ADAPTER CONNECTION | INITIAL SETTING |
CAMERA ADDRESS SETUP
Use SW701, SW702, or 703 for Camera Address setup. You may allocate up to 255 addresses by using SW701 to set the 3rd digit, SW702 the 2nd digit, and SW703 the 1st digit.
EX) In case of Camera Address 1, see the following figure for setup.
SCC-C6407(P) Adapter BOARD
SW701 SW702 SW703
Setting communication Protocol
Use number 1~4 PIN of SW704 to set communication Protocol.
E
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| PIN | PIN1 | PIN2 | PIN3 | PIN4 |
|
|
|
|
|
|
| Comp | ||||
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
| A | OFF | OFF | OFF | OFF |
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
| B | ON | OFF | OFF | OFF |
|
|
|
|
|
|
| C | OFF | ON | OFF | OFF |
|
|
|
|
|
|
| D | ON | ON | OFF | OFF |
|
|
|
|
|
|
| E | OFF | OFF | ON | OFF |
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
| F | ON | OFF | ON | OFF |
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
| G | OFF | ON | ON | OFF |
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
| H | ON | ON | ON | OFF |
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
| I | OFF | OFF | OFF | ON |
|
|
|
|
|
|
| J | ON | OFF | OFF | ON |
|
|
|
|
|
|
| K | OFF | ON | OFF | ON |
|
|
|
|
|
|
| L | ON | ON | OFF | ON |
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
| M | OFF | OFF | ON | ON |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| N | ON | OFF | ON | ON |
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| O | OFF | ON | ON | ON |
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| P | ON | ON | ON | ON |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
A : SAMSUNG HALF
B : SAMSUNG FULL
SEE INSTRUCTION MANUAL
ON 1 2 3 4 5 6 7 8
SW704
(x100) (x10) (x1)
SW701 SW702 SW703
(BOTTOM VIEW)
Baud Rate Setting
Use PIN 5 and 6 of SW704.
1 2 3 4 5 6 7 8
ON
OFF
SW 704
BAUD RATE | PIN 5 | PIN 6 |
4800 BPS | ON | ON |
9600 BPS | OFF | ON |
|
|
|
19200 BPS | ON | OFF |
|
|
|
38400 BPS | OFF | OFF |
The factory default setting is set to 9600BPS. |