Modbus network setting

Communication setting value

Please set the Modbus communication parameters by PCON or HMI for the communication. Slave address

Baud rate Parity

Communication loss timeout

Slave address

The EOCR has slave addresses from 1 to 247.

The factory default setting is 1.

Baud rate

The Communication speed provided is like below. 1.2kbps

2.4kbps 4.8kbps 9.6kbps 19.2kbps 38.4kbps

The factory default setting is 19.2kbps

Parity setting

Even Odd None

The factory default setting is even. Please refer to the table for the stop bit setting.

Parity setting

Stop bit

Even or Odd

1

None

2

Communication loss timeout

It is the criteria to confirm the communication disconnection with a master like as PLC. EOCR judges it as a communication disconnection error, if there is no call from the master during a certain preset time.

The time setting range is 1~999sec the factory default setting is OFF. The OFF means no communication error check. It is advised to set it at OFF, if there is no concern of communication disconnection or no needs of communication error check at ordinary times.

RS485 bus connection

RS485 standard allows several different characteristics. Polarization

Line terminator Number of slaves Length of the bus

There is a definition of Modbus presented in detail at the website of Modbus.org in 2002. Standard connection.

19

Image 19
Contents Page Page Bottom hole & terminal type Applications Public institutions EOCR-i3BZ/iFBZ/3BZ2/FBZ2 General FeaturesCommunication function Applicable to i3BZ/iFBZ Operating Condition & Setting Range Operation TimeProtection functions Auxillary functionsSpecifications Time-current characteristic curve Fail-safe operation Over current and time setting tipsOver current Setting tips in definite TCC mode Alert Operation Pattern #3Current display Front faceBar graph Buttons and Setting Sequence Phase digital ammeter functionButton Description Parameter Description Setting sequence and menuAlert *1 Menu Parameter Description DefaultCommunication *2 Control terminals Trip cause indication and fault records Single line Diagram Wiring Examples Phase line Diagram Single phase line DiagramDimensions Order Code RS485 bus connection Modbus network settingStandard connection Bus connection through a SCA type junction box Iksan Plant Head Office