Siemens RS-485 manual Control strategy for, Floating output with, Modulating burner, Operation

Page 14

Mudulating burner

Modulating controller:

 

The management system predefines the value (degree of modulation) for the analog

 

output via «RY».

 

Setting the «RK2» and «RK3» by the management system has no impact.

 

Both relays «K2» and «K3», are deenergized.

 

Floating step controller:

 

The management system controls the actuator («RK2» and «RK3», relays «K2» /

 

«K3»).

 

Setting the «RY» by the management system has no impact. In that case, the analog

 

output delivers 0 V or 0 / 4 mA.

 

The RWF40... always checks to ensure that «RK2» and «RK3» (opening / closing) are

 

not activated simultaneously. In such a case, the response is «K2 = K3 = deener-

 

gized».

 

If both relay contacts change their position during the controller’s sequence time, the

 

output is «K2 = K3 = deenergized». This time contact interval («K2 = K3 = off» for one

 

scanning time) is also permitted in 2-stage operation.

Control strategy for

The remote relay commands «RK2» and «RK3» (relays «K2» / «K3») control the

floating output with

opening and closing travel of the controlling element. Using parameter «RSTEP», the

modulating burner

management system predefines the required number of control cycles.

operation

Output «K2» (opening) is controlled by a travel command and a positive number.

 

Output «K3» (closing) is controlled by a travel command and a negative number.

 

The number gives the number of RWF40... scanning cycles (210 ms) with which the

 

output is controlled.

 

The travel command with number 0 deenergizes immediately «K2» and «K3».

 

If a new travel command is given before the control time has elapsed, the RWF40...

 

ascertains the direction of rotation requested by the command. If the direction of rota-

 

tion does not change, the control time will immediately be replaced by the new value. If

 

the direction of rotation must be reversed, the controlled output will be dactivated and,

 

for the next scanning cycle, the appropriate control time is used (time contact interval).

 

If, simultaneously with the control strategy for the floating output, outputs «K2» and

 

«K3» (via «RK2» and «RK3») are directly set by the management system, the relay

 

information from the control strategy and output information «K2» and «K3» have a

 

logic «OR» connection. «RK2» and «RK3» (opening / closing) must never be energized

 

simultaneously. In such a case, the response is «K2 = K3 = denergized».

Supervision of actual

In operating mode «FULLY REMOTE», the management system ensures burner con-

value by setpoint-

trol. The RWF40... monitors the actual value to make certain the switching hystereses

dependent switching

will be observed.

thresholds

If the actual value crosses the upper switch-off threshold, the management system will

 

be locked (status flag, «Management system locked» can be read via the interface).

 

The management system is released again when the actual value returns to a level

 

below the switch-on threshold.

 

If supervision of the actual value is not desired, the switching hystereses in the

 

RWF40... must be set to the respective maximum value.

 

In operating mode «REMOTE SETPOINT», the control algorithm ensures this kind of

 

supervision.

 

￿2002 Siemens Building Technologies

14/14

Subject to change!

 

 

Siemens Building Technologies

CC1A7865.1en

HVAC Products

31.10.2002

Image 14
Contents Master-slave principle 31.10.2002Device address Transmission mode RTUNot Baud rate Communication sequenceReply by the slave 600 813 19.200 406Communication during the slave’s internal handling time Data query sequenceTime sequence Communication during the slave’s response timeFunction code Fault handlingSlave address Data fieldReply CRC16 = Checksum CRC16CRC = SHR CRC Following functions for the device will be availableReading n words Writing 1 wordReply Example Write switch-on threshold Hys1 = Word address =Writing n words Instruction AddressAddress tables Address Data Access Parameter Value range DefaultAccess Parameter Roff TempREM SetpointAddress Data type Access Parameter Device stateRemote RK1 Description of operating modes«FULLY REMOTE» SPR Operating mode Floating output with Dependent switchingControl strategy for Modulating burner