Reference Manual
Rosemount 3051S
Solution to situation #3
Table
Table
Parameter | Configured Values |
|
|
L_TYPE | Indirect |
XD_SCALE | 2 to 9 psi |
|
|
OUT_SCALE | 0 to 16 ft |
Channel | 1 - pressure |
|
|
In this example, when the PV is 4 psi, OUT will be calculated as follows:
OUT = 4 psi – 2 psi * (16 ft. – 0 ft.) + 0 ft. = 4.57 ft. 9 psi – 2 psi
Differential pressure transmitter to measure flow
Table
Situation #4
The liquid flow in a line is to be measured using the differential pressure across an orifice plate in the line. Based on the orifice specification sheet, the differential pressure transmitter was calibrated for 0 to 20 inH20 for a flow of 0 to 800 gal/min.
Solution
Table
Parameter | Configured Values |
| ||
|
|
|
| |
L_TYPE |
| Indirect Square Root |
| |
XD_SCALE |
| 0 to 20 in.H2O |
| |
OUT_SCALE |
| 0 to 800 gal/min. |
| |
Channel |
| 1 - pressure |
| |
|
|
|
| |
Out = |
| |||
| XDSCALE100 |
|
| |
OUT= | 8inH2O – 0inH2O |
|
| |