Selection Procedure - IP Units

Cooling Capacity

Step 1

Calculate the building’s total and sensible cooling loads at design conditions. Use the Trane calculation form or any other standard accepted method.

Step 2

Size the equipment usingTable PD-1a. Match the cooling loads at design conditions.

Example: The following are the building cooling requirements:

A

Electrical Characteristics: 380–415/50/3

B

Summer Design Conditions:

Entering Evaporator Coil: 80 DB/ 67 WB

Outdoor Ambient: 95

C

Total Cooling Load: 53 MBh

D

Sensible Cooling Load: 33 MBh

E

Airflow: 2,000 cfm

External Static Pressure: .52 in. w.g.

F

Downflow Configuration

Table PD-1a shows that a WSC060AD has a gross cooling capacity of 59.0 MBh and 45.7 MBh sensible capacity at 95 degree ambient and 2,000 cfm with 80 DB/67 WB air entering the evaporator.

To find the net cooling capacities, fan motor heat must be subtracted. Determine the total unit static pressure:

External Static

0.52 in.

Standard Filter 1 in.

0.15 in.

Economizer

0.18 in.

Supplementary Electric Heat

0.083 in.

Total Static Pressure

0.933 in.

Note: The Evaporator Fan Performance Table PD-9a has deducted the pressure drop for a 1 in. filter already in the downflow unit.

Therefore, the actualTotal Static Pressure is 0.933 – 0.15 = 0.78. With 2,000 cfm and 0.78 inches,Table PD-9a shows 1.00 bhp.

Note below the table gives a formula to calculate Fan Motor Heat,

Fan Motor Heat (MBh) = 2.915 x (Fan bhp) + 0.451

= 2.915 x 1.00 + 0.451 = 3.37 MBh

NetTotal Cooling Capacity =

57 – 3.37 = 53.6 MBh

Net Sensible Cooling Capacity =

38 – 3.37 = 34.6 MBh

Heating Capacity

Step 1

Calculate the building heating load using theTrane calculation form or other standard accepted method.

Step 2

Size the equipment usingTable PD-5a to match the heating loads at design conditions.

A

Total Heating Load: 50 MBh

B

Outdoor Ambient (Winter) 17 DB

C

Indoor Return Temperature: 70 DB

D

Airflow: 2,000 cfm

Use the portion ofTable PD-5a for the WSC060AD to determine capacity at winter design conditions. The mechanical heating portion of the heat pump will provide 29.1 MBh.

Step 3

Because 29.1 MBh is less than the building’s required heating capacity at winter design conditions, a supplementary heater must be selected.

50 MBh – 29.1 MBh = 29.9 MBh

FromTable PD-9a, at 380 volts, the 38.0 MBh Heater will be adequate to do the job.

10.9 kW 38.0 MBh

FromTable ED-2 select heater BAYHTRR418A (38.0 MBh at 380 volts).

Air Delivery Selection

External static pressure drop through the air distribution system has been calculated to be 0.80 inches of water. EnterTable PD-9a for a WSC060AD at 2000 cfm and 0.80 static pressure. The standard motor will give the desired airflow.

Accessory Selection

Select accessories needed to accommodate the application.

PKGP-PRC004-EN

11

Image 11
Contents Packaged Heat Pumps American Standard Inc. All rights reserved IntroductionContents Features and Benefits Flexible Applications Easy Access Low Voltage Terminal BoardStandardized Components ReliaTel Micro Micro ControlsComm-3/4Trane Communication Interface Hinged Access DoorsPhase Monitor EconomizerVariTrac Quality And Reliability TestingWe test designs at our factory not on our customers Unit Pitch Barometric ReliefCondensate Trap Clearance RequirementsAir Delivery Selection Accessory SelectionCooling Capacity Step Heating Capacity StepSelection Procedure IP Units 060 11 12,13 Model Number DescriptionTable GD-1 General Data General DataTable PD-1a Gross Cooling Capacities MBH WSC060AD,T IP Performance DataTable PD-1 Gross Cooling Capacities kW WSC060AD,T SI Table PD-2a Gross Cooling Capacities MBH WSC072AD,T IP Table PD-2 Gross Cooling Capacities kW WSC072AD,T SITable PD-3a Gross Cooling Capacities MBH WSC090AD,T IP Table PD-3 Gross Cooling Capacities kW WSC090AD,T SITable PD-4a Gross Cooling Capacities MBH WSC120AD,T IP Table PD-4 Gross Cooling Capacities kW WSC120AD,T SIPerformance Data At Indicated Indoor Dry Bulb Temp C Performance Data 10.1 10.6 11.1 10.0 10.410.2 10.6 10.4 10.8Hi Static Drive Nom kW Standard Motor & Hi Static Drive2 HP Standard Motor & Static Drive 2 HP Standard Motor2 HP Std Motor & Drive Nom kW Standard Motor Hi Static DriveNom kW Standard Motor DriveHP Over-Sized Motor & Hi Static Drive Nom kW Standard Motor DriveNom kW Over-Sized Motor 2 HP Std Motor 2 HP Standard Motor Hi Static Drive1920 1002 Nom kW Standard Motor & Drive Hi Static DriveExternal Static Pressure Pascals 275 300 325 350 375 M3/h 3260 1002HP Standard Motor Nom kW Std Motor Nom kW Standard MotorNom kW Over-Sized Motor & Hi Static Drive HP Standard Motor Hi Static Drive2400 1051 Nom kW Standard Motor Nom kW OSHP Over-Sized Motor Hi Static Drive HP Standard Motor & High Static Drive Nom kW Standard Motor & Low Static DriveNom kW Standard Motor & High Static Drive HP Standard Motor & Low Static DriveHP Std Motor & Drive 807 844Table PD-20 Over-Sized Motor & Drive Sheave/Fan Speed RPM Table PD-21 Sound Power Level dB ref -12WattsTable PD-17 Standard Motor & Sheave/Fan Speed RPM 4080 4890 Econimizer withOA/RA Dampers2 3400 4080 3260Table PD-24a Auxiliary Electric Heat Capacity Table PD-24 Auxiliary Electric Heat Capacity10.9 11.3 12.1 Variation From Nominal Airflow Temperature Rise MultiplierTon 3400 M 3/H 4100 M 3/H 5100 M 3/H 6800 M 3/H StagesIntegrated Comfort System Sensors available Controls180-220 Table ED-1 Unit WiringElectrical Data 342-45614.4 17.2 KW Rating380 / 415 Volts 10.9 13.0Compressor Motor Condenser Fan Motor Unit Amps Model No Volts Phase380-415 108Jobsite Connections Wires, 24-volts, with Electric HeatDataWSC060 DimensionalDataWSC060 DataWSC072-120 DataWSC072-120 WSC072-120 Roof Curb WSC060 Barometric Relief Damper AccessoriesWSC072-120 Dimensional OptionsTable W-2a Accessory Net Weights1, 2 lbs WeightsTable W-2 Accessory Net Weights1, 2 kg Mechanical Specifications Manual Outside Air Damper Electric HeatersRoof Curb Remote PotentiometerZone Sensors Differential Pressure SwitchesCOMM3/4Trane Communications Interface Comm-5 LonTalk Communication InterfacePKGP-PRC004-EN PKGP-PRC004-EN Stocking Location Webb/Mason 02-04 Electronic Only Literature Order NumberFile Number PL-UN-000-PKGP-PRC004-EN-02-04 Supersedes PL-UN-000-PKGP-PRC004-EN-12-03