Reference Manual

00809-0200-4801, Rev BA April 2007

Rosemount 3051S

Solution to situation #3

Table 3-4. Analog Input function block configuration for a pressure transmitter used in level measurement (Situation #3).

Table 3-4 lists the appropriate configuration settings.

Parameter

Configured Values

 

 

L_TYPE

Indirect

XD_SCALE

2 to 9 psi

 

 

OUT_SCALE

0 to 16 ft

Channel

1 - pressure

 

 

In this example, when the PV is 4 psi, OUT will be calculated as follows:

OUT = 4 psi – 2 psi * (16 ft. – 0 ft.) + 0 ft. = 4.57 ft. 9 psi – 2 psi

Differential pressure transmitter to measure flow

Table 3-5. Analog Input Function Block Configuration for a Differential Pressure Transmitter.

Situation #4

The liquid flow in a line is to be measured using the differential pressure across an orifice plate in the line. Based on the orifice specification sheet, the differential pressure transmitter was calibrated for 0 to 20 inH20 for a flow of 0 to 800 gal/min.

Solution

Table 3-5 lists the appropriate configuration settings.

Parameter

Configured Values

 

 

 

 

 

L_TYPE

 

Indirect Square Root

 

XD_SCALE

 

0 to 20 in.H2O

 

OUT_SCALE

 

0 to 800 gal/min.

 

Channel

 

1 - pressure

 

 

 

 

 

Out =

PV------------------------------------------------XDSCALE0(OUTSCALE100 OUTSCALE0) + OUTSCALE0

 

XDSCALE100

 

 

OUT=

8inH2O 0inH2O

 

 

20inH-----------------------------------------------------2O0inH2O (800gal/min. - 0gal/min.) + 0gal/min. = 505.96gal/min.

3-13