Siemens SITRANS FUS1010 NEMA-4X/ IP 65 manual FLOW1

Page 61

Section 2

1010NFM-3J

 

 

 

NOTE: Before preceeding to mount transducers, it is recommended that Section 3 - HARD- WARE INSTALLATION GUIDE be reviewed. Refer to the Pick/Install Xdcr menu and menu structure shown below for menu cell descriptions and details.

Once you select the type, use this menu cell to specify the transducer size.

Use this menu cell to select the type of transducer to be installed.

These menu cells identify the spacing indices on the spacer bar. You must use these settings to mount the transducer properly.

This menu cell shows the actual spacing distance required between the transducers.

Siemens

2 Channel

[1]

FLOW1

Scroll List and select desired Model

 

Transducer Model

1011 Universal

Transducer Size

B3

 

 

Xdcr Mount Mode

Reflect

 

Spacing Offset

 

Spacer Bar PB-1

Number Index

 

0

 

 

Spacing Method

Track 1012TAH

Ltn Value (in)

 

0.565

 

Install Complete?

No

 

 

Empty Pipe Set

 

MTYmatic

 

Zero Flow Adjust

Actual Zero

Pick/Install Xdcr

 

 

 

 

This menu cell allows you to select a mounting mode. *Use Reflect Mode whenever possible.

This menu cell indicates the model number of the appropriate spacer bar for your transducers and spacing requirements.

Use this menu cell to inform the meter that you have completed the transducer mounting.

After the transducers are operating, you can use this menu cell to manually set the zero flow correction.

After the transducers are operating, you can use this menu cell to set the empty pipe threshold.

