Manual Addendum

1010FMA-14

 

 

EXPANDED I/O MODULE OPTION PROGRAMMING

The diagram below illustrates the Expanded I/O Module Option programming for a Single Channel meter with a 1010N-7 Expanded I/O Module.

FLOW COMPUTER

INTERNAL

CONNECTIONS

`

 

 

 

Io1

`

 

 

 

 

 

Io1

`

 

 

 

 

 

Pgen1

`

 

 

 

 

 

Pgen2

`

 

 

 

 

 

Vo1

`

 

 

 

 

 

Vo2

 

 

 

 

 

 

OUTPUT

TERMINAL STRIP

zAux Io1

zAux Io2

zAux Io3

zAux Io4

NOTE: The 1010N-7 Expanded I/O Module auxiliary output signals (Aux Io1 - Aux Io4) geneated from Pgen1, Pgen2, Vo1 and Vo2 are “mirrored” output currents. For example, if Vo1 is a 5 Vdc signal then Aux Io3 will be 12 mA.

NOTE: The method used to create auxiliary current loops makes it impractical to generate the 2 mA fault current produced by the primary 4-20 mA outputs of the meter.

3

May 2002

Image 12
Contents Sitrans Siemens Energy & Automation’s Standard Warranty Standard Terms and Conditions of Sale 10/1/2004Field Manual For Technical Assistance For General InformationManual Changes Manual Addendum July 1010FMA-4Call 800 631 Fax 631 Or sales.ultrasonicflow@siemens.comSetup Procedure Transducer InstallationManual Addendum 1010FMA-4 Flowmeter Setup Transfer Install Function Transfer Install ProcedureSaving New Transfer Install Site Manual Addendum May 1010FMA-14Manual Addendum 1010FMA-14 For Systems Equipped With 1010N-7 ModulesIntroduction Expanded I/O Module OptionAUX Io Meter Menu DisplayAux Io1 Aux Io2 Aux Io3 Aux Io4 Expanded I/O Module Option ProgrammingTable of Contents Table Of Contents 1010NFM-3J Netflow Alarm Letter Codes and Descriptions Using The 996PSP Pipe Simulator 12.1Meter Facilities Menu And Graphic Display Screens Vii Appendices IndexPipe Table Important Safety Considerations Flowmeter Installation StepsSection 1010NFM-3J Keypad Enable Switch Keypad Function Chart 1010N KeypadIntroduction to the 1010N Menu Screens KEY UsageHOW to USE the Installation Menu Explanation of the CALL-OUTSAccessing and Leaving the Menu HOW to Enter DataSection 1010NFM-3J Selecting Items from an Option List Multiple Select Option Lists Entering Numeric DataMeter Type Menu Section 1010NFM-3J Entering Alphanumeric StringsSection 1010NFM-3J Dual Channel Dual PathChannel 1+2 and Channel Arithmetic Operation Multi-Path OperationSelecting a Meter Type Meter types on the right-hand column. PressChannel Flow Creating a New Site Setup See paragraph Character position Flowmeter Installation Flowchart Using Faststart Setup Choosing the Pipe CLASS/SIZEPicking and Installing the Transducers Section 1010NFM-3J Press . This brings up a Flow Display Screen To scroll between the availAlternate Light Weight 1010WX Case 1010WX CLAMP-ON Liquid Flowmeters1010WX Flowmeter Label System HardwareDisplay and Keypad Options Electronic ModulesGeneral Installation Menu Notes Conventions used with these instructions areChannel Setup Menu HOW to Recall a Site SetupChannel Setup Menu Structure HOW to Enable and Disable a Measurement Channel HOW to CREATE/NAME a Site Setup HOW to ENABLE/DISABLE Site SecurityHOW to Delete a Site Setup HOW to SAVE/RENAME a Site SetupPipe Data Menu Pipe Data Menu Structure ASA Stainless SteelHOW to Select a Pipe Class HOW to Select a Pipe SizeSection 1010NFM-3J Pipe Data Menu Structure HOW to Enter the Pipe OD in. or mm HOW to