Siemens RS-485 manual Communication sequence, Reply by the slave, Baud rate, 600 813 19.200 406

Page 3

Communication sequence

Process

Both the start and end of a data block are characterized by transmission pauses. The maximum period of time that may elapse between 2 successive characters is 3 times the period of time required for the transmission of one character.

The character transmission time (period of time required for the transmission of 1 char- acter) is dependent on the Baud rate and the type of data format.

Using a data format of 8 data bits, no parity bit and 1 stop bit, the character transmis- sion time is calculated as follows:

Character transmission time [ms] = 1000 * 9 bits / Baud rate

Data query by the master

Transmission time = n characters * 1000 * x bits / Baud rate

Identification of end of data query

3 characters * 1000 * x bits / Baud rate

Handling of data query by the slave (￿ 250 ms)

 

 

 

Reply by the slave

 

 

Transmission time = n characters * 1000 * x bits / Baud rate

 

 

 

 

 

 

 

 

 

Identification of end of reply

 

 

 

3 characters * 1000 * x bits / Baud rate

 

Example

Identification of the data query or end of the reply with a data format of 10 / 9 bits.

 

Waiting time = 3 characters * 1000 * x bits / Baud rate

 

 

 

 

 

 

 

 

Baud rate

 

Data format [bits]

 

Waiting time [ms]

 

9.600

 

9

 

2.813

 

19.200

 

9

 

1.406

 

3/14

 

 

Siemens Building Technologies

CC1A7865.1en

HVAC Products

31.10.2002

Image 3
Contents 31.10.2002 Master-slave principleTransmission mode RTU NotDevice address 600 813 19.200 406 Communication sequenceReply by the slave Baud rateCommunication during the slave’s response time Data query sequenceTime sequence Communication during the slave’s internal handling timeData field Fault handlingSlave address Function codeFollowing functions for the device will be available Checksum CRC16CRC = SHR CRC Reply CRC16 =Writing 1 word Reading n wordsAddress Example Write switch-on threshold Hys1 = Word address =Writing n words Instruction ReplyAddress Data Access Parameter Value range Default Access ParameterAddress tables Setpoint TempREM RoffDevice state Address Data type Access ParameterDescription of operating modes «FULLY REMOTE» SPRRemote RK1 Operating mode Modulating burner Dependent switchingControl strategy for Floating output with