INSTALLING THE OUTDOOR UNIT
Auxiliary Circuit Breaker
Outdoor unit | Distribution | ||
| board | ||
|
| ||
|
|
|
|
|
|
|
|
Auxiliary power s/w
◆Auxiliary circuit breaker should be installed near outdoor unit so that each access is possible. Main/outdoor power supply cable are connected to upper/lower terminal of auxiliary circuit breaker.
◆It is necessary that the conduit kit for power supply to the outdoor unit be installed between auxiliary power S/W and the outdoor unit. (the conduit kit is optional)
❊The designs and shape are subject to change according to the model.
Electrical Work
1The supply voltage must be the same as the rated voltage of the air conditioner.
2Prepare the power souce for exclusive use with the air conditioner.
3Use 15 amperes time delay fuse or circuit breaker.
MODEL | AS07✴✴MA | AS09✴✴MA | AS12✴✴MC | |||
|
|
|
|
|
|
|
Power supply | 115V~/60Hz |
| 115V~/60Hz | |||
|
| |||||
| Single phase |
| Single phase | Single phase | ||
|
|
|
|
|
| |
Power cable |
|
| 3G AWG 14 |
| ||
|
|
|
| |||
Assembly cable | 2G AWG 14 + 2G AWG 18 | |||||
|
|
|
|
|
|
|
Operating current(C) | 6.4 |
|
| 8.5 | 6.1 | |
|
|
|
|
|
| |
Starting Current | 32A |
| 47A | 31A | ||
|
|
|
|
|
| |
Power consumption (C) | 680W |
| 900W | 1320W | ||
|
|
|
|
|
| |
|
|
|
|
| ||
MODEL | AS18✴✴RC |
| AS24✴✴RC | |||
|
|
|
|
|
|
|
Power supply |
| |||||
|
| |||||
| Single phase |
|
| Single phase | ||
|
|
|
|
|
| |
Power cable |
|
| 3G AWG 12 |
| ||
|
|
|
|
| ||
Assembly cable | 3G AWG 14 + 2G AWG 18 |
| 4G AWG 14 + 2G AWG 18 | |||
|
|
|
|
|
| |
Operating current(C) | 8.6A |
|
|
| 10.5A | |
|
|
|
|
|
| |
Starting Current | 35A |
|
|
| 10.5A | |
|
|
|
|
|
| |
Power consumption (C) | 1900W |
|
|
| 2350W | |
|
|
|
|
|
|
|
➢When using the special NFB, use the NFB to bear the capacity of the air conditioner.
➢ Otherwise, the shot circuit in the NFB may occur. | |
|