Select a Pipe MaterialHOW to Enter the Wall Thickness Liner Material Liner ThicknessApplication Data Menu Application Data Menu Structure Application Data Menu Structure HOW to Select a Liquid Class How to Edit the Estimated Vs liquid sonic velocitySection 1010NFM-3J How to Edit the Viscosity cS Setting How to Edit the Density SG SettingUniMass Table Application Data Menu Explanations for UniMass Table Create/Edit Table Point New Point + Points List Vs Vs ValueG. Specific Gravity Viscosity Liquid Viscosity cSEND HOW to Select a Pipe Temperature Range Column Parameter UnitsPipe Configuration Pipe Configuration Menu StructurePipe Configuration Option List Definitions PICK/INSTALL Xdcr MenuFLOW1 HOW to Select a Transducer Model PICK/INSTALL Xdcr Menu StructureHOW to Select a Transducer Size HOW to Select a Transducer Mount ModeHOW to USE the Spacing Offset Reviewing the Spacing MethodHOW to USE Install COMPLETED? Number Index Menu CellLtn Menu Cell Install Completed? Section 1010NFM-3J Force Transmit Procedure DriveMeasured Vs m/s How to Use the Actual MTY Command Empty Pipe SET MenuZero Flow Adjust Menu Section 1010NFM-3J How to Use the MTYmatic CommandHow to Use the Set Empty Command AutoZeroUsing Actual Zero Actual ZeroReversaMatic Using ReversaMatic Reverse Xdcrs / Press ENTZeroMatic optional function Conforms Indicated flow to Actual ZeroOperation Adjust Menu Operation AdjustOperation Adjust Menu Structure Damping ControlDeadband Control MEMORY/FAULT SET Reflexor ZERO/FAULT SET Option Reflexor Mode onlyMemory Delay sec FLOW/TOTAL Units Menu NetflowFlow Volume Units FLOW/TOTAL Units Menu StructureFlow Volume Units Flow Time UnitsTotal Volume Units Flow Display RangeFlow Display Scale Total Resolution Totalizer ScaleTotalizer Mode Mode Flow DirectionBATCH/SAMPLE Total Data SPAN/SET/CAL MenuSpan Data Data SPAN/SET/CAL Menu StructureMaximum span values represent Minimum span values represent Max FlowMin Flow SET Alarm Levels High Temperature Low TemperatureSection 1010NFM-3J High Flow Low FlowSection 1010NFM-3J Interface Vs m/s meters-per-second Aeration %Makeup Latch Calibrate Flow Rate Kc CalibrationTo calculate Kc MultiPoint CalibrationSection 1010NFM-3J Stripchart Setup Menu Section 1010NFM-3J To enable numeric entry pressStripchart Setup Menu Structure Select DataData Display Time BaseStripchart Clear Datalogger Setup MenuDatalogger Setup Menu Structure Datalogger Mode Datalogger DataSection 1010NFM-3J Alarm Letter Codes and Descriptions LOG Time IntervalDatalogger Events Display Datalogger I/O Data Control Menu Analog Output Setup I/O Data Control Menu StructureAnalog Out Setup Data Categories Table To Determine Proper I/O Installation DrawingsSection 1010NFM-3J System 1010 Analog Outputs VfoInstallation Drawing 1010N-2-7 Sheet 2 Installation Drawing 1010N-7-7 Sheet 2Relay Setup 1010N & 1010DN with 1010N-2 ModulesAnalog Input Setup optional function Relay Option ListSection 1010NFM-3J Assigning Relay 1 and 2 Functions Diagnostics Data Menu Setting up the Analog Current InputDiagnostic Data Menu Structure Main Diagnostics Screen Main Diagnostic Menu DescriptionFlow Data Menu Flow Data Menu Items Vs m/sSection 1010NFM-3J HiFlow and LoFlow AnCalApplication Info Menu Liquid Data MenuApplication Info Menu Items Liquid Data Menu ItemsSite Setup Data Menu Site Setup Menu ItemsUsing the HF Menu