Performance
Data
Table
|
|
|
|
|
|
|
|
|
| External Static Pressure (Pascals) |
|
|
|
|
|
|
|
|
| |||||
| 25 |
|
| 50 |
| 75 |
| 100 |
| 125 | 150 | 175 | 200 | 225 | 250 |
| ||||||||
m3/h | RPM | kW | RPM | kW | RPM | kW | RPM | kW | RPM | kW | RPM | kW | RPM | kW | RPM | kW | RPM | kW | RPM | kW | ||||
| 1.12 Nom kW Standard Motor & Low Static Drive |
|
|
|
|
|
| 1.12 Nom kW Standard Motor & Drive |
|
|
| |||||||||||||
3260 | — | — | 541 | 0.22 | 603 |
| 0.28 | 657 | 0.33 |
| 705 | 0.38 | 751 | 0.44 | 794 | 0.50 | 835 | 0.56 | 874 | 0.62 | 912 | 0.68 |
| |
3670 | — | — | 579 | 0.29 | 635 |
| 0.35 | 688 | 0.41 |
| 736 | 0.47 | 779 | 0.53 | 821 | 0.59 | 860 | 0.65 | 898 | 0.72 | 936 | 0.79 |
| |
4080 | 565 | 0.31 |
| 620 | 0.37 | 670 |
| 0.43 | 720 | 0.50 |
| 768 | 0.56 | 810 | 0.63 | 850 | 0.70 | 888 | 0.76 | 925 | 0.83 | 961 | 0.91 |
|
4490 | 610 | 0.40 |
| 662 | 0.47 | 709 |
| 0.53 | 753 | 0.60 |
| 799 | 0.67 | 843 | 0.75 | 882 | 0.82 | 919 | 0.89 | 954 | 0.97 | 987 | 1.04 |
|
4890 | 657 | 0.51 |
| 705 | 0.58 | 749 |
| 0.64 | 791 | 0.72 |
| 832 | 0.79 | 874 | 0.88 | 914 | 0.96 | 950 | 1.04 | 985 | 1.12 | 1018 | 1.20 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 1.12 Nom kW Standard Motor | |||||
|
|
|
| External Static Pressure (Pascals) |
|
|
|
|
|
|
|
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| & Hi Static Drive |
|
|
| ||||||||
| 275 |
| 300 | 325 | 350 |
| 375 |
|
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||
m3/h | RPM | kW | RPM | kW | RPM | kW | RPM | kW | RPM | kW |
|
|
|
|
|
|
|
|
|
|
| |||
| 1.12 Nom kW Standard Motor |
|
| 1.12 Nom kW Standard Motor & |
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
| & Drive |
|
|
|
|
| Hi Static Drive |
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
3260 | 948 | 0.75 |
| 982 | 0.81 | 1015 |
| 0.87 | 1047 | 0.93 |
| 1079 | 0.99 |
|
|
|
|
|
|
|
|
|
|
|
3670 | 971 | 0.86 |
| 1004 | 0.93 | 1037 |
| 1.00 | 1069 | 1.07 |
| 1099 | 1.14 |
|
|
|
|
|
|
|
|
|
|
|
4080 | 995 | 0.98 |
| 1027 | 1.06 | 1060 |
| 1.13 | 1091 | 1.21 |
| 1121 | 1.29 |
|
|
|
|
|
|
|
|
|
|
|
4490 | 1021 | 1.12 |
| 1053 | 1.20 | 1085 |
| 1.28 | 1115 | 1.36 |
| 1145 | 1.45 |
|
|
|
|
|
|
|
|
|
|
|
4890 | 1050 | 1.28 |
| 1081 | 1.36 | 1112 |
| 1.44 | 1140 | 1.53 |
| 1170 | 1.62 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 1.50 Nom kW |
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
| & Hi Static Drive |
|
|
|
|
|
|
|
|
|
|
|
|
| ||
Notes: |
|
|
|
|
|
|
|
|
|
|
|
|
| Factory Supplied Motors, In Commercial Equipment, Are |
|
|
|
| ||||||
Data Includes Pressure Drop Due To Wet Coils And Filters. |
|
|
|
|
|
|
|
|
| |||||||||||||||
|
|
|
|
| Definite Purpose Motors, Specifically Designed And Tested To |
|
|
| ||||||||||||||||
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132 |
|
|
|
|
|
|
|
| ||||||||||||||||
|
|
|
|
| Operate Reliably And Continuously At All Cataloged Conditions. |
|
|
| ||||||||||||||||
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464 |
|
|
|
|
|
|
|
| ||||||||||||||||
|
|
|
|
| Using The Full Horsepower Range Of Our Fan Motors As Shown |
|
|
| ||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| In Our Tabular Data Will Not Result In Nuisance Tripping Or |
|
|
|
|
Premature Motor Failure. Our Product’s Warranty Will Not Be
Affected.
