Emerson manual Rosemount 3051S, Reference Manual, Other

Models: 3051S

1 32
Download 32 pages 28.03 Kb
Page 17
Image 17
0Other

Reference Manual

00809-0200-4801, Rev BA April 2007

Rosemount 3051S

Table 3-6. Block Error Conditions

Number Name and Description

0Other

1Block Configuration Error: the selected channel carries a measurement that is incompatible with the engineering units selected in XD_SCALE, the L_TYPE parameter is not configured, or WRITE_CHECK = zero.

2 Link Configuration Error

3Simulate Active: Simulation is enabled and the block is using a simulated value in its execution.

4Local Override

5Device Fault State Set

6Device Needs Maintenance Soon

7Input Failure/Process Variable has Bad Status: The hardware is bad, or a bad status is being simulated.

8Output Failure: The output is bad based primarily upon a bad input.

9Memory Failure

10 Lost Static Data

11 Lost NV Data

12 Readback Check Failed

13 Device Needs Maintenance Now

14Power Up

15Out of Service: The actual mode is out of service.

Modes

The MAI Function Block supports three modes of operation as defined by the MODE_BLK parameter:

Manual (Man)

The block output (OUT) may be set manually

Automatic (Auto)

OUT_1 to OUT_8 reflects the analog input measurement or the simulated value when simulation is enabled.

Out of Service (OOS)

The block is not processed. PV is not updated and the OUT status is set to Bad: Out of Service. The BLOCK_ERR parameter shows Out of Service. In this mode, changes can be made to all configurable parameters. The target mode of a block may be restricted to one or more of the supported modes.

3-17

Page 17
Image 17
Emerson manual Rosemount 3051S, Reference Manual, Other