| Electrical | Connection | 1. Disconnect power. |
Direct Wire) |
| • Strip 5 inches of outer covering from end of cable. | |
|
|
| Leave bare grounding wire at 5 inches. |
Fire Hazard
Use 10 gauge solid copper wire.
Use a UL approved strain relief.
Disconnect power before making electrical connections.
Connect neutral wire (white or center wire) to center terminal (silver).
Ground wire (green or bare wire) must be connected to green ground connector.
Connect remaining 2 supply wires to remaining 2 terminals (gold).
Securely tighten all electrical connections. Failure to follow these instructions can result in death, fire, or electrical shock.
•Cut 1 inch from 3 remaining insulated wires. Strip insulation back 1 inch. Shape the end of each wire into a "U" shaped hook.
2.Remove
Terminalblockcover Hold-downscrew
GROUNDING INSTRUCTIONS
This appliance must be connected to a grounded metal, permanent wiring system; or an equipment- grounding conductor must be run with the circuit conductors and connected to the equipment- grounding terminal or lead on the appliance.
SAVE THESE INSTRUCTIONS
The dryer can be connected directly to fused disconnect or circuit breaker box with
A conduit connector must be installed at junction box. Allow four feet of slack in the line so dryer can be moved if servicing is ever necessary.
3.Attach a
horizontal position. Put the direct wire cable through the strain relief.
4.Remove the center terminal block screw. Remove the neutral grounding wire (green/yellow wire) from external grounding screw.
External ground | Center |
| terminal blockscrew |
Green/yellow wire of harness
8