Item Introduction to HF Menu ItemManual Adjustment Procedure Access Path/Channel Diagnostic DataAutomatic Adjustment Procedure AutomaticTest Facilities Commands Test Facilities MenuMakeup Detection Mode Test Facilities Graph ScreenEntering the Diagnostic Graph Screen Diagnostic Text DisplayTime Base Control Correlated PlotCommand Modes Transit Time Adjustment Hot KeyDigital Damping Control Hot Key 1 Zero Crossover Adjustment Hot Key Envelope Threshold Adjustment Hot Key 5Signal Masking Function Hot Key Description of Graph Screen Text Display ParametersHOT KEY Summary Troubleshooting Tips Flow Computer MessagesMessage Description Using the F4 Reset Sequence Section 1010NFM-3J Troubleshooting with Transducer Test Blocks Using the 1012TB-1 and 2 Test BlocksThk Mode Offset Using the 996PSP Pipe Simulator Mat’l Thk Mode IndexIf a Pipe Simulator/Test-Block Test Fails INSTALLATION/TRANSDUCER Mount Guidelines ProgrammingOPTIMIZATION/CORRECTION of Problems DIAGNOSTIC/PERFORMANCE VerificationNFM-3J START-UPDetection Fault/Low Signal Poor SignalSection 1010NFM-3J Low Valc High VaerOfficial Coupling Compounds Alternative Coupling CompoundsPart# Name Application Max Temp Remarks Trade Name Application Max Temp RemarksHOW to Identify 1011 Transducers and Mounting Hardware Preparing to Mount the TransducersSelecting a Location for CLAMP-ON Transducers CLAMP-ON Transducer Mounting Modes Pipe shown in Top View for ease in visualizing sonic pathPreparing the Pipe PipeReflect Mode Mounting Frames and Spacer BAR Positioned around Mounting FrameReflect Mode with Spacer BAR only Strap Mounting Kit P/N Pipe Diameter Band Sizes QtyInstallation Reflect Mount with Transducers and Spacing BAR Direct Mode Mounting FRAMES, Spacer BAR and Spacing Guides Spacer BAR Not Shown and Spacing GuideMylar Spacing Guide Wrapping the Mylar Spacing Guide around the Pipe Finding the Halfway Distance Using 1012T Mounting Tracks Installing a 1012T Mounting Track in Reflect ModeInstallation Reflect Mount with Mounting Track Front View ÇInstalling a 1012T Mounting Track in Direct Mode Installation Direct Mount 180º Opposed with Mounting TrackChain Tension Mounting Temperature Sensors Wiring Temperature Sensor to the Analog Input Module 1010N Single Channel Temperature Sensor Inputs2 1010N Supply and Return Connections 1012EC Series Terminal TB1 CableDual Path Models CLAMP-ON Resistive Temperature Device RTD Installation Notes Paralleling RTD Inputs for DUAL-CHANNEL Energy MeasurementMeter Facilities Menu and Graphic Display Screen Preferred UnitsTable Setups Menu Pipe TablePipe Table Menu Structure CREATE/EDIT Pipe Section 1010NFM-3J Pipe Table Menu StructureDelete Pipe Transducer Type Menu0A0 Transducer Type Menu StructureDatalogger Control Menu Datalogger Control Menu StructureOutput Datalogger Circular MemoryEST LOG Time Left Clear DataloggerMemory Control Menu Memory Control MenuAnalog Output Trim Menu Current Output Trim Io1 & Io2Voltage Output Trim Vo1 & Vo2 Analog Output Trim Menu StructurePgen Output Trim Pgen 1 & Pgen RTD Calibrate Menu optionalRTD Calibration by Data Entry ICE Bath RTD CalibrationWith ICE During AN ICE Bath Calibration Clock SET Menu DateTime Clock SET Menu StructureRS-232 Setup RS-232 Setup Menu StructureBaud Rate Parity Data BitsLine Feed Network ID RTS KEY TimeBacklight System Info1010 Graphic Display Screens