Alliance Laundry Systems WFF135, WFF75, WFF100, WFF65, WFF165 Electrical Installation

Page 31

4

Electrical Installation

Important

Electrical ratings are subject to changes. Refer to serial plate decal for electrical ratings information specific to your machine.

WARNING

Hazardous Voltage. Can cause shock, burn or cause death. Allow machine power to remain off for two minutes prior to working in and around AC inverter drive.

WARNING

Hazardous Voltage. Can cause shock, burn or death. Verify that a ground wire from a proven earth ground is connected to the lug near the input power block on this machine.

The AC inverter drive requires a clean power supply free from voltage spikes and surges. If a transformer or generator is connected to the building's power supply, always install line reactors before the terminal block connections to the machine. A voltage monitor should be used to check incoming power. The customer’s local power company may provide such a monitor.

If input voltage measures above 240V for a 220V drive or above 480V for a 400V drive, ask the power company to lower the voltage. As an alternative, a step-down transformer kit is available from the distributor.

The AC drive provides overload protection for the drive motor. However, a separate single or three-phase circuit breaker must be installed for complete electrical overload protection. This prevents damage to the motor by disconnecting all legs if one should be lost accidentally. Check the data plate on the back of the washer-extractor or consult Table 2 through 7 for circuit breaker requirements.

IMPORTANT: Do NOT use fuses in place of a circuit breaker.

For installation in the United States or Canada, branch circuit protection must be provided according to National and Local Codes. The branch circuit breaker must be of the inverse time or instantaneous trip type at the values given in the technical specifications for each machine.

Use a circuit breaker of the minimal type of 10kA interrupt current.

CAUTION

Do not use a voltage or phase converter on any variable speed machine.

The washer-extractor should be connected to an individual branch circuit not shared with lighting or another electrical device.

-In accordance with legal regulations, every machine must be protected with an earth leakage circuit breaker of 30mA.

-The earth leakage circuit breaker, which one uses, must be of the type SI.

-For countries outside the European Community, the usual safety instructions must be observed.

31

Image 31
Contents Washer Extractors Page Contents Internal connections of the electrical heating  WFF65 WFF75 Model NumbersPage Page Safety Safety and Environmental InformationsDisposal of Unit EnvironmentalExplanation of Safety Messages Important Safety Instructions Page Operator Safety Technical data WFF65, IWF065, IWF014, CWF065, CWF014 Technical data and dimensionsDimensions WFF65, IWF065, IWF014, CWF065, CWF014 Technical data WFF75, IWF074, IWF018, CWF074, CWF018 Dimensions WFF75, IWF074, IWF018, CWF074, CWF018 Technical data WFF100, IWF100, IWF025, CWF100, CWF025 Dimensions WFF100, IWF100, IWF025, CWF100, CWF025 Technical data WFF135, IWF135, IWF030, CWF135, CWF030 Dimensions WFF135, IWF135, IWF030, CWF135, CWF030 Technical data WFF165, IWF165, CWF165 Dimensions WFF165, IWF165, CWF165 Directly on the ground Installation and Connection InstructionsSurface Anchoring on a metal base273 560 645 287 550 660 233 560 645.1 327 550 660 233 660 29.33 16.81 745 427 550 260 670 731 410 640 780 260 770 831 510 640 780 Water drain Water connectionImportant Do not use fuses in place of a circuit breaker Electrical InstallationGrounding Instructions Machine Power Cable Connections Main power connectionConnection label Page Alternative Electric Heat Options Boiler Fed/Steam Heat Electric HeatLiters / 18 pounds Liters / 25 pounds Liters / 30 pounds Liters / 35 pounds Electrical Specifications WFF165, IWF165, CWF165Connection of the liquid soap hoses Liquid soap connection optionWith an external tension 24V DC See Label Label With direct steam injection into the machine See Table Steam connectionInternal connections of the electrical heating Technical remarksEnd of day General maintenance Periodical maintenance Maintenance instruction of the machineWFF165 Annual maintenanceWFF100 WFF135Nameplate Contact InformationNameplate Location Replacement Parts Repair and after-sales service