Emerson user manual XDF Startup Inspection Checklist, Site Conditions

Page 43

Startup

9.0STARTUP

Before plugging in your electronic equipment, make sure that all power switches are in the OFF posi- tion.

Be certain there are no obstructions, wire bundles, manuals, trash, etc., in front of or on either side of the XDF. Make sure all doors are shut and sealed properly.

Plug the XDF’s 120V power cord into a dedicated utility circuit.

Plug the XDF’s 208V power cord into a dedicated utility circuit.

9.1XDF Startup Inspection Checklist

9.1.1Site Conditions

___ 1. Confirm at least 36 in. (915mm) clearance in front of the XDF, on the right side and behind the unit. No left-side clearance required.

___ 2. Confirm at least 36 in. (915mm) clearance above the unit (self-contained, air cooled units only; water/glycol units do not require clearance above).

___ 3. Confirm site ventilation provisions:

___

Sufficient ambient space to dissipate heat rejected by the XDF (self-contained, air cooled

 

units).

___

Ambient temperature range is 35°F to 104°F (1.6 to 40°C).

___ 4. Ensure that the XDF is level.

___ 5. Confirm condensate drain tube is connected to a drain and will drain properly.

___ 6. Secure all electrical connections inside the XDF.

___ 7. Confirm that the dedicated circuits for the XDF’s compressor and fans are separate from the circuit for the UPS (not same duplex).

___

XDF requires a 120V/60Hz/15A, single-phase, 2-wire plus ground circuit.

___

Record the fan working input voltage 120VAC (±10%): ____________________

___

XDF requires a 208V/60Hz/30A, three-phase, 4-wire plus ground circuit.

___

Record the compressor working input voltage 208VAC (±10%): ____________________

___

Check UPS (if provided) nameplate for input electrical requirements.

___ 8. Examine the positioning of equipment inside the cabinet.

___

Prevent short cycling of airflow - no spaces larger than 1U between electronic devices.

___

Spaces larger than 5U at top of rack are covered with blanking panels.

___

Heaviest equipment installed near the bottom of the cabinet.

___ 9. Check cabinet seals—No gaps, loose cables, air leaks:

___

Door gaskets intact / free of damage. Close front and rear doors and confirm no visible

 

seal violations.

___

Side panels and the frame have uniform sealing.

___

Cable entrance points are sealed.

___ 10. Determine whether the UPS, if one is installed in the XDF, has fully charged batteries.

NOTE

The UPS’s batteries may require recharging before it can fully supply your equipment’s power needs for the rated time if utility power fails.

To charge the UPS batteries before using the unit, you can apply power to the UPS module while installing equipment or making adjustments.

Refer to the UPS manual for preparation for startup, details of UPS operation and the meaning of LED indicators.

37

Image 43
Contents Liebert XDF Page Table of Contents Cable Management Options Piping CONSIDERATIONS-WATER/GLYCOLMODELS onlyFilling the XDF with COOLANT-WATER or Glycol Electrical ConnectionsSpecifications MaintenanceTables Important Safety Instructions Indicates ground connection Glossary of SymbolsIndicates weight Hazardous Voltage PresentEntry Point Condenser Air ICOM Controller Backup Ventilation Air Intake CompressorCondenser Coil 1 Brazed Plate Condenser behind grille ICOM Controller Operational Overview Water/Glycol Cooled ModelReturn Line Female Condenser fanRemovable to reduce Height temporarilyDimensional data, self-contained, air cooled model Plate Connection 139.7mm176.5mm 47.6mmCable Entry Cutout 114mmEntry CutoutsDoors XDF ComponentsFrame EnclosureHeat Removal-Self-Contained, Air Cooled XDF Environmental ControlHeat Removal-Water/Glycol Cooled XDF Rear FrontBrazed Plate Condenser Liebert iCOM controller Control-Liebert’s iCOM ControllerClosed-Loop Water System Coolant Source-Water/Glycol ModelsWater/Glycol Return Line Cooled Drycooler LoopGeneral Enclosure Options Power Options MP Advanced Power Strips and ControllersUninterruptible Power Supply Optional EquipmentUnloading the XDF Recommended Setup EquipmentInstallation InspectionUnpack the XDF Handling the Unit While It is PackagedFork Lift Right front corner detail controls side of XDF Removing the XDF from SkidRoll XDF off the shipping skid 36 915mm XDF Site Preparation915mm Voltage Input Requirements Voltage RequirementsModel Feet m 60Hz 50Hz Drycooler Installation-Water/Glycol Cooled ModelOptional condensate pump performance Maximum HeadRecommended equipment arrangement Equipment LayoutRear-Mount Rails-Position Frame and Enclosure ConfigurationsMounting Hardware Internal Mounting RailsQuick Door Removal Door-RemoveSide Panels-Remove and Replace Remove the DoorReplace a Panel Remove the Right PanelWater supply flow rates GeneralClosed Loop Water System Piping CONSIDERATIONS-WATER/GLYCOL Models onlyCorrosion Protection Expansion Tanks, Fluid Relief Valves and Other DevicesFreeze Protection-Coolant Type and Insulation Glycol supply flow rates Glycol SolutionsDrycooler Loop System Ethylene glycol concentrationsFilling the XDF with COOLANT-WATER or Glycol XDF Water/Glycol Cooled Unit VolumeVolume in standard Type L copper piping Preparing the System for FillingCustomer Cable Entry Points Electrical ConnectionsDashed line delineates equipment compartment Rear Route Input Power Cables Through the XDF’s Top Utility Power SupplyCable Management Cable Management ConsiderationsCable Management Options Optional Cable Management Channel Cable AccessTop Cover and Back Cable Tray Detail View Startup XDF Startup Inspection ChecklistSite Conditions Escape Key Down Arrow Key Starting the XDFICOM Components and Functions Environmental ControlOperation Icon Key Name Function Keyboard icons and functionsOK no Navigating Through the iCOM DisplayEntering the Password Accessing Menus and Settings Viewing DataChanging Operational Settings Icon Name Description User menu iconsChanging the XDF’s Default Operating Temperature Changing iCOM’s Display SettingsHighlight the setting to be changed by pressing Enter Operation With the Door Open Uninterruptible Power Supply Backup Ventilation SystemXDF Compressor Maintenance Periodic MaintenanceTroubleshooting Monitoring SpecificationsPhysical specifications Self- Contained Water/Glycol Dimensions Air Cooled XDFTotal heat rejection Electrical specificationsSelf- Contained Water/Glycol Electrical Data Air Cooled XDF UPS performance data Optional Power SystemsTypes Quan Port Remote Monitoring and Control MP Advanced Power Strip specificationsRemote Monitoring Only Page That Ne tIti Ti n