Omega Engineering FLR7000 series, FLR9000 series, FLR8000 series, FLR6000 series manual Output Mode

Page 15

FLR Flow Transmitter Installation & Programming Instructions

Output Mode

The FLR Flow Transmitter offers three analog output modes:

4–20 mAOutput Signal

0–5 Volts DC Output Signal

0–10 Volts DC Output Signal

The output mode selected is determined by the type of peripheral device being connected to the FLR Flow Transmitter.

The displayed name is OUT MODE and is viewed or changed using the List Item Selection Procedure found on page 8.

Note: Setup prompts and descriptors for configuring and calibrating the analog output will correspond to the output mode selected. Refer to the Flow Chart on pages 10 and 11.

Flow at 0V or 4mA Setting

This selection is used to configure the minimum ana- log output signal to the corresponding flow rate. Enter the flow rate at which the minimum analog output sig- nal is required using the Numeric Value Entry Procedure found on page 8.

Flow at 5V, 10V or 20mA Setting

This selection is used to configure the maximum ana- log output signal to the corresponding flow rate. Enter the flow rate at which the maximum analog output sig- nal is required using the Numeric Value Entry Procedure found on page 8.

Calibration of Analog Output

This selection allows access to the calibration and testing of the analog output signal. Calibration of the Analog Output is preset at the factory, but can be changed to customize calibration for your installation.

To test or change the analog output calibration, it is first necessary to change the default setting for CAL OUT? from NO to YES.

Note: Setup prompts and descriptors for configuring and calibrating the analog output will correspond to the output mode selected. Refer to the Flow Chart on pages 10 and 11.

1.At the CAL OUT? prompt press ENTER. NO will display.

2.To change to YES, press either arrow key.

3.The analog output will go to its minimum output level. A numeric value between 0–4000 will dis- play. This is an internal number used to drive the analog output.

4.To increase the analog output signal level, press the UP ARROW key. To decrease the analog output signal level, press the RIGHT ARROW key.

5.Press ENTER to store the setting.

6.The analog output will go to its maximum output level. A numeric value between 0–4000 will dis- play. This is an internal number used to drive the analog output.

7.To increase the analog output signal level, press the UP ARROW key. To decrease the analog output signal level, press the RIGHT ARROW key.

8.Press ENTER to store the setting.

9.The unit will advance to the analog output test mode. The analog output will go to its minimum output level. A numeric value of 0 will display. For test purposes, the analog output signal can be run up or down in increments of 1 milliamp or 1 volt, depending on the OUT MODE selected.

10.To increase the analog output signal level, press the UP ARROW key. To decrease the analog output signal level, press the RIGHT ARROW key.

11.Press ENTER to exit the analog calibration mode.

12.The unit automatically advances to the PASS- WORD feature.

Page 13

Image 15
Contents User’s Guide Servicing North America FLR Flow Transmitter IntroductionII. Specifications III. Installation Electrical Connections Terminology Operating the Meter Installing the TransmitterNormal Operation RUN Mode IV. OperationCover Removal/Reinstallation Programming Operation Program ModeList Item Selection Procedure Total Flow Units Programming DescriptionsFLR Flow Transmitter Installation & Programming Instructions FLR Flow Transmitter Installation & Programming Instructions Zero Capture Meter Size TypesOutput Mode Cartridge Cleaning on page 5 and on MaintenanceVII. Appendix VI. TroubleshootingFluid Selection Correction FactorsFlow vs. Pressure Drop Water Petroleum Fluids Phosphate Ester I. Oil Air / Compressed Gases FLR Flow Transmitter Installation & Programming Instructions FLR Flow Transmitter Installation & Programming Instructions WARRANTY/ Disclaimer Shop online at omega.com