Table
|
|
|
|
|
|
|
|
|
| External Static Pressure (Inches of Water) |
|
|
|
|
|
|
| ||||||
| 0.10 | 0.20 | 0.30 |
| 0.40 | 0.50 | 0.60 | 0.70 | 0.80 | 0.90 | 1.00 | ||||||||||||
CFM |
| RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP |
| RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | |
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||
1920 |
| — | — | 541 | 0.30 | 603 | 0.37 |
| 657 | 0.44 | 705 | 0.51 | 751 | 0.59 | 794 | 0.67 | 835 | 0.75 | 874 | 0.83 | 912 | 0.92 | |
2160 |
| — | — | 579 | 0.39 | 635 | 0.46 |
| 688 | 0.55 | 736 | 0.63 | 779 | 0.71 | 821 | 0.79 | 860 | 0.88 | 898 | 0.97 | 936 | 1.06 | |
2400 | 565 | 0.42 | 620 | 0.49 | 670 | 0.57 |
| 720 | 0.66 | 768 | 0.76 | 810 | 0.84 | 850 | 0.93 | 888 | 1.02 | 925 | 1.12 | 961 | 1.22 | ||
2640 | 610 | 0.54 | 662 | 0.62 | 709 | 0.71 |
| 753 | 0.80 | 799 | 0.90 | 843 | 1.00 | 882 | 1.10 | 919 | 1.20 | 954 | 1.29 | 987 | 1.39 | ||
2880 | 657 | 0.68 | 705 | 0.78 | 749 | 0.86 |
| 791 | 0.96 | 832 | 1.06 | 874 | 1.17 | 914 | 1.28 | 950 | 1.39 | 985 | 1.50 | 1018 | 1.60 | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
|
|
|
| External Static Pressure (Inches of Water) |
|
|
|
|
|
|
|
|
|
| |||||||||
| 1.10 | 1.20 | 1.30 |
| 1.40 | 1.50 |
|
|
|
|
|
| Hi Static Drive |
|
| ||||||||
CFM |
| RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP |
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
| & Hi Static Drive |
|
| & Hi Static Drive |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
1920 |
| 948 | 1.00 | 982 | 1.08 | 1015 | 1.16 |
| 1047 | 1.25 | 1079 | 1.33 |
|
|
|
|
|
|
|
|
|
|
|
2160 | 971 | 1.15 | 1004 | 1.25 | 1037 | 1.34 |
| 1069 | 1.43 | 1099 | 1.52 |
|
|
|
|
|
|
|
|
|
|
| |
2400 | 995 | 1.32 | 1027 | 1.42 | 1060 | 1.52 |
| 1091 | 1.62 | 1121 | 1.73 |
|
|
|
|
|
|
|
|
|
|
| |
2640 | 1021 | 1.50 | 1053 | 1.60 | 1085 | 1.72 |
| 1115 | 1.83 | 1145 | 1.94 |
|
|
|
|
|
|
|
|
|
|
| |
2880 | 1050 | 1.71 | 1081 | 1.82 | 1112 | 1.94 |
| 1140 | 2.05 | 1170 | 2.17 |
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
| 2 HP |
|
|
|
|
|
|
|
|
|
|
|
| ||||||
Notes: |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Data Includes Pressure Drop Due To Wet Coils And Filters. |
|
|
|
|
| Factory Supplied Motors, In Commercial Equipment, |
|
|
|
| |||||||||||||
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451 |
|
|
|
|
| Are Definite Purpose Motors, Specifically Designed And Tested To |
|
| |||||||||||||||
2 HP – Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500 |
|
|
|
|
| Operate Reliably And Continuously At All Cataloged Conditions. |
|
| |||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Using The Full Horsepower Range Of Our Fan Motors As Shown In
Our Tabular Data Will Not Result In Nuisance Tripping Or Premature
Motor Failure. Our Product’s Warranty Will Not Be Affected.
24 |