American Dryer Corp MDG31, MDG77 Gas Pressure Testing, Water Information, Gas Pressure Adjustment

Page 21

Converting from unregulated L.P. to unregulated natural gas: no change to the regulator is required.

Converting from regulated L.P. to regulated natural gas: remove the white plastic regulator adjustment screw (under vent cap). Remove spring under screw and replace with spring from kit (P/N 140415). Replace regulator adjustment screw.

Install the gas train back into the dryer gas train enclosure. Be sure the tab at the rear of the gas train engages into the mounting slot.

Connect the union and the 3 electrical plugs.

Open all shutoff valves, reconnect electrical power to the dryer, and test for leaks.

Operate the dryer through 1 complete cycle to ensure proper operation.

With dryer operating, check the manifold (burner) pressure at the tap on the gas valve to ensure proper operating pressure (refer to chart on page 18).

Gas Pressure Adjustment

Disconnect electrical power to the dryer.

Important

!The MDG51 and MDG77 will require that the following procedures be performed on both

burner assemblies.

To adjust gas valve’s internal regulator, remove the regulator vent cap with the regulator adjustment tool, which is located on the back guard between the gas inlet and exhaust outlet (refer to the illustration below for proper use of adjustment tool). Be sure to use one of the wide ends of the adjustment tool for removal of the vent cap. Once vent cap is removed, the narrow end of the adjustment tool can be used to turn the plastic adjustment screw in the valve. Turn the screw clockwise to raise pressure and counterclockwise to lower pressure.

Gas (burner) pressures are measured with the burner in operation for all burner adjustment conditions. Therefore once the necessary adjustments have been made, the dryer must be operated in a heating cycle to verify that the pressure is correct. If it is not correct, you must discontinue the power to the unit and make further adjustments. Repeat these steps as many times as necessary to achieve the correct burner pressure. Once the adjustment of the valve is complete, the vent cap must be replaced and sealed with, for example, paint to prevent maladjustment by the user.

Edge #1 for vent cap

Edge #2 for adjustment screw

Warning (CE Dryers)

!This appliance must only be operated with the gas type indicated on the dryer’s data plate. If the

appliance is converted (gas type changed), a data plate amendment must be obtained from Maytag.

Conversions done improperly can result in a fire or explosion!

Gas Pressure Testing _________________

For proper operation, the gas pressure must be correct, consistent and maintained at the gas pressure rates shown on page 18. Provisions are made at the gas valve for taking gas pressure readings.

There are 2 types of devices used to measure gas pressure. They are the spring/mechanical type gauge and the manometer. The use of the spring/mechanical type gauge is not recommended because they are very easily damaged and are not always accurate. The preferred type of gauge is the manometer because it is a simple device to use and is highly accurate. A manometer is simply a glass or transparent plastic tube with a scale graduated in inches or mb. When it is filled with water and pressure is applied, the water in the tube rises, showing the exact gas pressure.

Gas Pressure Test Procedure

Turn gas cock in gas supply line to “OFF” position.

50 Hz dryers: Back out miniature screw inside pressure tap and attach manometer (refer to the illustration on page 20).

60 Hz dryers: Install pressure tap and attach manometer (refer to the illustration on page 20).

Turn gas cock to “ON” position.

Start the dryer in Heat Mode and wait for ignition. Gas manifold pressure should be as shown on page 18.

If the gas pressure needs to be adjusted, refer to “Gas Pressure Adjustment” on this page.

Once test is complete, turn gas cock to “OFF” position. Remove manometer. Tighten screw inside the pressure tap or install plug.

Turn gas cock to “ON” position and check for leaks with soap solution with main burner “ON.”

Water Information _____________________

Before You Start

Check Local Codes and Permits

Call your local water company or the proper municipal authority for information regarding local codes.

Important

! It is your responsibility to have all plumbing connections made by a qualified professional to

ensure that the plumbing installation is adequate and conforms to local, state, and federal regulations or codes.

It is the installer’s or owner’s responsibility to see that the required water pressure, pipe size, or connections are provided. The manufacturer assumes no responsibility if the fire suppression system is not connected, installed, or maintained properly.

113430 - 9

Telephone: (641) 787-7000

21

Image 21
Contents MDG31 / MDG51 / MDG77 Installation/Operator Manual Retain This Manual in a Safe Place for Future Reference Table of Contents What To Do If You Smell Gas Safety PrecautionsCE only MDG31 Specifications MDG31 Specifications MDG51 Specifications MDG51 Specifications MDG77 Specifications MDG77 Specifications Unpacking/Setting Up Installation ProceduresLocation Requirements Dryer Enclosure RequirementsFresh Air Supply Requirements Exhaust RequirementsDomestic Type I MDG31, MDG51 Only Single Dryer Venting Outside Ductwork ProtectionHorizontal Venting Vertical VentingElectrical Requirements Electrical InformationSingle-Phase 1ø Wiring Connections/Hookup Electrical Service Specifications Gas Models OnlyGrounding Electrical ConnectionsCE Dryers Gas InformationMDG31 Piping/Connections Converting from One Family Gas to AnotherConversion from Natural Gas to Propane or Butane Gas Parts Required for ConversionUnregulated Gas Valve Non-CE DryersRegulated Gas Valve Conversion from Propane or Butane Gas to Natural GasGas Pressure Adjustment Gas Pressure TestingGas Pressure Test Procedure Water InformationPreoperational Test Preparation for Operation/Start-UpPreoperational Instructions Service/Parts InformationCoin Models Non-Coin ModelsRoutine Maintenance Warranty InformationDays After Installation Every 12 Months Thereafter Data Label InformationStandard Label CE Label 02/15/08