EOCR-i3BZ/iFBZ/3BZ2/FBZ2
Setting sequence and menu
No. | Menu |
| Parameter | Description |
| Default | |||
|
|
|
|
|
| Threshold of Alert output, set by % of the over current threshold (oc). If the load |
|
|
|
|
|
|
|
|
| current is higher than this value, alert |
|
|
|
|
|
|
|
|
| according to the setting of “ALo:XX”. |
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| If the load current is detected, alert |
|
|
|
|
|
|
|
|
| threshold is no meaning for this operation. |
|
|
|
|
|
|
|
|
| Refer to the Alert Operation Pattern. |
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| If the load current is higher than the alert threshold, alert |
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
| repeats open for 1s and close for 1s (flickering), The flickering starts from the |
|
|
|
|
|
|
|
|
|
|
|
| |
22 | Alert *1) |
|
|
|
| motor starting. |
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
| Refer to the Alert Operation Pattern. |
|
|
|
|
|
|
|
|
| If the load current is higher than the alert threshold, alert |
|
|
|
|
|
|
|
|
| closed (holding) and remains closed until the load current decrease under the |
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
| alert threshold. The alert output is blocked during motor starting. |
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
| Refer to the Alert Operation Pattern. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| If the accumulated running hour is more than the Running Hour threshold, |
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
| the alert output repeats close for 1s and open for 1s. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| The alert output is used only for under current protection. If this mode is selected, |
|
|
|
|
|
|
|
|
| a trip by an under current fault is signaled through alert |
|
|
|
|
|
|
|
|
| overload trip |
|
|
|
|
|
|
|
|
|
|
|
|
Fault reset by a power cycle or by pressing the ESC button.
|
| Fault reset only by pressing the ESC button. |
| |
23 | Reset |
|
| |
|
| Fault reset by a |
| |
|
| Setting range of the timer : 0.5sec~20min. |
| |
|
| Also the fault can be reset by a power cycle or by ESC button. |
| |
|
| The maximum |
| |
24 | Reset Limitation | The |
| |
pressing ESC button when the counter reaches the limitation. |
| |||
|
|
| ||
|
| To disable limitation, select “oFF”. Setting range : oFF~5 times. |
| |
|
| In this menu, toggle display, |
| |
25 | Total Running Hour | The accumulation starts from the installation and the user cannot clear the | Not | |
accumulated value. | adjustable | |||
|
| |||
|
| This display unit is 1 hour. |
| |
|
| In this menu, toggle display, |
| |
|
| user can clear the accumulated value by selecting the running hour threshold to |
| |
26 | Running Hour | “rh:oFF”. When motor stops | Not | |
This display unit is 0.1 hour (6 minutes). | adjustable | |||
|
| |||
|
| By selecting “ALo:to”, the user can get the alert signal through alert |
| |
|
| when the accumulated value is more than the running hour threshold. |
| |
| Running Hour | Threshold for alert output when the user selects “ALo:to”. The unit is 10 hours |
| |
27 | and this menu is not displayed when the motor is starting or running. |
| ||
Threshold |
| |||
| Setting range : 10~9990 hours, oFF |
| ||
|
|
| ||
|
| Modbus slave address. |
| |
|
| Range : 1 ~ 247. |
| |
|
| Setting for Communication speed |
| |
|
| Range : 1.2kbps, 2.4Kbps, 4.8Kbps, 9.6Kbps,19.2Kbps, 38.4Kbps . |
| |
28 | Communication*2) | Parity setting |
| |
|
| Range : odd, even, non. |
| |
|
| Duration for communication loss detection. |
| |
|
| Displays alarm when no new communication data is received for the duration. |
| |
|
| If “oFF” is selected, no monitoring for communication channel is activated. |
| |
|
| Setting range : 1~999 sec, oFF |
| |
|
| When this menu activated, OL trip signal and enabled EF trip signal is generated |
| |
|
| when (3s+ot) expires. The display shows “End” when the test is done. |
| |
29 | Test Trip | By pressing ESC, returns to the load current display mode. | No | |
This menu is not displayed when the motor is starting or running. | parameter | |||
|
| |||
|
| Before (3s+ot) expires, pressing ESC or motor starting or running blocks the test |
| |
|
| trip and return to the load current display. |
| |
30 | End | This shows the end of test trip. Test result is stored in the fault record. | No | |
parameter | ||||
|
|
|
*1) This menu is only available in “C” Type.
*2) These are applied to i3BZ & iFBZ only.
14