Siemens CP 343-1 manual Profinet IO Controller, Requirements for Configuration in Step

Page 24

6 Configuring and Programming the CP as a PROFINET IO Device

6.3.2Assigning the PROFINET IO Device to a PROFINET IO Controller

PROFINET IO Controller

This section describes the configuration of PROFINET IO controllers with STEP 7. This includes:

SStations of the type SIMATIC 300 and SIMATIC 400

CPU with integrated PROFINET IO controller (for example CPU 317−2 PN/DP).

CPU with external PROFINET IO controller (for example CP 343−1).

SSIMATIC PC station

For example with CP 1616

If you do not configure your system with STEP 7, you will need to use the GSDML file of the CP to configure the CP in your configuration system (download address see Section 9.10)

When configuring the PROFINET IO device (see Section 6.3.1), the selected PROFINET IO controller is unimportant.

Requirements for Configuration in STEP 7

There must be a SIMATIC station in the STEP 7 project in which a module (CPU or CP) supports operation as PROFINET IO controller.

Notice

The IP address of the PROFINET IO device and the IP address of the PROFINET IO controller must be located in the same IP subnet.

Step 1: Configuring the PROFINET IO controller

With some PROFINET IO controller types, STEP 7 automatically creates a PROFINET IO system as soon as you insert the module, otherwise you may need to add a PROFINET IO system. Drag the required IO devices from the hardware catalog to this PROFINET IO system.

Configure a PROFINET IO controller as follows:

1.Open the hardware configuration of the station you want as PROFINET IO controller in HW Config.

2.If no PROFINET IO system exists, select the PROFINET IO controller (for example CP 343−1 EX30/GX21, CP 443−1 EX41, CPU 317−2 PN/DP) and insert a PROFINET IO system (menu “Insert” "“PROFINET IO System”).

B3L−24

CP 343-1 Lean for Industrial Ethernet / Manual Part B3L

Release 03/2007

C79000-G8976-C198-04

Image 24
Contents S7-CPs for Industrial Ethernet CP 343-1 LeanAddress label Unique MAC address preset for the CP Product NamesPrinted Product Information Supplied with the Product Compatibility with the Previous VersionContents B3L−33 B3L−44B3L−46 B3L−53Properties / Services ServicesApplication B3L−5Properties / Services Configuration Programming − Using BlocksVersion / NCM IE Functions of the CP B3L−7Requirements for Use General OperationB3L−8 Order NumberB3L−9 CPU 314 IFMB3L−10 Installation and Commissioning Procedure / Steps Step Explanation / MeaningGround/Chassis Ground Concept B3L−13 DC 5 V power supply via the backplane bus green = OK DisplaysAcyclic data exchange, for example Send/Receive Not relevant for Profinet IO dataLEDs for displaying the mode CP Operating ModeSFred BF red GreenLEDs for displaying the CP communication status B3L−16Display Meaning RX/TX green P1 / P2Characteristic Data for S7 Communication Characteristic Explanation / ValuesPerformance Data Number of Possible Connections over EthernetCharacteristics of the SEND/RECEIVE Interface Execution Times of the FCs Agsend / AgrecvComponent Explanation / Values Characteristic Data for Profinet IO CP as Profinet IO deviceExecution times of the FCs Pniosend / Pniorecv Configuring and Programming the CP as a Profinet IO Device ConfigurationProgrammingOverview of the Preparatory Steps Intelligent Profinet IO Device Principle of Data Exchange over Profinet IO Configuration Installing the CP and Specifying it as Profinet IO DeviceDownload the configuration data to the Simatic 300 station B3L−23Requirements for Configuration in Step Configuring the Profinet IO controllerProfinet IO Controller Result B3L−25Configuring the properties of the CP as Profinet IO device Properties Dialog of the Device Assigning the Device NameProgramming Interface for Programming on the Profinet IO DeviceFCs Initialization and Configuration Data consistencyInitialization Reasons for reinitialization WatchdogB3L−29 Example of Configuration and Programming Pniorecv PniosendCall interface Pniosend in the user program B3L−31Call interface Pniorecv in the user program B3L−32Web Diagnostics Settings for Access to Diagnostic DataStarting and Working with Web Diagnostics Web diagnostics opens with the StartDiagnostics Pages of the CP Layout of the Diagnostics PagesStart Parameter FunctionGeneral StatusIdentification ParameterIdentification VersionRack Configuration Rack Configuration Rack nameB3L−38 Diagnostic Buffer EventsDetails no. of the event Industrial Ethernet Parameters TabNetwork attachment IP parametersStatistics Tab TCP Connections TabUDP Connections Tab Profinet IO Configuration Parameters of a Profinet IO DeviceB3L−43 Assigned Pnio controllerReplacing Older Modules / Replacing Faulty Modules Use as a ReplacementCompatibility with Predecessor Products Extended FunctionalityModule Replacement Originally configured module Configuration StepsB3L−45 Memory Reset How to Use the FunctionDefaults Further Notes on OperationWorking with Fast Ethernet − automatic switchover Behavior after Memory ResetHow Automatic Switchover of the Network Settings Works AutocrossingAutomatic Setting or Individual Network Settings Further NotesSnmp Agent Supported MIB ObjectsAccess Permissions using Community Name Influence of MPI on Connections via Industrial EthernetSpecial Features of IP Configuration Protocol Port number ServiceReserved Port Numbers Other information available about the CP Gsdml fileHow to Load New Firmware How to Download New FirmwareLEDs to Indicate the CP Mode RequirementsTechnical Specifications B3L−54B3L−55 B3L−56
Related manuals
Manual 22 pages 56.26 Kb