Rosemount 3051S
Reference Manual
Filtering | The filtering feature changes the response time of the device to smooth |
| variations in output readings caused by rapid changes in input. Adjust the |
| filter time constant (in seconds) using the PV_FTIME parameter. Set the filter |
| time constant to zero to disable the filter feature. |
Figure
PV_FTIME filtering Diagram.
Low Cutoff
OUT (mode in man) |
OUT (mode in auto) |
PV |
63% of Change |
FIELD_VAL |
Time (seconds)
PV_FTIME
When the converted input value is below the limit specified by the LOW_CUT parameter, and the Low Cutoff I/O option (IO_OPTS) is enabled (True), a value of zero is used for the converted value (PV). This option is useful to eliminate false readings when the differential pressure measurement is close to zero, and it may also be useful with
NOTE
Low Cutoff is the only I/O option supported by the AI block. Set the I/O option in Manual or Out of Service mode only.