Rosemount 3051S
Reference Manual
Solution to Situation #2
Table
Table
(situation #1).
Parameter | Configured Values |
|
|
L_TYPE | Indirect |
XD_SCALE | 0 to 7 psi |
|
|
OUT_SCALE | 0 to 16 ft |
Channel | 1 - pressure |
|
|
Output calculation for Situation #2
When the L_Type is configured as Indirect, the OUT parameter is calculated as:
OUT = | PV – XD_SCALE_0% | * (OUT_SCALE_100% – OUT_SCALE_0%) + OUT_SCALE_0% |
XD_SCALE_100% – XD_SCALE_0%
In this example, when PV is 5 psi, then the OUT parameter will be calculated as follows:
OUT = 5 psi – 0 psi * (16 ft. – 0 ft.) + 0 ft. = 11.43 ft.
7 psi – 0 psi
Situation #3
The transmitter in situation #3 is installed below the tank in a position where the liquid column in the impulse line, with an empty tank, is equivalent to 2.0 psi (see Figure
Figure
Diagram.
16 ft
Empty Tank
0 ft
2.0 psi measured at the transmitter