
INSTALLING THE INDOOR UNIT
Cutting/Extending the Piping
Five metres(16ft 5in) of piping is supplied with the air conditioner(Optional). This length can if necessary be:
◆Extended to a maximum of “L” m/ft.
◆Shortened as required
☛If more than 5m(16ft 5in) of piping is required:
◆The assembly cable must also be extended
◆Refrigerant must be added to the circuit by an approved installer; otherwise, the indoor unit may freeze
1 Make sure that you have the required tools available (pipe cutter, reamer, flaring tool and pipe holder).
2If you wish to shorten the piping, cut it using a pipe cutter, taking care to
ensure that the cut edge remains at a 90° angle with the side of the pipe, and referring to the illustrations below for examples of edges cut correctly and incorrectly.
90O  | Oblique  | Rough  | Burr  | 
O  | x  | x  | x  | 
3 To prevent any gas from leaking out, remove all burrs at the cut end of the pipe, using a reamer.
4Slide a flare nut on to the pipe and modify the flare.
Pipe | Outer Diameter (D)  | Depth (A) | 
Liquid refrigerant  | 6.35 mm(1/4˝)  | 1.3 mm(1/16˝)  | 
Gas refrigerant  | 9.52 mm(3/8˝)  | 1.8 mm(1/16˝)  | 
Gas refrigerant  | 12.70 mm(1/2˝)  | 2.0 mm(1/16˝)  | 
Gas refrigerant  | 15.88 mm(5/8˝)  | 2.2 mm(1/8˝)  | 
5Check that the flaring is correct, referring to the illustrations below for examples of incorrect flaring.
Inclined  | Damaged Surface  | Cracked  | Uneven Thickness  | 
6 Align the pipes to be connected and tighten the flare nuts first manually and then with a wrench, applying the following torque.
Pipe | Outer Diameter  | Torque | 
Liquid refrigerant  | 6.35 mm(1/4˝)  | 160kg•cm(11.6ft•lb )  | 
Gas refrigerant  | 9.52 mm(3/8˝)  | 300kg•cm(21.8ft•lb )  | 
Gas refrigerant  | 12.70 mm(1/2˝)  | 500kg•cm(36.4ft•lb )  | 
Gas refrigerant  | 15.88 mm(5/8˝)  | 700kg•cm(50.6ft•lb )  | 
7For further details on how to connect up to the outdoor unit and purge the circuit, refer to page 41.