Siemens SITRANS FUS1010 NEMA-4X/ IP 65 manual Totalizer Scale, Total Resolution

Page 81

Section 2

1010NFM-3J

 

 

 

2.6.6 TOTALIZER SCALE

After you select totalizer units, the meter automatically computes a prefix to provide the best combina- tion of capacity and resolution (e.g. MGAL/MIN). The [Totalizer Scale] menu cell shows the results. If the displayed scaling is not suitable, you can edit it by accessing the option list. Note that this scaling applies to all flow total data displayed on the flow display screen, even if the units do not appear next to the data (because there may not be room on the screen). Always keep this prefix in mind when you enter totalizer-related data.

To select a different Totalizer Scale:

To access the [Totalizer Scale] option list press

Move the cursor to the desired display scale by pressing

To register selection press ENT

2.6.7 TOTAL RESOLUTION

The meter assigns multiplier prefixes for the flow total units you selected (e.g., MGPM). It provides three resolution (or capacity) levels. Therefore, actual Totalizer display units depend on the selected multiplier. Check the total units by accessing the [Totalizer Scale] menu cell.

If you use the totalizer (TOTCNT) relay output, take into account:

a)The TOTCNT relay output pulses at a maximum rate of .5 pulses per sec. (.5 Hz).

b)The meter sends a totalizer output pulse for every advance of the rightmost visible totalizer digit.

It is possible for a high flow rate to persist long enough to exceed the relay output’s .5 Hz rate. If this occurs, the meter will store excess pulses in an overflow buffer, and route them back to the relay when the flow rate drops enough to allow the TOTCNT output to catch-up. Exceeding the .5 Hz rate for long periods could cause an excessive accumulation of buffered pulses and continue to trip the relay after the flow rate lessens, or even stops. If this occurs, the meter will be unable to indicate the current flow total. Therefore, select a resolution to ensure that, even at the maximum expected flow rate, the TOTCNT pulse will not be activated more than .5 times per second for any appreciable length of time. Note that resetting the Totalizer also clears the overflow buffer.

To change the default resolution:

