Emerson manual Rosemount 3051S, Reference Manual, Selected

Models: 3051S

1 32
Download 32 pages 28.03 Kb
Page 32
Image 32
Selected

Rosemount 3051S

Reference Manual

00809-0200-4801, Rev BA April 2007

Figure 3-10. Download Mass

Flow Configuration File

Selected

 

 

Device

Send Mass Flow

 

(Highlighted)

 

Configuration File to

Status Confirms Mass

 

 

Selected Device

 

Flow Configuration File

 

 

 

 

Installations

Table 3-7. Mass Flow Block Device - Specific Parameter Values

 

 

Data Type/

 

 

 

 

 

 

 

Index

Parameter

Structure

Store

Size

Valid Range

Initial Value

Units

Mode

Description

 

 

 

 

 

 

 

 

 

 

14

DIFFERENTIAL

DS-65

D

5

 

 

inH20

MAN

The differential pressure status and

 

_PRESSURE

 

 

 

 

 

@68°F

 

value

 

 

 

 

 

 

 

 

 

 

15

DIFFERENTIAL

Unsigned16

S

2

10: DP Sensor

10

E

O/S

The channel through which the

 

_PRESSURE_

 

 

 

(scaled)

 

 

 

differential pressure is communicated

 

SOURCE

 

 

 

 

 

 

 

(and converted to the proper units)

16

PRESSURE

DS-65

D

5

 

 

Psia

MAN,

The absolute pressure status and value

 

 

 

 

 

 

 

 

O/S(1)

 

17

PRESSURE_

Unsigned16

S

2

5: Absolute

8

E

O/S

The channel through which the absolute

 

SOURCE

 

 

 

Pressure

 

 

 

pressure is communicated. When

 

 

 

 

 

(A0.OUT)

 

 

 

AO.OUT value is used, FAULT_STATE

 

 

 

 

 

8: Absolute

 

 

 

is used if status goes bad. When

 

 

 

 

 

Pressure

 

 

 

CAS_IN shadow is used, bad

 

 

 

 

 

(CAS_IN

 

 

 

status/value will be propagated to the

 

 

 

 

 

shadow)

 

 

 

mass flow block. If a value of “Constant”

 

 

 

 

 

255: Constant

 

 

 

is specified, the PRESSURE parameter

 

 

 

 

 

 

 

 

 

becomes writable in O/S and the

 

 

 

 

 

 

 

 

 

constant value is used in the calculation.

18

TEMPERATUR

DS-65

D

5

 

 

°F

MAN,

The process temperature status and

 

E

 

 

 

 

 

 

O/S(2)

value

19

TEMPERATUR

Unsigned16

S

2

6: Process

9

E

O/S

The channel through which the process

 

E_SOURCE

 

 

 

Temperature

 

 

 

temperature is communicated. When

 

 

 

 

 

(CAS_IN

 

 

 

AO.OUT value is used, FAULT_STATE

 

 

 

 

 

shadow)

 

 

 

is used if status goes bad. When

 

 

 

 

 

9: Process

 

 

 

CAS_IN shadow is used, bad

 

 

 

 

 

Temperature

 

 

 

status/value will be propagated to the

 

 

 

 

 

(CAS_IN

 

 

 

mass flow block. If a value of “Constant”

 

 

 

 

 

shadow)

 

 

 

is specified, the TEMPERATURE

 

 

 

 

 

255: Constant

 

 

 

parameter becomes writable in O/S and

 

 

 

 

 

 

 

 

 

the constant value is used in the

 

 

 

 

 

 

 

 

 

calculation.

 

 

 

 

 

 

 

 

 

 

(1)PRESSURE can be written in O/S mode if the PRESSURE_SOURCE is set to “Constant”

(2)TEMPERATURE can be written in O/S mode if the TEMPERATURE_SOURCE is set to “Constant”

3-32

Page 32
Image 32
Emerson manual Rosemount 3051S, Reference Manual, Selected