FOUNDATION Fieldbus

Rosemount 3051S

Reference Manual

00809-0200-4801, Rev BA April 2007

Create and Send a Mass Flow Configuration using 3051S EA for

FOUNDATION Fieldbus

A mass flow configuration file can be created in either OFFLINE or ONLINE mode.

1.Select the device tag name requiring a new or updated mass flow configuration file. The selected device tag will become highlighted. Information about the selected device will appear on the Device Status portion of the screen.

2.Select the EA Wizard. A window stating, “Welcome to Rosemount Engineering Assistant for FOUNDATION Fieldbus” will appear.

Figure 3-8. Open EA Wizard

Mass Flow Configuration File

Name

Open EA

Wizard

Select Device

Tag Name

 

Start EA Wizard

Scan FOUNDATION

Browse and
fieldbus segment
Open
for 3051S devices
Existing FIle

3.3.Select either “Start new file in Flow Wizard” or “Open existing configuration files” in Flow Wizard. Select either create a new file or open a current (saved) file and edit. Follow the EA Wizard and step through completing a mass flow configuration (see page 3-33for details.)

3-30