To access the [Total Resolution] option list press

Move the cursor to the required resolution by pressing

To store selection press ENT

2-41

Image 81
Contents Sitrans Standard Terms and Conditions of Sale 10/1/2004 Siemens Energy & Automation’s Standard WarrantyFor Technical Assistance For General Information Field ManualManual Changes 1010FMA-4 Manual Addendum JulyCall 800 631 Fax 631 Or sales.ultrasonicflow@siemens.comSetup Procedure Transducer InstallationManual Addendum 1010FMA-4 Flowmeter Setup Transfer Install Function Transfer Install ProcedureSaving New Transfer Install Site 1010FMA-14 Manual Addendum MayFor Systems Equipped With 1010N-7 Modules Manual Addendum 1010FMA-14Introduction Expanded I/O Module OptionMeter Menu Display AUX IoExpanded I/O Module Option Programming Aux Io1 Aux Io2 Aux Io3 Aux Io4Table of Contents Table Of Contents 1010NFM-3J Netflow Alarm Letter Codes and Descriptions 12.1 Using The 996PSP Pipe SimulatorMeter Facilities Menu And Graphic Display Screens Vii Appendices IndexPipe Table Important Safety Considerations Flowmeter Installation StepsSection 1010NFM-3J Keypad Enable Switch 1010N Keypad Keypad Function ChartIntroduction to the 1010N Menu Screens KEY UsageExplanation of the CALL-OUTS HOW to USE the Installation MenuHOW to Enter Data Accessing and Leaving the MenuSection 1010NFM-3J Selecting Items from an Option List Entering Numeric Data Multiple Select Option ListsSection 1010NFM-3J Entering Alphanumeric Strings Meter Type MenuSection 1010NFM-3J Dual Channel Dual PathChannel 1+2 and Channel Multi-Path Operation Arithmetic OperationSelecting a Meter Type Meter types on the right-hand column. PressChannel Flow Creating a New Site Setup See paragraph Character position Flowmeter Installation Flowchart Choosing the Pipe CLASS/SIZE Using Faststart SetupPicking and Installing the Transducers Section 1010NFM-3J To scroll between the avail Press . This brings up a Flow Display Screen1010WX CLAMP-ON Liquid Flowmeters Alternate Light Weight 1010WX Case1010WX Flowmeter Label System HardwareElectronic Modules Display and Keypad OptionsConventions used with these instructions are General Installation Menu NotesChannel Setup Menu HOW to Recall a Site SetupChannel Setup Menu Structure HOW to Enable and Disable a Measurement Channel HOW to ENABLE/DISABLE Site Security HOW to CREATE/NAME a Site SetupHOW to SAVE/RENAME a Site Setup HOW to Delete a Site SetupPipe Data Menu ASA Stainless Steel Pipe Data Menu StructureHOW to Select a Pipe Class HOW to Select a Pipe SizeSection 1010NFM-3J Pipe Data Menu Structure HOW to Enter the Pipe OD in. or mm HOW to Select a Pipe MaterialHOW to Enter the Wall Thickness Liner Material Liner ThicknessApplication Data Menu Application Data Menu Structure Application Data Menu Structure How to Edit the Estimated Vs liquid sonic velocity HOW to Select a Liquid ClassSection 1010NFM-3J How to Edit the Viscosity cS Setting How to Edit the Density SG SettingUniMass Table Application Data Menu Explanations for UniMass Table Vs Vs Value Create/Edit Table Point New Point + Points ListG. Specific Gravity Viscosity Liquid Viscosity cSEND Column Parameter Units HOW to Select a Pipe Temperature RangePipe Configuration Menu Structure Pipe ConfigurationPICK/INSTALL Xdcr Menu Pipe Configuration Option List DefinitionsFLOW1 PICK/INSTALL Xdcr Menu Structure HOW to Select a Transducer ModelHOW to Select a Transducer Mount Mode HOW to Select a Transducer SizeReviewing the Spacing Method HOW to USE the Spacing OffsetHOW to USE Install COMPLETED? Number Index Menu CellLtn Menu Cell Install Completed? Drive Section 1010NFM-3J Force Transmit ProcedureMeasured Vs m/s Empty Pipe SET Menu How to Use the Actual MTY CommandSection 1010NFM-3J How to Use the MTYmatic Command Zero Flow Adjust MenuHow to Use the Set Empty Command AutoZeroUsing Actual Zero Actual ZeroReversaMatic Reverse Xdcrs / Press ENT Using ReversaMaticConforms Indicated flow to Actual Zero ZeroMatic optional functionOperation Adjust Operation Adjust MenuOperation Adjust Menu Structure Damping ControlDeadband Control MEMORY/FAULT SET Reflexor ZERO/FAULT SET Option Reflexor Mode onlyMemory Delay sec Netflow FLOW/TOTAL Units MenuFLOW/TOTAL Units Menu Structure