American Dryer Corp ML-130 II Reversing, 3ø GAS ML-130 II Reversing, 3ø Steam

Page 27

2.Electrical Service Specifications

ML-130 II Reversing, 3ø (GAS) ML-130 II Reversing, 3ø (STEAM)

ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)

IMPORTANT: 208 VAC AND 230/240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.

NOTES: A . When fuses are used they must be dual element, time delay, current limiting, class RK1 or RK5 ONLY. Calculate/determine correct fuse value, by applying either local and/or National Electrical Codes to listed appliance amp draw data.

B. Circuit breakers are thermal-magnetic (industrial) motor curve type ONLY. For others, calculate/verify correct breaker size according to appliance amp draw rating and type of breaker used.

C. Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.

SERVICE

 

WIRE

APPROX.

MINIMUM

FUSING

CIRCUIT

PHASE

Dual Element

AMP DRAW

BREAKER

VOLTAGE

SERVICE

WIRE SIZE

Time Delay

 

 

 

 

 

 

 

 

60 Hz

50 Hz

 

60 Hz

50 Hz

60 Hz

50 Hz

208

3

13.7

13.7

*

20

20

20

20

 

 

 

 

 

 

 

 

 

 

230/240

3

12.5

12.8

*

20

20

20

20

380-400

3/4

---

7.3

*

---

15

---

15

 

 

 

 

 

 

 

 

 

 

416

3/4

---

7.2

*

---

15

---

15

 

 

 

 

 

 

 

 

 

 

460

3/4

7.2

---

*

15

---

15

---

 

 

 

 

 

 

 

 

 

 

480

3/4

7.2

---

*

15

---

15

---

 

 

 

 

 

 

 

 

 

 

575

3

6.3

---

*

15

---

15

---

 

 

 

 

 

 

 

 

 

 

*AWG Stranded Type Wire ... size wire as per National Electrical Code or local codes. (Motor lead type wire is recommended).

IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is affixed to the left side panel/wall area behind the control door. In the case of 208 VAC or 230/240 VAC, the supply voltage must match the electric service specifications of the data label exactly.

WARNING: 208 VAC AND 230/240 VAC ARE NOT THE SAME. Any damage done to dryer components due to improper voltage connections will automatically VOID THE WARRANTY.

NOTE: ADC reserves the right to make changes in specifications at any time without notice or obligation.

23

Image 27
Contents ML-130 Retain This Manual In a Safe Place For Future Reference For Your Safety Page Table of Contents Section Routine Maintenance Receiving and Handling Important InformationWhat to do if YOU Smell GAS Safety PrecautionsStandards Specifications SPECIFICATIONS/COMPONENT IdentificationSpecifications Component Identification Page Location Requirements Installation ProceduresUNPACKING/SETTING UP Page This Exhaust Duct Transition Piece Must be Installed First Dryer Enclosure Requirements Fresh AIR Supply Requirements Exhaust Requirements Page Downstream of Dryer Page Page Page Electrical Information ML-130 II Reversing, 3ø GAS ML-130 II Reversing, 3ø Steam MLE-130 II 72 Kw Electric Reversing, 3ø MLE-130 II 80 Kw Electric Reversing, 3ø Page Page GAS Information Type of GAS Page Page Steam Information Operating Steam PressurePage Bars Page Preparation for Operation Preoperational Tests Basket Coating Operating Instructions Shut Down InstructionsPage SERVICE/PARTS Information ServiceParts Returning Warranty Parts Warranty InformationReturning Warranty Cards WarrantyPage Routine Maintenance CleaningSuggested Cleaning Schedule Steam Dryers Lubrication AdjustmentsData Label Data Label InformationSerial Number Timing Legend Reversing Timer SPIN/DWELL AdjustmentsProcedure for Functional Check Replacement Components Page Page P O R T a N T For Timer or Phase 5 Without Heat Fault ADC 113314 1- 06/21/01-25