Mudulating burner | Modulating controller: |
| The management system predefines the value (degree of modulation) for the analog |
| output via «RY». |
| Setting the «RK2» and «RK3» by the management system has no impact. |
| Both relays «K2» and «K3», are deenergized. |
| Floating step controller: |
| The management system controls the actuator («RK2» and «RK3», relays «K2» / |
| «K3»). |
| Setting the «RY» by the management system has no impact. In that case, the analog |
| output delivers 0 V or 0 / 4 mA. |
| The RWF40... always checks to ensure that «RK2» and «RK3» (opening / closing) are |
| not activated simultaneously. In such a case, the response is «K2 = K3 = deener- |
| gized». |
| If both relay contacts change their position during the controller’s sequence time, the |
| output is «K2 = K3 = deenergized». This time contact interval («K2 = K3 = off» for one |
| scanning time) is also permitted in |
Control strategy for | The remote relay commands «RK2» and «RK3» (relays «K2» / «K3») control the |
floating output with | opening and closing travel of the controlling element. Using parameter «RSTEP», the |
modulating burner | management system predefines the required number of control cycles. |
operation | Output «K2» (opening) is controlled by a travel command and a positive number. |
| Output «K3» (closing) is controlled by a travel command and a negative number. |
| The number gives the number of RWF40... scanning cycles (210 ms) with which the |
| output is controlled. |
| The travel command with number 0 deenergizes immediately «K2» and «K3». |
| If a new travel command is given before the control time has elapsed, the RWF40... |
| ascertains the direction of rotation requested by the command. If the direction of rota- |
| tion does not change, the control time will immediately be replaced by the new value. If |
| the direction of rotation must be reversed, the controlled output will be dactivated and, |
| for the next scanning cycle, the appropriate control time is used (time contact interval). |
| If, simultaneously with the control strategy for the floating output, outputs «K2» and |
| «K3» (via «RK2» and «RK3») are directly set by the management system, the relay |
| information from the control strategy and output information «K2» and «K3» have a |
| logic «OR» connection. «RK2» and «RK3» (opening / closing) must never be energized |
| simultaneously. In such a case, the response is «K2 = K3 = denergized». |
Supervision of actual | In operating mode «FULLY REMOTE», the management system ensures burner con- |
value by setpoint- | trol. The RWF40... monitors the actual value to make certain the switching hystereses |
dependent switching | will be observed. |
thresholds | If the actual value crosses the upper |
| be locked (status flag, «Management system locked» can be read via the interface). |
| The management system is released again when the actual value returns to a level |
| below the |
| If supervision of the actual value is not desired, the switching hystereses in the |
| RWF40... must be set to the respective maximum value. |
| In operating mode «REMOTE SETPOINT», the control algorithm ensures this kind of |
| supervision. |