecv in the user program B3L−32Starting and Working with Web Diagnostics Web DiagnosticsSettings for Access to Diagnostic Data Web diagnostics opens with the StartDiagnostics Pages of the CP Layout of the Diagnostics PagesGeneral StartParameter Function StatusIdentification IdentificationParameter VersionRack Configuration Rack Configuration Rack nameB3L−38 Diagnostic Buffer EventsDetails no. of the event Network attachment Industrial EthernetParameters Tab IP parametersStatistics Tab TCP Connections TabUDP Connections Tab Profinet IO Configuration Parameters of a Profinet IO DeviceB3L−43 Assigned Pnio controllerCompatibility with Predecessor Products Replacing Older Modules / Replacing Faulty ModulesUse as a Replacement Extended FunctionalityModule Replacement Originally configured module Configuration StepsB3L−45 Defaults Memory ResetHow to Use the Function Further Notes on OperationHow Automatic Switchover of the Network Settings Works Working with Fast Ethernet − automatic switchoverBehavior after Memory Reset AutocrossingAutomatic Setting or Individual Network Settings Further NotesSnmp Agent Supported MIB ObjectsAccess Permissions using Community Name Influence of MPI on Connections via Industrial EthernetSpecial Features of IP Configuration Protocol Port number ServiceReserved Port Numbers Other information available about the CP Gsdml fileLEDs to Indicate the CP Mode How to Load New FirmwareHow to Download New Firmware RequirementsTechnical Specifications B3L−54B3L−55 B3L−56