Page 8

Writing n words

Instruction

Slave

 

Function

 

Address

Number of

 

Number of

 

 

Word

 

Check-

 

address

 

0x10

 

of first

 

 

words

 

 

 

bytes

 

 

value(s)

 

sum

 

 

 

 

 

 

 

 

 

 

word

 

 

 

 

 

 

(max. 2)

 

 

 

 

 

 

 

CRC16

 

1 byte

 

1 byte

 

2 bytes

 

 

2 bytes

 

 

 

1 byte

 

 

x byte(s)

 

2 bytes

Reply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Slave address

 

Function 0x10

 

Address of

 

Number of

 

 

Checksum

 

 

 

 

 

 

 

 

 

 

 

 

 

first word

 

words

 

 

 

CRC16

 

 

1 byte

 

 

 

 

1 byte

 

 

2 bytes

 

 

 

2 bytes

 

 

 

2 bytes

Example

Write switch-on threshold (Hys1 = -10)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Word address = 0x0018

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Instruction:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0B

 

10

 

00

 

18

 

00

 

02

 

04

 

00

 

00

 

C1

 

20

 

 

CRC16

 

Reply:

0B

10

00

18

00

02

CRC16

Data type “char“

The high byte must be transmitted first.

 

 

Example: Configuration code C111: “9030“

 

MOD bus:

0B10 0024 00 02 04 0903

Data type “float“

The following explanations apply under the condition that the master works with the

 

IEEE-754 format. Before transmitting a value, the bytes must be exchanged in a way

 

that the order corresponds to the presentation for the MOD bus (see illustration below).

M-23 bit normalized mantissa

E-exponent (complement to base 2)

S-Sign-bit; 1 = negative, 0 = positive

MOD-BusMMMMMMMM MMMMMMMM SEEEEEEE EMMMMMMM

Read

Master

SEEEEEEE EMMMMMMM MMMMMMMM MMMMMMMM

(IEEE 754)

7865z13e/1102

Write

Example:

 

Transmission of decimal value “550“:

 

MOD bus:

0x80, 0x00, 0x44, 0x09

Following is a description of all process values (variables) with their addresses, data type and type of access.

Where:

 

R / O

Read only access

R / W

Read and write access

float

Float value (4 bytes / 2 words)

word

Integer (2 bytes / 1 word)

The process values are subdivided into logic areas.

8/14

Siemens Building Technologies

CC1A7865.1en

HVAC Products

31.10.2002

Image 8
Contents Master-slave principle 31.10.2002Device address Transmission mode RTUNot Communication sequence Reply by the slaveBaud rate 600 813 19.200 406Data query sequence Time sequenceCommunication during the slave’s internal handling time Communication during the slave’s response timeFault handling Slave addressFunction code Data fieldChecksum CRC16 CRC = SHR CRCReply CRC16 = Following functions for the device will be availableReading n words Writing 1 wordExample Write switch-on threshold Hys1 = Word address = Writing n words InstructionReply AddressAddress tables Address Data Access Parameter Value range DefaultAccess Parameter Temp REMRoff SetpointAddress Data type Access Parameter Device stateRemote RK1 Description of operating modes«FULLY REMOTE» SPR Operating mode Dependent switching Control strategy forFloating output with Modulating burner