2-21

Image 61
Contents Sitrans Standard Terms and Conditions of Sale 10/1/2004 Siemens Energy & Automation’s Standard WarrantyFor Technical Assistance For General Information Field ManualManual Changes 1010FMA-4 Manual Addendum JulyCall 800 631 Fax 631 Or sales.ultrasonicflow@siemens.comTransducer Installation Setup ProcedureManual Addendum 1010FMA-4 Flowmeter Setup Transfer Install Procedure Transfer Install FunctionSaving New Transfer Install Site 1010FMA-14 Manual Addendum MayFor Systems Equipped With 1010N-7 Modules Manual Addendum 1010FMA-14Introduction Expanded I/O Module OptionMeter Menu Display AUX IoExpanded I/O Module Option Programming Aux Io1 Aux Io2 Aux Io3 Aux Io4Table of Contents Table Of Contents 1010NFM-3J Netflow Alarm Letter Codes and Descriptions 12.1 Using The 996PSP Pipe SimulatorMeter Facilities Menu And Graphic Display Screens Vii Index AppendicesPipe Table Flowmeter Installation Steps Important Safety ConsiderationsSection 1010NFM-3J Keypad Enable Switch 1010N Keypad Keypad Function ChartIntroduction to the 1010N Menu Screens KEY UsageExplanation of the CALL-OUTS HOW to USE the Installation MenuHOW to Enter Data Accessing and Leaving the MenuSection 1010NFM-3J Selecting Items from an Option List Entering Numeric Data Multiple Select Option ListsSection 1010NFM-3J Entering Alphanumeric Strings Meter Type MenuDual Path Section 1010NFM-3J Dual ChannelChannel 1+2 and Channel Multi-Path Operation Arithmetic OperationMeter types on the right-hand column. Press Selecting a Meter TypeChannel Flow Creating a New Site Setup See paragraph Character position Flowmeter Installation Flowchart Choosing the Pipe CLASS/SIZE Using Faststart SetupPicking and Installing the Transducers Section 1010NFM-3J To scroll between the avail Press . This brings up a Flow Display Screen1010WX CLAMP-ON Liquid Flowmeters Alternate Light Weight 1010WX Case1010WX Flowmeter Label System HardwareElectronic Modules Display and Keypad OptionsConventions used with these instructions are General Installation Menu NotesHOW to Recall a Site Setup Channel Setup MenuChannel Setup Menu Structure HOW to Enable and Disable a Measurement Channel HOW to ENABLE/DISABLE Site Security HOW to CREATE/NAME a Site SetupHOW to SAVE/RENAME a Site Setup HOW to Delete a Site SetupPipe Data Menu ASA Stainless Steel Pipe Data Menu StructureHOW to Select a Pipe Size HOW to Select a Pipe ClassSection 1010NFM-3J Pipe Data Menu Structure HOW to Select a Pipe Material HOW to Enter the Pipe OD in. or mmHOW to Enter the Wall Thickness Liner Thickness Liner MaterialApplication Data Menu Application Data Menu Structure Application Data Menu Structure How to Edit the Estimated Vs liquid sonic velocity HOW to Select a Liquid ClassHow to Edit the Density SG Setting Section 1010NFM-3J How to Edit the Viscosity cS SettingUniMass Table Application Data Menu Explanations for UniMass Table Vs Vs Value Create/Edit Table Point New Point + Points ListG. Specific Gravity Viscosity Liquid Viscosity cSEND Column Parameter Units HOW to Select a Pipe Temperature RangePipe Configuration Menu Structure Pipe ConfigurationPICK/INSTALL Xdcr Menu Pipe Configuration Option List DefinitionsFLOW1 PICK/INSTALL Xdcr Menu Structure HOW to Select a Transducer ModelHOW to Select a Transducer Mount Mode HOW to Select a Transducer SizeReviewing the Spacing Method HOW to USE the Spacing OffsetNumber Index Menu Cell HOW to USE Install COMPLETED?Ltn Menu Cell Install Completed? Drive Section 1010NFM-3J Force Transmit ProcedureMeasured Vs m/s Empty Pipe SET Menu How to Use the Actual MTY CommandSection 1010NFM-3J How to Use the MTYmatic Command Zero Flow Adjust MenuHow to Use the Set Empty Command AutoZeroActual Zero Using Actual ZeroReversaMatic Reverse Xdcrs / Press ENT Using ReversaMaticConforms Indicated flow to Actual Zero ZeroMatic optional functionOperation Adjust Operation Adjust MenuDamping Control Operation Adjust Menu StructureDeadband Control Reflexor ZERO/FAULT SET Option Reflexor Mode only MEMORY/FAULT SETMemory Delay sec Netflow FLOW/TOTAL Units MenuFLOW/TOTAL Units Menu Structure Flow Volume UnitsFlow Time Units Flow Volume UnitsFlow Display Range Total Volume UnitsFlow