Flow Volume UnitsFlow Time Units Flow Volume UnitsTotal Volume Units Flow Display RangeFlow Display Scale Totalizer Scale Total ResolutionMode Flow Direction Totalizer ModeBATCH/SAMPLE Total Data SPAN/SET/CAL MenuData SPAN/SET/CAL Menu Structure Span DataMaximum span values represent Minimum span values represent Max FlowMin Flow SET Alarm Levels Low Temperature High TemperatureSection 1010NFM-3J High Flow Low FlowSection 1010NFM-3J Interface Vs m/s meters-per-second Aeration %Makeup Latch Kc Calibration Calibrate Flow RateTo calculate Kc MultiPoint CalibrationSection 1010NFM-3J Section 1010NFM-3J To enable numeric entry press Stripchart Setup MenuStripchart Setup Menu Structure Select DataTime Base Data DisplayDatalogger Setup Menu Stripchart ClearDatalogger Setup Menu Structure Datalogger Data Datalogger ModeSection 1010NFM-3J Alarm Letter Codes and Descriptions LOG Time IntervalDatalogger Events Display Datalogger I/O Data Control Menu I/O Data Control Menu Structure Analog Output SetupTable To Determine Proper I/O Installation Drawings Analog Out Setup Data CategoriesSection 1010NFM-3J System 1010 Analog Outputs VfoInstallation Drawing 1010N-7-7 Sheet 2 Installation Drawing 1010N-2-7 Sheet 2Relay Setup 1010N & 1010DN with 1010N-2 ModulesAnalog Input Setup optional function Relay Option ListSection 1010NFM-3J Assigning Relay 1 and 2 Functions Setting up the Analog Current Input Diagnostics Data MenuDiagnostic Data Menu Structure Main Diagnostics Screen Main Diagnostic Menu DescriptionFlow Data Menu Vs m/s Flow Data Menu ItemsAnCal Section 1010NFM-3J HiFlow and LoFlowLiquid Data Menu Application Info MenuApplication Info Menu Items Liquid Data Menu ItemsSite Setup Menu Items Site Setup Data MenuIntroduction to HF Menu Item Using the HF Menu ItemAccess Path/Channel Diagnostic Data Manual Adjustment ProcedureAutomatic Automatic Adjustment ProcedureTest Facilities Commands Test Facilities MenuMakeup Test Facilities Graph Screen Detection ModeDiagnostic Text Display Entering the Diagnostic Graph ScreenTime Base Control Correlated PlotCommand Modes Transit Time Adjustment Hot KeyDigital Damping Control Hot Key 1 Envelope Threshold Adjustment Hot Key 5 Zero Crossover Adjustment Hot KeySignal Masking Function Hot Key Description of Graph Screen Text Display ParametersHOT KEY Summary Troubleshooting Tips Flow Computer MessagesMessage Description Using the F4 Reset Sequence Section 1010NFM-3J Using the 1012TB-1 and 2 Test Blocks Troubleshooting with Transducer Test BlocksThk Mode Offset Mat’l Thk Mode Index Using the 996PSP Pipe SimulatorIf a Pipe Simulator/Test-Block Test Fails Programming INSTALLATION/TRANSDUCER Mount GuidelinesDIAGNOSTIC/PERFORMANCE Verification OPTIMIZATION/CORRECTION of ProblemsNFM-3J START-UPPoor Signal Detection Fault/Low SignalSection 1010NFM-3J Low Valc High VaerAlternative Coupling Compounds Official Coupling CompoundsPart# Name Application Max Temp Remarks Trade Name Application Max Temp RemarksHOW to Identify 1011 Transducers and Mounting Hardware Preparing to Mount the TransducersSelecting a Location for CLAMP-ON Transducers Pipe shown in Top View for ease in visualizing sonic path CLAMP-ON Transducer Mounting ModesPipe Preparing the PipePositioned around Mounting Frame Reflect Mode Mounting Frames and Spacer BARStrap Mounting Kit P/N Pipe Diameter Band Sizes Qty Reflect Mode with Spacer BAR onlyInstallation Reflect Mount with Transducers and Spacing BAR Spacer BAR Not Shown and Spacing Guide Direct Mode Mounting FRAMES, Spacer BAR and Spacing GuidesMylar Spacing Guide Wrapping the Mylar Spacing Guide around the Pipe Finding the Halfway Distance Installing a 1012T Mounting Track in Reflect Mode Using 1012T Mounting TracksFront View Ç Installation Reflect Mount with Mounting TrackInstallation Direct Mount 180º Opposed with Mounting Track Installing a 1012T Mounting Track in Direct ModeChain Tension Mounting Temperature Sensors 1010N Single Channel Temperature Sensor Inputs Wiring Temperature Sensor to the Analog Input Module1012EC Series Terminal TB1 Cable 2 1010N Supply and Return ConnectionsDual Path Models Paralleling RTD Inputs for DUAL-CHANNEL Energy Measurement CLAMP-ON Resistive Temperature Device RTD Installation