American Dryer Corp MDG31, MDG77 manual Fresh Air Supply Requirements, Exhaust Requirements

Page 13

Domestic Type I (MDG31, MDG51 Only)

A = 6-inches (15.24 cm)

B = 24-inches (60.96 cm)

EXAMPLE: For MDG51, 2 unrestricted openings measuring 6-inches by 24-inches (15.24 cm by 60.96 cm) are acceptable.

If a closet door is installed: unobstructed air openings are required. The air openings shall be located 3-inches (7.62 cm) from the lower opening (above floor level) and upper opening (below ceiling). The total free area of the air openings in the door shall not be less than 179 inch2 (1154.836 cm2) for MDG31; and 293 inch2 (1890.319 cm2) for MDG51. Louvered doors with equivalent air openings are acceptable.

No other fuel-burning appliance shall be installed in the same closet as the dryer.

Fresh Air Supply Requirements _______

When the dryer is operating, it draws in room air, heats it, passes this air through the tumbler, and exhausts it out of the building. Therefore, the room air must be continually replenished from the outdoors. If the make-up air is inadequate, drying time and drying efficiency will be adversely affected. Ignition problems and sail switch “fluttering” problems may result, as well as premature motor failure from overheating. The dryer must be installed with provisions for adequate combustion and make-up air supply.

Air supply (make-up air) must be given careful consideration to ensure proper performance of each dryer. As a general rule, an unrestricted air entrance from the outdoors of 110 inch2 (710 cm2) is required for each MDG77, 90 inch2 (580 cm2) for each MDG51, 55 inch2 (354 cm2) for each MDG31. (Based on 1 inch2 [6.5 cm2] per 1,000 Btu [252 kcal].)

It is not necessary to have a separate make-up air opening for each dryer. Common make-up air openings are acceptable. However, they must be set up in such a manner that the make-up air is distributed equally to all the dryers.

To compensate for the use of registers or louvers used over the openings, this area must be increased by approximately 33%. Make-up air openings should not be located in an area directly near where exhaust vents exit the building.

Allowances must be made for remote or constricting passageways or where dryers are located at high altitudes or predominantly low pressure areas.

Note

!Component failure due to dry cleaning solvent fumes will void the warranty.

A = 10-inches (25.4 cm)

B = 11-inches (27.94 cm)

EXAMPLE: For a bank of 4 MDG31 dryers, 2 unrestricted openings measuring 10-inches by 11-inches (25.4 cm by 27.94 cm) are acceptable.

Important

!Make-up air must be free of dry cleaning solvent fumes. Make-up air that is contaminated by dry

cleaning solvent fumes will result in irreparable damage to the motors and other dryer components.

Exhaust Requirements ________________

Exhaust ductwork should be designed and installed by a qualified professional. Improperly sized ductwork will create excessive back pressure, which results in slow drying, increased use of energy, and shutdown of the burner by the airflow (sail) switch, burner hi-limits, or lint chamber hi-limit protector thermostat. The dryer must be installed with a proper exhaust duct connection to the outside.

The dryer shall not be exhausted into any gas vent, chimney, wall, ceiling or concealed space of a building.

Caution

!This dryer produces combustible lint and must be exhausted to the outdoors.

Improperly sized or installed exhaust ductwork can create a potential fire hazard.

The ductwork should be laid out in such a way that the ductwork travels as directly as possible to the outdoors with as few turns as possible. There should be a minimum 6-inch (15.24 cm) clearance between the back guard and the first bend in the ductwork for ease of servicing. Single or independent dryer venting is recommended. It is suggested that the use of 90° turns be avoided; use 30° and/or 45° bends instead. The radius of the elbows should preferably be 1-1/2 times the diameter of the duct. All ductwork should be smooth inside with no projections from sheet metal screws or other obstructions, which will collect lint. When adding ducts, overlap the duct being connected. All ductwork joints must be taped to prevent moisture and lint from escaping into the building. Back draft dampers must be installed in all commonly ducted systems. Inspection doors should be installed at strategic points in the exhaust ductwork for periodic inspection and cleaning of lint from the ductwork.

Important

!It is recommended that exhaust or booster fans not be used in the exhaust ductwork system.

113430 - 9

Telephone: (641) 787-7000

13

Image 13
Contents MDG31 / MDG51 / MDG77 Installation/Operator Manual Retain This Manual in a Safe Place for Future Reference Table of Contents What To Do If You Smell Gas Safety PrecautionsCE only MDG31 Specifications MDG31 Specifications MDG51 Specifications MDG51 Specifications MDG77 Specifications MDG77 Specifications Unpacking/Setting Up Installation ProceduresLocation Requirements Dryer Enclosure RequirementsExhaust Requirements Fresh Air Supply RequirementsDomestic Type I MDG31, MDG51 Only Single Dryer Venting Outside Ductwork ProtectionHorizontal Venting Vertical VentingElectrical Requirements Electrical InformationSingle-Phase 1ø Wiring Connections/Hookup Electrical Service Specifications Gas Models OnlyGrounding Electrical ConnectionsCE Dryers Gas InformationMDG31 Piping/Connections Converting from One Family Gas to AnotherConversion from Natural Gas to Propane or Butane Gas Parts Required for ConversionUnregulated Gas Valve Non-CE DryersRegulated Gas Valve Conversion from Propane or Butane Gas to Natural GasGas Pressure Adjustment Gas Pressure TestingGas Pressure Test Procedure Water InformationPreoperational Test Preparation for Operation/Start-UpPreoperational Instructions Service/Parts InformationCoin Models Non-Coin ModelsRoutine Maintenance Warranty InformationData Label Information Days After Installation Every 12 Months ThereafterStandard Label CE Label 02/15/08