Section 1010NFM-3J System Info Menu Structure30.068.10 11.01 Dual Display ScreenTo Obtain Technical Assistance Considerations for Critical ApplicationsPipe Dimensions Pipe Considerations for CLAMP-ON TransducerPicking the Appropriate Transducer Flow Velocity RangeAccuracy RepeatabilityData Stability Data ScatterFlow Conditions LOW Flow RatesFlow Data Scatter & Damping System 1010 Damping and Slewing ControlsErroneous Liquid Parameter Specification Liquid CompatibilityAeration TWO-PHASE Liquids Temperature and Pressure RatingsSlurries Viscous LiquidsReference Tables Sonic Velocity for Pure Water @ Various TEMP. meters/secLiquid Deg. C Deg. F Vs m/s Page CC# USE Characteristics Recommended Sonic Coupling CompoundsSystem 1010 Reynolds Compensation Factor Reynolds # Positive Comp Negative CompTerminology Chart Term ExplanationRTD Nema DUAL-CHANNEL Menu Chart Meter Type MenuMeter Facilities Menu CLAMP-ON Menu CLAMP-ON Menu Section 1010NFM-3J ÖÚ No General Installation Guidelines Typical Industries Serviced includeLiquid Applicability and Compatibility Typical Applications includeSelecting the Right Flow Tube Flow Tube Mounting LocationFlow Tube Material, Size & Flow Range Ratings Flow Data Scatter and Damping To Obtain Technical AssistanceHOW to SET UP System 1010 for Flow Tube Operation Setup ProcedureOverview Press to leave the Channel Setup menu Menu Key Install to start operation Sired Offset Specifications Cpvc Flow Tube Specifications Kynar Pvdf Flow TubeSpecifications Teflon PFA Flow Tube Specifications 316 Stainless Steel Flow TubeAdditional Installation Notes 1011FT Series 316 Stainless Steel Flow Tube992DFT992DFTSeriesSeriesTeflonTeflonPFA FlowPFATubeFlow Tube Reflexor Installation Steps Select a Transducer SET for USE by ReflexorIncorrect Transducer Placement Select the Transducer Mounting LocationElbow Expansion Contraction Valve Orifice Plate Reflexor Mode Adjacent Transducer Mounting Mounting the TransducersSelect Reflexor Operating Mode Installing Reflexor Operating ModeAccess the Install Xdcr Transducer Menu Connection of Transducer CablesSpectra Display Screen HOW to USE Spectra Graph Data and Controls Cursor USE on the Spectra GraphAvailable Adjustments to Spectra Graph Adjustment FunctionReflexor Diagnostic Data Display of F AT no Flow Conditions Selection of Liquid CompositionOther Menu Entries Appendix a Page Site Setup Considerations for 1010/1020N Blind Systems RS-232 Interface CableAppendix 1010NFM-3J Appendix Meter Type Cable Type Controlotron Part NumberHOW to USE the Windows HyperTerminal Program Communicating with System 1010/1020 VIA the RS-232 InterfaceNone Accessing the Installation Menu Data Display Mode This is the current measured liquidTerminal Mode Menu Commands Keyboard PC Keyboard DescriptionTransfer of Information from a 1010/1020 Flowmeter to the PC Close the Terminal or HyperTerminal ProgramReset Procedure for Blind Systems To Clear Active Memory Using the RS-232 InterfaceTo Clear All Dynamic Memory Using the RS-232 Interface Transducer and Accessory Drawings Appendix1010NFM-3JFlow Computer Drawings Channel Drawings990TRMVH-7B Symbols Index 1010NFM-3JIndex-2 Index1010NFM-3JIndex-3 Index-4 Index-5 Index-6 Index-7 Index-8 Index-9 Index-10 Index-11 Index-12 Trademarks TradeMarks of Siemens Energy & Automation IncDuctile Iron Pipe Size NON-STANDARD Carbon