American Dryer Corp ML-130 II installation manual MLE-130 II 72 Kw Electric Reversing, 3ø

Page 28

MLE-130 II (72 Kw Electric)

Reversing, 3ø

ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)

IMPORTANT: 208 VAC AND 230/240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.

NOTES: A. When fuses are used they must be dual element, time delay, current limiting, class RK1 or RK5 ONLY. Calculate/determine correct fuse value, by applying either local and/or National Electrical Codes to listed appliance amp draw data.

B.Circuit breakers are thermal-magnetic (industrial) type ONLY. For others, calculate/verify correct breaker size according to appliance amp draw rating and type of breaker used.

C.Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.

OVEN SIZE

SERVICE

 

WIRE

APPROX.

PHASE

AMP DRAW

(Kw)

VOLTAGE

SERVICE

 

60 Hz

50 Hz

 

 

 

 

72

208

3

214

214

 

 

 

 

 

 

72

230/240

3

189

189

72

380-400

3/4

---

114

72

416

3/4

---

107

 

 

 

 

 

 

72

480

3/4

94

---

 

 

 

 

 

 

72

575

3

79

---

 

 

 

 

 

 

IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is affixed to the left side panel/wall area behind the control door. In the case of 208 VAC or 230/240 VAC, the supply voltage must match the electric service specifications of the data label exactly.

WARNING: 208 VAC AND 230/240 VAC ARE NOT THE SAME. Any damage done to dryer components due to improper voltage connections will automatically VOID THE WARRANTY.

NOTE: ADC reserves the right to make changes in specifications at any time without notice or obligation.

24

Image 28
Contents ML-130 Retain This Manual In a Safe Place For Future Reference For Your Safety Page Table of Contents Section Routine Maintenance Important Information Receiving and HandlingSafety Precautions What to do if YOU Smell GASStandards SPECIFICATIONS/COMPONENT Identification SpecificationsSpecifications Component Identification Page Installation Procedures Location RequirementsUNPACKING/SETTING UP Page This Exhaust Duct Transition Piece Must be Installed First Dryer Enclosure Requirements Fresh AIR Supply Requirements Exhaust Requirements Page Downstream of Dryer Page Page Page Electrical Information ML-130 II Reversing, 3ø GAS ML-130 II Reversing, 3ø Steam MLE-130 II 72 Kw Electric Reversing, 3ø MLE-130 II 80 Kw Electric Reversing, 3ø Page Page GAS Information Type of GAS Page Page Operating Steam Pressure Steam InformationPage Bars Page Preparation for Operation Preoperational Tests Basket Coating Shut Down Instructions Operating InstructionsPage Service SERVICE/PARTS InformationParts Warranty Information Returning Warranty CardsWarranty Returning Warranty PartsPage Cleaning Routine MaintenanceSuggested Cleaning Schedule Steam Dryers Adjustments LubricationData Label Information Data LabelSerial Number Reversing Timer SPIN/DWELL Adjustments Timing LegendProcedure for Functional Check Replacement Components Page Page P O R T a N T For Timer or Phase 5 Without Heat Fault ADC 113314 1- 06/21/01-25