NotesPreferred Units Meter Facilities Menu and Graphic Display ScreenTable Setups Menu Pipe TablePipe Table Menu Structure Section 1010NFM-3J Pipe Table Menu Structure CREATE/EDIT PipeTransducer Type Menu Delete PipeTransducer Type Menu Structure 0A0Datalogger Control Menu Structure Datalogger Control MenuCircular Memory Output DataloggerClear Datalogger EST LOG Time LeftMemory Control Menu Memory Control MenuCurrent Output Trim Io1 & Io2 Analog Output Trim MenuVoltage Output Trim Vo1 & Vo2 Analog Output Trim Menu StructureRTD Calibrate Menu optional Pgen Output Trim Pgen 1 & PgenRTD Calibration by Data Entry ICE Bath RTD CalibrationWith ICE During AN ICE Bath Calibration Date Clock SET MenuTime Clock SET Menu StructureRS-232 Setup RS-232 Setup Menu StructureBaud Rate Parity Data BitsLine Feed RTS KEY Time Network IDBacklight System InfoSection 1010NFM-3J System Info Menu Structure 1010 Graphic Display Screens30.068.10 Dual Display Screen 11.01Considerations for Critical Applications To Obtain Technical AssistancePipe Considerations for CLAMP-ON Transducer Pipe DimensionsPicking the Appropriate Transducer Flow Velocity RangeRepeatability AccuracyData Stability Data ScatterLOW Flow Rates Flow ConditionsFlow Data Scatter & Damping System 1010 Damping and Slewing ControlsErroneous Liquid Parameter Specification Liquid CompatibilityAeration Temperature and Pressure Ratings TWO-PHASE LiquidsSlurries Viscous LiquidsReference Tables Sonic Velocity for Pure Water @ Various TEMP. meters/secLiquid Deg. C Deg. F Vs m/s Page Recommended Sonic Coupling Compounds CC# USE CharacteristicsReynolds # Positive Comp Negative Comp System 1010 Reynolds Compensation FactorTerm Explanation Terminology ChartRTD Nema DUAL-CHANNEL Menu Chart Meter Type MenuMeter Facilities Menu CLAMP-ON Menu CLAMP-ON Menu Section 1010NFM-3J ÖÚ No Typical Industries Serviced include General Installation GuidelinesLiquid Applicability and Compatibility Typical Applications includeSelecting the Right Flow Tube Flow Tube Mounting LocationFlow Tube Material, Size & Flow Range Ratings To Obtain Technical Assistance Flow Data Scatter and DampingHOW to SET UP System 1010 for Flow Tube Operation Setup ProcedureOverview Press to leave the Channel Setup menu Menu Key Install to start operation Sired Offset Specifications Kynar Pvdf Flow Tube Specifications Cpvc Flow TubeSpecifications 316 Stainless Steel Flow Tube Specifications Teflon PFA Flow Tube1011FT Series 316 Stainless Steel Flow Tube Additional Installation Notes992DFT992DFTSeriesSeriesTeflonTeflonPFA FlowPFATubeFlow Tube Select a Transducer SET for USE by Reflexor Reflexor Installation StepsIncorrect Transducer Placement Select the Transducer Mounting LocationElbow Expansion Contraction Valve Orifice Plate Mounting the Transducers Reflexor Mode Adjacent Transducer MountingInstalling Reflexor Operating Mode Select Reflexor Operating ModeAccess the Install Xdcr Transducer Menu Connection of Transducer CablesSpectra Display Screen Cursor USE on the Spectra Graph HOW to USE Spectra Graph Data and ControlsAdjustment Function Available Adjustments to Spectra GraphReflexor Diagnostic Data Display of F AT no Flow Conditions Selection of Liquid CompositionOther Menu Entries Appendix a Page Site Setup Considerations for 1010/1020N Blind Systems RS-232 Interface CableAppendix 1010NFM-3J Meter Type Cable Type Controlotron Part Number AppendixCommunicating with System 1010/1020 VIA the RS-232 Interface HOW to USE the Windows HyperTerminal ProgramNone Accessing the Installation Menu This is the current measured liquid Data Display ModeKeyboard PC Keyboard Description Terminal Mode Menu CommandsClose the Terminal or HyperTerminal Program Transfer of Information from a 1010/1020 Flowmeter to the PCReset Procedure for Blind Systems To Clear Active Memory Using the RS-232 InterfaceTo Clear All Dynamic Memory Using the RS-232 Interface Appendix1010NFM-3J Transducer and Accessory DrawingsFlow Computer Drawings Channel Drawings990TRMVH-7B Index 1010NFM-3J SymbolsIndex1010NFM-3J Index-2Index-3 Index-4 Index-5 Index-6 Index-7 Index-8 Index-9 Index-10 Index-11 Index-12 TradeMarks of Siemens Energy & Automation Inc TrademarksDuctile Iron Pipe NON-STANDARD Carbon Size