Reference Manual
Rosemount 3051S
Process Alarms
Process Alarm detection is based on the OUT value. Configure the alarm limits of the following standard alarms:
•High (HI_LIM)
•High high (HI_HI_LIM)
•Low (LO_LIM)
•Low low (LO_LO_LIM)
In order to avoid alarm chattering when the variable is oscillating around the alarm limit, an alarm hysteresis in percent of the PV span can be set using the ALARM_HYS parameter. The priority of each alarm is set in the following parameters:
•HI_PRI
•HI_HI_PRI
•LO_PRI
•LO_LO_PRI
Alarm Priority
Alarms are grouped into five levels of priority:
Priority |
|
Number | Priority Description |
0The alarm condition is not used.
1An alarm condition with a priority of 1 is recognized by the system, but is not reported to the operator.
2An alarm condition with a priority of 2 is reported to the operator.
Status Options
Status Options (STATUS_OPTS) supported by the AI block are shown below:
Propagate Fault Forward
If the status from the sensor is Bad, Device failure or Bad, Sensor failure, propagate it to OUT without generating an alarm. The use of these
Uncertain if Limited
Set the output status of the Analog Input block to uncertain if the measured or calculated value is limited.
BAD if Limited
Set the output status to Bad if the sensor is violating a high or low limit.
Uncertain if Man Mode
Set the output status of the Analog Input block to uncertain if the actual mode of the block is Man.
NOTES
The instrument must be in Out of Service mode to set the status option.