Samsung A6 installation manual Auxiliary Circuit Breaker, Electrical Work

Page 38

INSTALLING THE OUTDOOR UNIT

Auxiliary Circuit Breaker

Outdoor unit

Distribution

 

board

 

 

 

 

 

 

 

 

 

 

Auxiliary power s/w

Auxiliary circuit breaker should be installed near outdoor unit so that each access is possible. Main/outdoor power supply cable are connected to upper/lower terminal of auxiliary circuit breaker.

It is necessary that the conduit kit for power supply to the outdoor unit be installed between auxiliary power S/W and the outdoor unit. (the conduit kit is optional)

The designs and shape are subject to change according to the model.

Electrical Work

1The supply voltage must be the same as the rated voltage of the air conditioner.

2Prepare the power souce for exclusive use with the air conditioner.

3Use 15 amperes time delay fuse or circuit breaker.

MODEL

AS07✴✴MA

AS09✴✴MA

AS12✴✴MC

 

 

 

 

 

 

 

Power supply

115V~/60Hz

 

115V~/60Hz

208-230V~/60Hz

 

 

 

Single phase

 

Single phase

Single phase

 

 

 

 

 

 

Power cable

 

 

3G AWG 14

 

 

 

 

 

Assembly cable

2G AWG 14 + 2G AWG 18

 

 

 

 

 

 

 

Operating current(C)

6.4

 

 

8.5

6.1

 

 

 

 

 

 

Starting Current

32A

 

47A

31A

 

 

 

 

 

 

Power consumption (C)

680W

 

900W

1320W

 

 

 

 

 

 

 

 

 

 

 

MODEL

AS18✴✴RC

 

AS24✴✴RC

 

 

 

 

 

 

 

Power supply

208-230V~/60Hz

 

208-230V~/60Hz

 

 

 

Single phase

 

 

Single phase

 

 

 

 

 

 

Power cable

 

 

3G AWG 12

 

 

 

 

 

 

Assembly cable

3G AWG 14 + 2G AWG 18

 

4G AWG 14 + 2G AWG 18

 

 

 

 

 

 

Operating current(C)

8.6A

 

 

 

10.5A

 

 

 

 

 

 

Starting Current

35A

 

 

 

10.5A

 

 

 

 

 

 

Power consumption (C)

1900W

 

 

 

2350W

 

 

 

 

 

 

 

When using the special NFB, use the NFB to bear the capacity of the air conditioner.

E-38

Otherwise, the shot circuit in the NFB may occur.

 

Image 38
Contents Installation Manual Manual DE Instrucciones Safety Precautions Contents View of the Unit Indoor UnitOutdoor Unit Remote Control Buttons and Display Getting Started Inserting the Remote Control Batteries Way Function Using with the indoor unitSelecting with the Remote Control To obtain anSelecting the Automatic Operating Mode Cooling Your Room Changing the Room Temperature Quickly Removing Excess Humidity Airing Your Room Adjusting the Air Flow Direction Vertically Adjusting the Air Flow Direction HorizontallySetting the On Timer To Cancel the On TimerSetting the Off Timer To Cancel the Off TimerSetting the Sleep Timer To Cancel the Sleep TimerOperating Recommendations Topic RecommendationIf the air conditioner is used at... Then Temperature and Humidity RangesMode Outdoor Temperature Indoor Temperature Indoor Humidity Cleaning Your Air Conditioner Model AS07A5A6MA / AS09A5A6MA / AS12A5A6MCSolving Common Problems AUTO, CoolInstalling a Filter Option Technical Specifications ModelOutdoor Unit Installation Manual Electrical Work Deciding on Where to Install the Air Conditioner Indoor Unit30mm1inch or more Accessories in the Outdoor Unit Case Air Conditioner and AccessoriesAccessories in the Indoor Unit Case Fixing the Installation Plate Then follow StepsConnecting the Assembly Cable Purging the Unit07/09/12 Installing and Connecting the Indoor Unit Drain Hose To install the drain hose, proceed as followsTorque Installing and Connecting the Indoor Unit Assembly PipingPipe Cutting/Extending the Piping Depth a18/24 Connecting the Cables to the Outdoor Unit07/09 Auxiliary Circuit Breaker Electrical WorkChecking Correct Earthing 5019Fixing the Unit in Position Connecting Up and Purging the Circuit If you have used ThenTo check for gas leaks on Then, using a leak detector Check Performing Leak TestsPlacing the Indoor Unit in Position Checking and Testing Operations Explaining Operations to the Owner Electronics