Example of a group operation system with multiple heat source units (Shielding wires and address setting are necessary.)

<Examples of transmission cable wiring>

[Fig. 10.3.1] M-NET Remote Controller (P.5)

[Fig. 10.3.2] MA Remote Controller (P.5)

<A>

Change the jumper connector from CN41 to CN40.

 

 

 

<B>

SW2-1:ON

 

 

 

 

<C>

Keep the jumper connector on CN41.

 

 

 

A Group 1

B Group 4

C Group 5

D Shielded wire

E Sub remote controller

( )

Address

 

 

 

 

<Wiring Method and Address Settings>

a.Always use shielded wire when making connections between the heat source unit (OC) and the indoor unit (IC), as well for all OC-OC, and IC-IC wiring intervals.

b.Use feed wiring to connect terminals M1 and M2 and the earth terminal on the transmission cable terminal block (TB3) of each heat source unit (OC) to terminals M1, M2 and terminal S on the transmission cable block of the indoor unit (IC).

c.Connect terminals 1 (M1) and 2 (M2) on the transmission cable terminal block of the indoor unit (IC) that has the most recent address within the same group to the terminal block on the remote controller (RC).

d.Connect together terminals M1, M2 and terminal S on the terminal block for central control (TB7) for the heat source unit (OC).

e.On one heat source unit only, change the jumper connector on the control panel from CN41 to CN40.

f.Connect the terminal S on the terminal block for central control (TB7) for the heat source unit (OC) for the unit into which the jumper connector was inserted into CN40

in Step above to the ground terminal in the electrical component box.

g.Set the address setting switch as follows.

*To set the outdoor unit address to 100, the outdoor address setting switch must be set to 50.

Unit

Range

Setting Method

IC (Main)

01 to 50

Use the most recent address within the same group of indoor units.

 

 

 

IC (Sub)

01 to 50

Use an address, other than that of the IC (Main) from among the units within the same group of indoor units. This must be

in sequence with the IC (Main)

 

 

Heat source Unit

51 to 100

Use the most recent address of all the indoor units plus 50

M-NET R/C (Main)

101 to 150

Set at an IC (Main) address within the same group plus 100

M-NET R/C (Sub)

151 to 200

Set at an IC (Main) address within the same group plus 150

MA R/C

Unnecessary address setting (Necessary main/sub setting)

 

 

 

h. The group setting operations among the multiple indoor units is done by the remote controller (RC) after the electrical power has been turned on.

<Permissible Lengths>

1M-NET Remote controller

Max length via outdoor units: L1 + L2 + L3 + L4 and L1 + L2 + L3 + L5 and L1 + L2 + L6 = 500 m [1640 ft] (1.25 mm2 [AWG16] or more)

• Max transmission cable length: L1 and L3 + L4 and L3 + L5 and L6 and L2 + L6 = 200 m [656 ft] (1.25 mm2 [AWG16] or more)

Remote controller cable length: r1, r2, r3, r4 = 10 m [32 ft] (0.3 to 1.25 mm2 [AWG22 to 16])

If the length exceeds 10 m [32 ft], use a 1.25 mm2 [AWG16] shielded wire. The length of this section (L8) should be included in the calculation of the maximum length and overall length.

2MA Remote controller

Max length via outdoor unit (M-NET cable): L1 + L2 + L3 + L4 and L1 + L2 + L6 = 500 m [1640 ft] (1.25 mm2 [AWG16] or more)

Max transmission cable length (M-NET cable): L1 and L3 + L4 and L6 and L2 + L6 = 200 m [656 ft] (1.25 mm2 [AWG16] or more)

Remote controller cable length: c1 and c1 + c2 + c3 and c1 + c2 + c3 + c4 = 200 m [656 ft] (0.3 to 1.25 mm2 [AWG22 to 16])

3Transmission booster

Max transmission cable length (M-NET cable): 1 L8 + L1 + L2 + L3 + L5 + L6 = 200 m [656 ft] (1.25 mm2 [AWG16])

2 L8 + L1 + L2 + L3 + L5 + L7 = 200 m [656 ft] (1.25 mm2 [AWG16])

3 L8 + L1 + L2 + L4 = 200 m [656 ft] (1.25 mm2 [AWG16])

4 L6 + L5 + L3 + L4, L4 + L3 + L5 + L7 = 200 m [656 ft] (1.25 mm2 [AWG16])

Remote controller cable length: r1, r2 = 10 m [32 ft] (0.3 to 1.25 mm2 [AWG22 to 16])

If the length exceeds 10 m [32 ft], use 1.25 mm2 [AWG16] shielded cable and calculate the length of that portion (L4 and L7) as within the total extended length and the longest remote length.

GB

13

Image 13
Contents PQHY-P72·96TGMU-A Side piping Top piping = 8 m 26 ftHeat source model Liquid pipe Gas pipe P72 Ø9.52 3/8 Unit mmP96 Ø22.2 7/8E J 10.210.4 10.3~208-230 Safety precautions ContentsBefore getting installed SpecificationsBefore installation electrical work About the productWater pipe installation Installation of unit and service spaceConfirmation of parts attached Lifting methodPump interlock Refrigerant piping installationRefrigerant piping system Calculation of additional refrigerant charge Additional refrigerant chargeThermal insulation of refrigerant piping Airtight test, evacuation, and refrigerant chargingAirtight test Only use refrigerant R410AControl box and connecting position of wiring WiringWiring transmission cables Unnecessary address setting Necessary main/sub setting Examples of transmission cable wiringSequence with the IC Main Transmission boosterTest run Wiring of main power supply and equipment capacityInformation on rating plate Following phenomena do not represent trouble emergencyConsignes de sécurité Table des matièresAvant de procéder à l’installation élec- trique Avant de procéder à l’installationAvant d’effectuer l’essai Installation du tuyau d’eau Installation de l’appareil et espace de serviceLe produit Association aux appareils intérieursMise en place de l’isolation Installation des tuyaux de réfrigérantTraitement de l’eau et contrôle de la qualité de l’eau Engrenage des pompesPrécaution Charge supplémentaire de réfrigérantSystème de mise en place des tuyaux de réfrigérant Calcul de la charge supplémentaire de réfrigérantForce de torsion N·m/kg·cm Force de torsion appropriée avec clé dynamométriqueNe pas utiliser de liquide de détection de fuite Test d’étanchéité à l’airUtiliser uniquement le réfrigérant R410A Isolation thermique des tuyaux de ré- frigérantEcoulement Ajout du réfrigérant10.1. Précaution 10. CâblageMise en place des câbles de transmis- sion Schéma du câblage exemple Auxiliaire de transmissionEssai de fonctionnement Informations sur la plaque signalétiquePage Page Page WT04681X01