| Troubleshooting Reference | |||||||
| Table |
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Problem | Possible Cause | Solution | |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| No output voltage. No | The switch is in Standby ( ) | Turn the On/Standby switch to On ( |
| ). |
| ||||||||
|
|
| ||||||||||||
| indicator lights are | mode. |
|
|
|
|
|
|
|
|
|
|
|
|
| illuminated. |
| Check the DC wiring to the inverter for | |||||||||||
|
| No input power to the inverter. | ||||||||||||
|
|
| loose connections, frayed wiring or an | |||||||||||
|
|
| open DC Disconnect. | |||||||||||
|
| DC fuse open (external) | Have a qualified service technician | |||||||||||
|
|
| check and replace the fuse. | |||||||||||
| No output voltage. Inverter | Supplemental Circuit | Disconnect all appliances to reduce the |
| ||||||||||
| ON light is illuminated. | Protection button has tripped. | overload. Check the AC wiring, and | |||||||||||
|
|
| reset the Supplemental Circuit | |||||||||||
|
|
| Protection button. | |||||||||||
|
| GFCI has tripped. | Clear the ground fault, and reset the | |||||||||||
|
|
| GFCI by pressing the Reset button on | |||||||||||
|
|
| the GFCI. | |||||||||||
| No output voltage. Fault light | Inverter may be overloaded. | Disconnect all appliances connected to |
| ||||||||||
| is illuminated. |
| the inverter, and reset the inverter by | |||||||||||
|
|
| turning the On/Standby switch to | |||||||||||
|
| Battery voltage may be too | Standby ( |
|
|
| ) and then to On ( |
| ). | |||||
|
|
|
|
|
| |||||||||
|
| The inverter will restart if the battery | ||||||||||||
|
| high. | voltage drops below 14.5 volts DC. | |||||||||||
|
| Over temperature. | Allow the inverter to cool down. The | |||||||||||
|
|
| inverter will restart automatically. | |||||||||||
| No output voltage. Low | Battery voltage is too low. | Recharge the battery to more than 12.6 |
| ||||||||||
| Battery light is illuminated. |
| volts DC. The inverter will restart | |||||||||||
|
|
| automatically. | |||||||||||
|
| Poor DC wiring. | Turn the inverter to Standby ( |
| ). | |||||||||
|
|
| ||||||||||||
|
|
| ||||||||||||
|
|
| Disconnect the DC wiring. Use proper | |||||||||||
|
|
| wiring and ensure all connections are | |||||||||||
|
|
| tight. | |||||||||||
| Output voltage is present. | Battery voltage is low. | Disconnect all appliances. Charge the |
| ||||||||||
| Inverter ON light and Low |
| batteries. | |||||||||||
| Battery light are illuminated. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|