Device data
Address | Data | Access |
| Parameter | Value range | Default | |
| type |
|
|
|
|
| value |
0x0300 | word [13] | R / O | Device data |
|
|
|
|
0x0300 |
|
| char SWVersion [11+1] | Software version |
|
| |
0x0306 |
|
| char VDNNr [13+1] | VdN number |
|
| |
Remote operation |
|
|
|
|
|
| |
|
|
|
|
|
|
| |
Address | Data | Access |
| Parameter | Value range | Default | |
| type |
|
|
|
|
| value |
0x0400 | float | R / O | TEMP | Actual value E3 (unfiltered) |
|
| |
|
|
|
|
|
|
| |
0x0500 | word | R / W | REM | Activation remote operation | 0...2 * | 0 | |
0x0501 | word | R / W | ROFF | Controller OFF in REMOTE | 0...1 ** | 0 | |
|
|
|
| SETPOINT |
|
| |
0x0502 | float | R / W | RHYS1 | HYS1 | |||
0x0504 | float | R / W | RHYS2 | 0...RHYS3 | HYS2 | ||
|
|
|
| REMOTE |
|
| |
0x0506 | float | R / W | RHYS3 | 0...9999 | HYS3 | ||
0x0508 | float | R / W | SPR | Setpoint REMOTE | SPL...SPH | SP1 | |
|
|
|
|
|
|
| |
0x050A | word | R / W | RK1 | Burner control remote operation | 0...1 | 0 | |
0x050B | word | R / W | RK2 | Relay K2 remote operation | 0...1 | 0 | |
0x050C | word | R / W | RK3 | Relay K3 remote operation | 0...1 | 0 | |
0x050D | word | R / W | RK6 | Relay LK remote operation | 0...1 | 0 | |
0x050E | word | R / W | RSTEP | Step control remote operation | 0 | ||
0x050F | float | R / W | RY | Positioning output remote | 0...100 | 0 | |
|
|
|
| operation |
|
| |
* 0 = local |
|
| ** 1 = controller OFF |
|
| ||
1 = remote setpoint |
|
|
|
|
| ||
2 = fully remote |
|
|
|
|
|
|
10/14
Siemens Building Technologies | CC1A7865.1en |
HVAC Products | 31.10.2002 |