FLR Flow Transmitter Installation & Programming Instructions
FLOW
INLET PORT
Figure 5. Flow Direction Arrow
Installing the Transmitter
1.Disconnect electrical power from the target sys- tem before making or changing any transmitter connections.
2.Use 0.05A fast acting fuse if
3.Terminate cable shield connection at either DC ground or Earth ground.
4.Mount the transmitter so fluid is traveling in the direction of the flow arrow. See Figure 5.
5.Install unit in desired location. Use wrench on transmitter flats to hold the unit in place during installation. DO NOT TURN the transmitter using the wrench. See Figure 6.
6.After installation, rotate transmitter by hand to view display. See Figure 7.
7.Capture the zero flow position on the meter cone using the ZERO CAPTURE procedure found on page 12.
IV. OPERATION
NOTE: Refer to the Appendix for application informa- tion and fluid charts.
Operating the Meter
The monitor has two modes of operation, referred to as RUN mode and PROGRAM mode as indicated on the display screen readout. Normal operation will be in the run mode. To access the program mode, press the MENU key until the first programming screen DISPLAY appears. (PROGRAM appears on left side of
Place wrench on
transmitter flats on the same side plumbing is being tightened
Never place wrench on transmitter flats opposite plumbing being tightened
Figure 6. Installing Transmitter
Rotate transmitter by
hand to view flow
display
Never use wrench to
rotate transmitter
body when viewing
flow display
Figure 7. Rotating Transmitter
display.) After programming the meter a password may be entered to prevent unauthorized access or chang- ing of the setup features.
Normal Operation (RUN) Mode
During normal operation, the display will show RUN and the flow rate, total flow, or toggle back and forth between the two as defined by the DISPLAY configu- ration.
The 4 buttons have the following function in RUN mode:
MENU - Selects programming mode.
UP ARROW - No function.
RIGHT ARROW - No function.
Page 6