Table
Number Name and Description
0Other
1Block Configuration Error: the selected channel carries a measurement that is incompatible with the engineering units selected in XD_SCALE, the L_TYPE parameter is not configured, or WRITE_CHECK = zero.
2 Link Configuration Error
3Simulate Active: Simulation is enabled and the block is using a simulated value in its execution.
4Local Override
5Device Fault State Set
6Device Needs Maintenance Soon
7Input Failure/Process Variable has Bad Status: The hardware is bad, or a bad status is being simulated.
8Output Failure: The output is bad based primarily upon a bad input.
9Memory Failure
10 Lost Static Data
11 Lost NV Data
12 Readback Check Failed
13 Device Needs Maintenance Now
14Power Up
15Out of Service: The actual mode is out of service.
Modes
The MAI Function Block supports three modes of operation as defined by the MODE_BLK parameter:
Manual (Man)
The block output (OUT) may be set manually
Automatic (Auto)
OUT_1 to OUT_8 reflects the analog input measurement or the simulated value when simulation is enabled.
Out of Service (OOS)
The block is not processed. PV is not updated and the OUT status is set to Bad: Out of Service. The BLOCK_ERR parameter shows Out of Service. In this mode, changes can be made to all configurable parameters. The target mode of a block may be restricted to one or more of the supported modes.