Pressure (Channel 1)

Rosemount 3051S

Reference Manual

00809-0200-4801, Rev BA April 2007

XD_SCALE and OUT_SCALE

The XD_SCALE and OUT_SCALE each include three parameters: 0%, 100%, and, engineering units. Set these based on the L_TYPE:

L_TYPE is Direct

When the desired output is the measured variable, set the XD_SCALE to the “Primary_Value_Range”. This is found in the Sensor Transducer Block. Set OUT_SCALE to match XD_SCALE.

L_TYPE is Indirect

When an inferred measurement is made based on the sensor measurement, set the XD_SCALE to represent the operating range that the sensor will see in the process. Determine the inferred measurement values that correspond to the XD_SCALE 0 and 100% points and set these for the OUT_SCALE.

L_TYPE is Indirect Square Root

When an inferred measurement is made based on the sensor measurement AND the relationship between the inferred measurement and sensor measurement is square root, set the XD_SCALE to represent the operating range that the sensor will see in the process. Determine the inferred measurement values that correspond to the XD_SCALE 0 and

100% points and set these for the OUT_SCALE.:

Pressure (Channel 1)

Temperature (Channel 2)

Flow (Channel 7)

 

 

 

Pa

°C

lbm/sec

 

 

 

kPa

°F

lbm/min

bar

°K

lbm/hour

 

 

 

mPa

 

lbm/day

mbar

 

kg/sec

 

 

 

torr

 

kg/min

atm

 

kg/hour

 

 

 

psi

 

grams/sec

g/cm2

 

grams/min

 

 

 

kg/cm2

 

grams/hour

inH2O at 68 °F

 

StdCuFt/sec

mmH2O at 68 °F

 

StdCuFt/min

in.H2O at 4 °F

 

StdCuFt/min

mmH2O at 4 °F

 

StdCuFt/hour

ftH2O at 68 °F

 

StdCuFt/day

inHg at 0 °C

 

StdCuM/hour

mmHg at 0 °C

 

StdCuM/day

 

 

 

 

 

NmlCuM/hour

 

 

NmlCuM/day

NOTE

When the engineering units of the XD_SCALE are selected, this causes the engineering units of the PRIMARY_VALUE_RANGE in the Transducer Block to change to the same units. THIS IS THE ONLY WAY TO CHANGE THE ENGINEERING UNITS IN THE SENSOR TRANSDUCER BLOCK, PRIMARY_VALUE_RANGE parameter.