EOCR-i3BZ/iFBZ/3BZ2/FBZ2
Over current and time setting tips
●Over current
Setting tips in definite TCC mode
1.Over current threshold (OC) :
-Set the OC at the rating current of a motor. To protect machine together, it is recommended to set at 110~120% of the actual normal operating current.
2.Starting delay time
-Set an expected
time to reach the normal operation current by monitoring the displayed current and then set the time at 2 sec longer than the time measured. For a
3.Operation time
Configuration tips when Inverse or Thermal Inverse characteristic is necessary
1.Overcurrent threshold (oc) :
-This value is the basic current and from the point of 105% of oc, the inverse curve starts. Usually oc is set to the rated current of the motor.
2.Starting delay time
-Usually this value is set to zero. With zero
-But if the user wants fast trip with very high current during starting, set
-If the Inverse is selected, and
-If Thermal Inverse is selected, it detects overcurrent regardless of
3.Operation time
-When Inverse or Thermal Inverse is selected,
graphical representation of Inverse or Thermal Inverse to check trip time.
Caution : Do not use any External CT
Alert Operation Pattern (#3)
Do use this function by OL/GR common output.
Running Stage | Normal Operation | Higher than the preset |
Starting | Trip | |
ALo Selection |
| Alert value |
Aux |
|
|
Flicker |
| 1 Sec |
| ◀▶ | |
|
| |
Hold |
| 1 Sec |
| ◀▶ | |
|
|
Fail-safe operation
under normal operation
and Tripped
ON
OFF