Emerson manual Rosemount 3051S, Reference Manual, differential pressure in AI.XDSCALE units

Models: 3051S

1 32
Download 32 pages 28.03 Kb
Page 9
Image 9
differential pressure in AI.XD_SCALE units

Reference Manual

00809-0200-4801, Rev BA April 2007

Rosemount 3051S

CHANNEL

Select the channel that corresponds to the desired sensor measurement. The 3051S measures both pressure (channel 1) and sensor temperature (channel 2).

Table 3-1. I/O Channel Definitions

Channel Number

Channel Description

 

 

1

differential pressure in AI.XD_SCALE units

 

 

2

sensor temperature in AI.XD_SCALE units

3

differential pressure in inH20 @68°F (ADB)

 

 

4

mean differential pressure

5

absolute pressure (AO.OUT)

 

 

6

process temperature (AO.OUT)

7

mass flow

 

 

8

absolute pressure (AO.CAS_IN shadow)

9

process temperature (AO.CAS_IN shadow)

 

 

10

differential pressure in inH20 @68°F (MFTB)

11

All MAI channels (12-19 below)

 

 

12

SPM1 mean (ADB)

13

SPM1 standard deviation (ADB)

 

 

14

SPM2 mean (ADB)

15

SPM2 standard deviation (ADB)

 

 

16

SPM3 mean (ADB)

17

SPM3 standard deviation (ADB)

 

 

18

SPM4 mean (ADB)

19

SPM4 standard deviation (ADB)

NOTE

Channel 3 and channels 12-19 are only available when the Advanced Diagnostic Block is licensed. Channels 5-9 are only available when the Mass Flow Block is licensed.

L_TYPE

The L_TYPE parameter defines the relationship of the sensor measurement (pressure or sensor temperature) to the desired output of the AI Block (e.g. pressure, level, flow, etc.). The relationship can be direct, indirect, or indirect square root.

Direct

Select direct when the desired output will be the same as the sensor measurement (pressure or sensor temperature).

Indirect

Select indirect when the desired output is a calculated measurement based on the sensor measurement (e.g. a pressure measurement is made to determine level in a tank). The relationship between the sensor measurement and the calculated measurement will be linear.

Indirect Square Root

Select indirect square root when the desired output is an inferred measurement based on the sensor measurement and the relationship between the sensor measurement and the inferred measurement is square root (e.g. flow).