Sterling SSC1-5Q service manual Changing Parameters, Starting the System

Page 24

Important!

Setting either the CNV>BB or BB CYC parameters to “0” will disable the blowback feature. DO NOT set other blowback parameters to “0.”

5-2-1-1-3 Input and Output Screen Features

To access the I/O screen, press the right arrow key (►) when the Blowback Parameter screen is displayed or the left arrow key (◄) when the Convey/Dump/No Convey screen is displayed.

The I/O screen allows a service technician to view the status of the controller’s inputs and outputs during operation.

5-2-1-1-4 Changing Parameters

To change the settings in the Conveying, Pump Parameters, or Blowback screens {To access the required screen, press the right (►) or the left arrow key (◄)}, the following operations will need to be performed:

1.When the controller is in the menu screen of the feature you wish to configure, press the up (▲) and down (▼) arrow keys to select the value you wish to change. (The parameter value will flash when selected.)

2.Use the Plus (+) key to increase the value or the Minus (-) key to decrease the value.

3.Press the OK key to update and accept the new value entered.

4.Press the ESC key to cancel the parameters you entered and return the values to the previous settings.

5-2-2 Starting the System

Once you have finished the setup procedues described on the previous pages, you are now ready to start the system. To start your system, complete the following steps.

Page 23 of 38

Image 24
Contents SSC1-5Q Parts and Service Department Model # Serial # Table of Contents Configurable Settings Charts and Figures Safety Considerations Sterling SSC1-5Q Conveying Systems Pump 5-Station Controller General Information Equipment FunctionNecessary Documents System CapabilitiesEquipment Cycle Models Covered by this ManualSSC1-5Q 5-Station Controller SSC1-5Q Controller Safety Safety ConsiderationsWork Rules Tools and Equipment NeededReporting a Safety Defect General ResponsibilityMaintenance Responsibility Operator ResponsibilitySafety Devices Safety Circuit StandardsFail Safe Operation Safety Device Lock-Outs Page Shipping Information Unpacking and InspectionEvent of Shipping Damages Parcel Post ShipmentUnited Parcel Service Shipment If the Shipment is Not CompleteIf the Shipment is Not Correct ReturnsInstallation Installing the SCC1-5Q Control PanelMaking SSC1-5Q Control Panel Power Drop Wiring Connections Connecting the Control Panel to Vacuum ReceiversConnecting the Control Panel to the Pump Package Special Timed ConveyUsing the Controller SetupBasic Menus and Setup of Controller IntroductionSetting Pump Parameters Setting Blowback ParametersChanging Parameters Starting the SystemHigh vaccum alarm will sound in Short Tones Long Tones6Configurable Settings Options for Station SetupOptions for Pump Setup Idle7Maintenance Troubleshooting General TroubleshootingAlarms Station AlarmsPump Alarms Remote Audible/visual alarm Options230/1/60 Operation CE Package for 220/1/50 OperationSpare Parts List Recommended Spare Parts ListTechnical Assistance Contact Information for Technical AssistanceWarranty Returns Returned Material PolicyCredit Returns Warranty Safety Tag Information Controller Safety TagsController Identification Serial Number Tag Appendix Page Service Department