Display Scale Totalizer Scale Total ResolutionMode Flow Direction Totalizer ModeBATCH/SAMPLE Total Data SPAN/SET/CAL MenuData SPAN/SET/CAL Menu Structure Span DataMax Flow Maximum span values represent Minimum span values representMin Flow SET Alarm Levels Low Temperature High TemperatureSection 1010NFM-3J High Flow Low FlowAeration % Section 1010NFM-3J Interface Vs m/s meters-per-secondMakeup Latch Kc Calibration Calibrate Flow RateTo calculate Kc MultiPoint CalibrationSection 1010NFM-3J Section 1010NFM-3J To enable numeric entry press Stripchart Setup MenuStripchart Setup Menu Structure Select DataTime Base Data DisplayDatalogger Setup Menu Stripchart ClearDatalogger Setup Menu Structure Datalogger Data Datalogger ModeLOG Time Interval Section 1010NFM-3J Alarm Letter Codes and DescriptionsDatalogger Events Display Datalogger I/O Data Control Menu I/O Data Control Menu Structure Analog Output SetupTable To Determine Proper I/O Installation Drawings Analog Out Setup Data CategoriesSection 1010NFM-3J System 1010 Analog Outputs VfoInstallation Drawing 1010N-7-7 Sheet 2 Installation Drawing 1010N-2-7 Sheet 2Relay Setup 1010N & 1010DN with 1010N-2 ModulesRelay Option List Analog Input Setup optional functionSection 1010NFM-3J Assigning Relay 1 and 2 Functions Setting up the Analog Current Input Diagnostics Data MenuDiagnostic Data Menu Structure Main Diagnostic Menu Description Main Diagnostics ScreenFlow Data Menu Vs m/s Flow Data Menu ItemsAnCal Section 1010NFM-3J HiFlow and LoFlowLiquid Data Menu Application Info MenuApplication Info Menu Items Liquid Data Menu ItemsSite Setup Menu Items Site Setup Data MenuIntroduction to HF Menu Item Using the HF Menu ItemAccess Path/Channel Diagnostic Data Manual Adjustment ProcedureAutomatic Automatic Adjustment ProcedureTest Facilities Menu Test Facilities CommandsMakeup Test Facilities Graph Screen Detection ModeDiagnostic Text Display Entering the Diagnostic Graph ScreenTime Base Control Correlated PlotTransit Time Adjustment Hot Key Command ModesDigital Damping Control Hot Key 1 Envelope Threshold Adjustment Hot Key 5 Zero Crossover Adjustment Hot KeyDescription of Graph Screen Text Display Parameters Signal Masking Function Hot KeyHOT KEY Summary Flow Computer Messages Troubleshooting TipsMessage Description Using the F4 Reset Sequence Section 1010NFM-3J Using the 1012TB-1 and 2 Test Blocks Troubleshooting with Transducer Test BlocksThk Mode Offset Mat’l Thk Mode Index Using the 996PSP Pipe SimulatorIf a Pipe Simulator/Test-Block Test Fails Programming INSTALLATION/TRANSDUCER Mount GuidelinesDIAGNOSTIC/PERFORMANCE Verification OPTIMIZATION/CORRECTION of ProblemsNFM-3J START-UPPoor Signal Detection Fault/Low SignalSection 1010NFM-3J Low Valc High VaerAlternative Coupling Compounds Official Coupling CompoundsPart# Name Application Max Temp Remarks Trade Name Application Max Temp RemarksPreparing to Mount the Transducers HOW to Identify 1011 Transducers and Mounting HardwareSelecting a Location for CLAMP-ON Transducers Pipe shown in Top View for ease in visualizing sonic path CLAMP-ON Transducer Mounting ModesPipe Preparing the PipePositioned around Mounting Frame Reflect Mode Mounting Frames and Spacer BARStrap Mounting Kit P/N Pipe Diameter Band Sizes Qty Reflect Mode with Spacer BAR onlyInstallation Reflect Mount with Transducers and Spacing BAR Spacer BAR Not Shown and Spacing Guide Direct Mode Mounting FRAMES, Spacer BAR and Spacing GuidesMylar Spacing Guide Wrapping the Mylar Spacing Guide around the Pipe Finding the Halfway Distance Installing a 1012T Mounting Track in Reflect Mode Using 1012T Mounting TracksFront View Ç Installation Reflect Mount with Mounting TrackInstallation Direct Mount 180º Opposed with Mounting Track Installing a 1012T Mounting Track in Direct ModeChain Tension Mounting Temperature Sensors 1010N Single Channel Temperature Sensor Inputs Wiring Temperature Sensor to the Analog Input Module1012EC Series Terminal TB1 Cable 2 1010N Supply and Return ConnectionsDual Path Models Paralleling RTD Inputs for DUAL-CHANNEL Energy Measurement CLAMP-ON Resistive Temperature Device RTD Installation NotesPreferred Units Meter Facilities Menu and