Alliance Laundry Systems WFF65, WFF75, WFF135, WFF100 Main power connection, Connection label

Page 33

4

Main power connection

Label 4

Connection label:

Machine power connections are made at the back of the machine. Three or four conductor power cable is the recommended method (See chapter electrical specs for minimum cable requirements, if local electrical codes exceed these requirements, follow local codes). The number of conductors in this cable and the proper connection points for the cable wires shall be determined by the machine and power requirements. All machines must have a ground wire and be properly grounded. The ground wire must be insulated with a green/yellow color. This wire is normally within the power cable but can also be a separate wire run along side the power cable if properly sized.

Never run a machine that does not have a ground wire. This ground wire must be connected to the machine grounding lug found near the main switch. This lug is identified with the international “protective earth” symbol and the letters “PE”. Failure to connect this ground wire can lead to an unsafe machine condition leading to machine damage and/or operator injury or death. This wire must be connected to earth ground at far end.

Machine Power Cable Connections:

Remove main switch cover plate at back of machine (see chapter dimensions part (F)). Run power cable through the cabinet knock-out located directly below the cover plate. Before installing, obtain and install a cord-grip to hold the cable in place. Never rely upon the electrical connections to hold cable in place. Allow some slack in this cable outside of the machine to form a drip-loop between the supply power circuit breaker and the machine knock-out. Connect power cable wires as directed below. Always connect the

ground wire first and remove last.

Wiring based on the supply power and machine design (voltage/frequency):

440-480 Volts, 3-Phase, 3-wire or 4-wire + PE, 50 or 60 Hertz Configuration (Named: N-Voltage):

With supply power of: 440-480 Volts, 3-phase, 3-wire, after connecting the green/yellow PE ground wire,

connect one wire to each of the bottom terminals of the power contactor switch marked: “L1,L2,L3”. When this supply power has four wires, connect this 4th wire, identified as a neutral wire, to the bottom terminal of the auxiliary contactor on the power contactor switch marked: “N”. Connect the remaining power wires

as first noted.

380-415 Volts, 3-Phase, 4-wire + PE, 50 or 60 Hertz Configuration (Named: P-Voltage):

With supply power of: 380-415 Volts, 3-phase, 4-wire, after connecting the green/yellow PE ground wire, follow the directions of the four wire system for 440-480 Volt configuration.

33

Image 33
Contents Washer Extractors Page Contents Internal connections of the electrical heating  WFF65 WFF75 Model NumbersPage Page Safety Safety and Environmental InformationsDisposal of Unit EnvironmentalExplanation of Safety Messages Important Safety Instructions Page Operator Safety Technical data WFF65, IWF065, IWF014, CWF065, CWF014 Technical data and dimensionsDimensions WFF65, IWF065, IWF014, CWF065, CWF014 Technical data WFF75, IWF074, IWF018, CWF074, CWF018 Dimensions WFF75, IWF074, IWF018, CWF074, CWF018 Technical data WFF100, IWF100, IWF025, CWF100, CWF025 Dimensions WFF100, IWF100, IWF025, CWF100, CWF025 Technical data WFF135, IWF135, IWF030, CWF135, CWF030 Dimensions WFF135, IWF135, IWF030, CWF135, CWF030 Technical data WFF165, IWF165, CWF165 Dimensions WFF165, IWF165, CWF165 Surface Installation and Connection InstructionsAnchoring on a metal base Directly on the ground273 560 645 287 550 660 233 560 645.1 327 550 660 233 660 29.33 16.81 745 427 550 260 670 731 410 640 780 260 770 831 510 640 780 Water drain Water connectionImportant Do not use fuses in place of a circuit breaker Electrical InstallationGrounding Instructions Main power connection Machine Power Cable ConnectionsConnection label Page Alternative Electric Heat Options Boiler Fed/Steam Heat Electric HeatLiters / 18 pounds Liters / 25 pounds Liters / 30 pounds Liters / 35 pounds Electrical Specifications WFF165, IWF165, CWF165Connection of the liquid soap hoses Liquid soap connection optionWith an external tension 24V DC See Label Label With direct steam injection into the machine See Table Steam connectionInternal connections of the electrical heating Technical remarksEnd of day General maintenance Periodical maintenance Maintenance instruction of the machineWFF100 Annual maintenanceWFF135 WFF165Contact Information NameplateNameplate Location Replacement Parts Repair and after-sales service