Schneider Electric 3BZ2, iFBZ, FBZ2, EOCR-i3BZ manual Protection functions, Auxillary functions

Page 7

EOCR-i3BZ/iFBZ/3BZ2/FBZ2

EOCR-i3BZ / iFBZ : Intelligent Digital Over-Current, Earth Fault Relay with built-in ZCT,

EOCR-3BZ2 / FBZ2 : Economic Digital Over-Current, Earth Fault Relay with built-in ZCT

Protection functions

Item

Operating Condition & Setting Range

Operation Time

Over Current (oc)

Load current(In) exceeds threshold(Is)

Definite(Def) : 0.2~30s Adjustable

Setting Range : 0.5~80A(Def), 0.5~32A(Inv & th)

Inverse(Inv) & Thermal(th) : 1~30 Class

 

 

 

 

Under Current (uc)

Load current(In) less than threshold(uc) In <= uc

oFF, 1~30s Adjustable

uc should be less than oc Setting

 

 

 

 

 

Phase Loss (PL)

max imbalance is more than 85% among 3 phase current,

oFF, 0.5~5s Adjustable

Enable or disable : Selectable

 

 

 

 

 

Reverse Phase(rP)

Reversed phase sequence input on EOCR.

Within 0.15s

Enable or disable : Selectable

 

 

 

 

 

 

Active only in motor starting, In Stall threshold (Sc×OC).

 

Stall (Sc)

Setting Range : Adjustable

Immediately after D-Time elapsed

 

2~8 times of oc setting if Sc×OC doesnt exceed 250A

 

 

 

 

 

Active only in motor running, In Jam threshold (JA×OC).

 

Jam (JA)

Setting Range :

0.2~10s Adjustable

 

1.5~8 times of oc setting if JA×OC doesnt exceed 250A

 

 

 

 

 

Current unbalance threshold1~10s Adjustable.

 

Unbalance (ub)

Setting Range : 10~50%

1~10s Adjustable

Unbalance[%] = 100 × (Max phase current - Min phase current)/

 

 

 

Max phase current

 

 

 

 

Earth Fault (EF)

EF current(Ie) exceeds threshold(Ies)

0.1~10s Adjustable

Setting Range : oFF, 0.03~10A

 

 

 

 

 

 

Auxillary functions

Password

Secure configuration, available only with i3BZ/iFBZ

 

 

Communication

Serial network communication for monitoring of metering, status, and fault history

 

 

Fail Safe

Enable/Disable fail-safe operation of OL trip output

 

 

Phase selection

Select a Single-phase motor or 3-Phase motor

 

 

Total Running-Hour

Record of total running from installation which cannot be modified or cleared

 

 

Running-Hour

Accumulated running hour from preset point which can be cleared to zero, when motor stops

 

 

Fault History

Records for recent 3 faults each phase current which stored in a non-volatile memory

 

 

Limitation of autoreset attempt

Block auto-reset if the reset count exceeds the pre-set count within 30 minutes

 

 

Communication function (Applicable to i3BZ/iFBZ)

Item

Setting

Remark

Protocol type

Modbus RTU

 

 

 

 

Communication type

RS-485

 

 

 

 

Baud rate

1.2, 2.4, 4.8, 9.6, 19.2, 38.4 kbps

 

 

 

 

Maximum length of the bus

Maximum 1.2kM

Depend on the environment

 

 

 

Type of trunk cable

RS-485 Shielded Twist 2-Pair Cable

 

 

 

 

7

Image 7
Contents Page Page Bottom hole & terminal type Applications Public institutions EOCR-i3BZ/iFBZ/3BZ2/FBZ2 General FeaturesCommunication function Applicable to i3BZ/iFBZ Operating Condition & Setting Range Operation TimeProtection functions Auxillary functionsSpecifications Time-current characteristic curve Fail-safe operation Over current and time setting tipsOver current Setting tips in definite TCC mode Alert Operation Pattern #3Current display Front faceBar graph Buttons and Setting Sequence Phase digital ammeter functionButton Description Parameter Description Setting sequence and menuAlert *1 Menu Parameter Description DefaultCommunication *2 Control terminals Trip cause indication and fault recordsSingle line Diagram Wiring ExamplesPhase line Diagram Single phase line DiagramDimensions Order Code RS485 bus connection Modbus network settingStandard connection Bus connection through a SCA type junction box Iksan Plant Head Office