Graphic Display ScreenPipe Table Table Setups MenuPipe Table Menu Structure Section 1010NFM-3J Pipe Table Menu Structure CREATE/EDIT PipeTransducer Type Menu Delete PipeTransducer Type Menu Structure 0A0Datalogger Control Menu Structure Datalogger Control MenuCircular Memory Output DataloggerClear Datalogger EST LOG Time LeftMemory Control Menu Memory Control MenuCurrent Output Trim Io1 & Io2 Analog Output Trim MenuVoltage Output Trim Vo1 & Vo2 Analog Output Trim Menu StructureRTD Calibrate Menu optional Pgen Output Trim Pgen 1 & PgenICE Bath RTD Calibration RTD Calibration by Data EntryWith ICE During AN ICE Bath Calibration Date Clock SET MenuTime Clock SET Menu StructureRS-232 Setup Menu Structure RS-232 SetupBaud Rate Data Bits ParityLine Feed RTS KEY Time Network IDBacklight System InfoSection 1010NFM-3J System Info Menu Structure 1010 Graphic Display Screens30.068.10 Dual Display Screen 11.01Considerations for Critical Applications To Obtain Technical AssistancePipe Considerations for CLAMP-ON Transducer Pipe DimensionsPicking the Appropriate Transducer Flow Velocity RangeRepeatability AccuracyData Stability Data ScatterLOW Flow Rates Flow ConditionsFlow Data Scatter & Damping System 1010 Damping and Slewing ControlsLiquid Compatibility Erroneous Liquid Parameter SpecificationAeration Temperature and Pressure Ratings TWO-PHASE LiquidsSlurries Viscous LiquidsSonic Velocity for Pure Water @ Various TEMP. meters/sec Reference TablesLiquid Deg. C Deg. F Vs m/s Page Recommended Sonic Coupling Compounds CC# USE CharacteristicsReynolds # Positive Comp Negative Comp System 1010 Reynolds Compensation FactorTerm Explanation Terminology ChartRTD Meter Type Menu Nema DUAL-CHANNEL Menu ChartMeter Facilities Menu CLAMP-ON Menu CLAMP-ON Menu Section 1010NFM-3J ÖÚ No Typical Industries Serviced include General Installation GuidelinesLiquid Applicability and Compatibility Typical Applications includeFlow Tube Mounting Location Selecting the Right Flow TubeFlow Tube Material, Size & Flow Range Ratings To Obtain Technical Assistance Flow Data Scatter and DampingSetup Procedure HOW to SET UP System 1010 for Flow Tube OperationOverview Press to leave the Channel Setup menu Menu Key Install to start operation Sired Offset Specifications Kynar Pvdf Flow Tube Specifications Cpvc Flow TubeSpecifications 316 Stainless Steel Flow Tube Specifications Teflon PFA Flow Tube1011FT Series 316 Stainless Steel Flow Tube Additional Installation Notes992DFT992DFTSeriesSeriesTeflonTeflonPFA FlowPFATubeFlow Tube Select a Transducer SET for USE by Reflexor Reflexor Installation StepsSelect the Transducer Mounting Location Incorrect Transducer PlacementElbow Expansion Contraction Valve Orifice Plate Mounting the Transducers Reflexor Mode Adjacent Transducer MountingInstalling Reflexor Operating Mode Select Reflexor Operating ModeAccess the Install Xdcr Transducer Menu Connection of Transducer CablesSpectra Display Screen Cursor USE on the Spectra Graph HOW to USE Spectra Graph Data and ControlsAdjustment Function Available Adjustments to Spectra GraphReflexor Diagnostic Data Selection of Liquid Composition Display of F AT no Flow ConditionsOther Menu Entries Appendix a Page RS-232 Interface Cable Site Setup Considerations for 1010/1020N Blind SystemsAppendix 1010NFM-3J Meter Type Cable Type Controlotron Part Number AppendixCommunicating with System 1010/1020 VIA the RS-232 Interface HOW to USE the Windows HyperTerminal ProgramNone Accessing the Installation Menu This is the current measured liquid Data Display ModeKeyboard PC Keyboard Description Terminal Mode Menu CommandsClose the Terminal or HyperTerminal Program Transfer of Information from a 1010/1020 Flowmeter to the PCTo Clear Active Memory Using the RS-232 Interface Reset Procedure for Blind SystemsTo Clear All Dynamic Memory Using the RS-232 Interface Appendix1010NFM-3J Transducer and Accessory DrawingsFlow Computer Drawings Channel Drawings990TRMVH-7B Index 1010NFM-3J SymbolsIndex1010NFM-3J Index-2Index-3 Index-4 Index-5 Index-6 Index-7 Index-8 Index-9 Index-10 Index-11 Index-12 TradeMarks of Siemens Energy & Automation Inc TrademarksDuctile Iron Pipe NON-STANDARD Carbon Size