Siemens RS-485 Data query sequence, Time sequence, Communication during the slave’s response time

Page 4

Data query sequence

Time sequence

The time sequence of a data query looks as follows:

Master

Data query

Data query

Slave

Reply

7865z12e/1102

t0

t1

t0

t2

t0 Identification of end = 3 characters (time is dependent on the Baud rate)

t1 This time is dependent on internal handling. The maximum handling time is 250 ms

t2 This is the time required by the device to switch from the transmitting mode back to the receiving mode.

This time must be observed by the master before it makes a new data query. It must always be maintained, even if the new data query is sent to some other device.

t2 ￿ 20 ms

Communication during the slave’s internal handling time

The master is not allowed to make any data queries during the slave’s internal handling time.

Data queries made during that period of time will be ignored by the slave.

Communication during the slave’s response time

The master is not allowed to make any data queries during the slave’s response time. Data queries made during that period of time cause all data currently on the bus to become obsolete.

4/14

Siemens Building Technologies

CC1A7865.1en

HVAC Products

31.10.2002

Image 4
Contents Master-slave principle 31.10.2002Not Transmission mode RTUDevice address Communication sequence Reply by the slaveBaud rate 600 813 19.200 406Data query sequence Time sequenceCommunication during the slave’s internal handling time Communication during the slave’s response timeFault handling Slave addressFunction code Data fieldChecksum CRC16 CRC = SHR CRCReply CRC16 = Following functions for the device will be availableReading n words Writing 1 wordExample Write switch-on threshold Hys1 = Word address = Writing n words InstructionReply AddressAccess Parameter Address Data Access Parameter Value range DefaultAddress tables Temp REMRoff SetpointAddress Data type Access Parameter Device state«FULLY REMOTE» SPR Description of operating modesRemote RK1 Operating mode Dependent switching Control strategy forFloating output with Modulating burner