Rosemount 3051S
Reference Manual
Figure
Flow Configuration File
Selected |
|
| |
Device | Send Mass Flow |
| |
(Highlighted) |
| ||
Configuration File to | Status Confirms Mass | ||
| |||
| Selected Device | ||
| Flow Configuration File | ||
|
| ||
|
| Installations |
Table
|
| Data Type/ |
|
|
|
|
|
|
|
Index | Parameter | Structure | Store | Size | Valid Range | Initial Value | Units | Mode | Description |
|
|
|
|
|
|
|
|
|
|
14 | DIFFERENTIAL | D | 5 |
|
| inH20 | MAN | The differential pressure status and | |
| _PRESSURE |
|
|
|
|
| @68°F |
| value |
|
|
|
|
|
|
|
|
|
|
15 | DIFFERENTIAL | Unsigned16 | S | 2 | 10: DP Sensor | 10 | E | O/S | The channel through which the |
| _PRESSURE_ |
|
|
| (scaled) |
|
|
| differential pressure is communicated |
| SOURCE |
|
|
|
|
|
|
| (and converted to the proper units) |
16 | PRESSURE | D | 5 |
|
| Psia | MAN, | The absolute pressure status and value | |
|
|
|
|
|
|
|
| O/S(1) |
|
17 | PRESSURE_ | Unsigned16 | S | 2 | 5: Absolute | 8 | E | O/S | The channel through which the absolute |
| SOURCE |
|
|
| Pressure |
|
|
| pressure is communicated. When |
|
|
|
|
| (A0.OUT) |
|
|
| AO.OUT value is used, FAULT_STATE |
|
|
|
|
| 8: Absolute |
|
|
| is used if status goes bad. When |
|
|
|
|
| Pressure |
|
|
| CAS_IN shadow is used, bad |
|
|
|
|
| (CAS_IN |
|
|
| status/value will be propagated to the |
|
|
|
|
| shadow) |
|
|
| mass flow block. If a value of “Constant” |
|
|
|
|
| 255: Constant |
|
|
| is specified, the PRESSURE parameter |
|
|
|
|
|
|
|
|
| becomes writable in O/S and the |
|
|
|
|
|
|
|
|
| constant value is used in the calculation. |
18 | TEMPERATUR | D | 5 |
|
| °F | MAN, | The process temperature status and | |
| E |
|
|
|
|
|
| O/S(2) | value |
19 | TEMPERATUR | Unsigned16 | S | 2 | 6: Process | 9 | E | O/S | The channel through which the process |
| E_SOURCE |
|
|
| Temperature |
|
|
| temperature is communicated. When |
|
|
|
|
| (CAS_IN |
|
|
| AO.OUT value is used, FAULT_STATE |
|
|
|
|
| shadow) |
|
|
| is used if status goes bad. When |
|
|
|
|
| 9: Process |
|
|
| CAS_IN shadow is used, bad |
|
|
|
|
| Temperature |
|
|
| status/value will be propagated to the |
|
|
|
|
| (CAS_IN |
|
|
| mass flow block. If a value of “Constant” |
|
|
|
|
| shadow) |
|
|
| is specified, the TEMPERATURE |
|
|
|
|
| 255: Constant |
|
|
| parameter becomes writable in O/S and |
|
|
|
|
|
|
|
|
| the constant value is used in the |
|
|
|
|
|
|
|
|
| calculation. |
|
|
|
|
|
|
|
|
|
|
(1)PRESSURE can be written in O/S mode if the PRESSURE_SOURCE is set to “Constant”
(2)TEMPERATURE can be written in O/S mode if the TEMPERATURE_SOURCE is set to “Constant”