Device state
Address |
| Data type |
|
|
|
| Access |
|
|
|
|
|
| Parameter |
|
|
|
| ||||
0x0200 |
| word |
|
|
|
|
| R / O |
|
| Outputs and states |
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| B15 | B14 | B13 |
| B12 | B11 |
| B10 | B9 | B8 |
| B7 | B6 | B5 |
| B4 | B3 | B2 |
| B1 | B0 | |
| B8 | Hysteresis limitation |
|
|
|
| B0 | Output 1 off |
|
|
|
|
|
| ||||||||
|
| (for remote operation) |
|
|
|
| B1 | Output 3 off |
|
|
|
|
|
| ||||||||
| B9 | Management system off |
|
|
| B2 | Output 2 off |
|
|
|
|
|
| |||||||||
|
| (for remote operation) |
|
|
|
| B3 | Output 4 off |
|
|
|
|
|
| ||||||||
| B10 |
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
| B11 | Second setpoint active |
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
| B12 | Measured value range crossing input 1 |
|
|
|
|
|
|
|
|
|
| ||||||||||
| B13 | Measured value range crossing input 2 |
|
|
|
|
|
|
|
|
|
| ||||||||||
| B14 | Measured value range crossing input 3 |
|
|
|
|
|
|
|
|
|
| ||||||||||
| B15 | Reserved |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||
0x0201 |
| word |
|
|
|
|
| R / O |
|
| Binary signal and hardware identification |
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
| B15 | B14 | B13 |
| B12 | B11 |
| B10 | B9 | B8 |
| B7 | B6 | B5 |
| B4 | B3 | B2 |
| B1 | B0 | |
| B15 | Reserved |
|
|
|
|
|
|
|
| B0 | Operating mode |
|
| ||||||||
| B14 | Interface present |
|
|
|
| B1 | Manual operation active |
|
|
|
| ||||||||||
| B13 | Analog output present |
|
|
|
| B2 | Binary input 1 closed |
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| B3 | Binary input 2 closed |
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
| B4 | Thermostat function active |
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
| B5 | First controller output active |
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
| B6 | Second controller output active |
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
| B7 | Limit comparator active |
|
|
|
|
| 11/14 |
|
|
Siemens Building Technologies | CC1A7865.1en |
HVAC Products | 31.10.2002 |