Performance
Data
Table
|
| 5 Ton | 6 Ton | 7.5 Ton | 10 Ton | ||||
|
| 3400 M3/H |
| 4100 M3/H |
| 5100 M3/H |
| 6800 M3/H |
|
kW | Stages | WSC060AD, T | WSC072AD, T | WSC090AD, T | WSC120AD, T | ||||
|
|
|
|
|
|
|
|
|
|
7.5 | 2 | 6.6 |
| — | — | — | |||
8.3 | 2 | 7.3 |
| — | — | — | |||
9.0 | 2 | 7.9 |
| — | — | — | |||
10.9 | 2 | 9.6 |
| — | — | — | |||
11.3 | 1 | — | 8.3 |
| 6.6 |
| — | ||
12.1 | 2 | 10.6 |
| — | — | — | |||
12.5 | 1 | — | 9.1 |
| 7.3 |
| — | ||
13.0 | 2 | 11.4 |
| — | — | — | |||
13.5 | 1 | — | 9.9 |
| 7.9 |
| — | ||
14.4 | 2 | 12.6 |
| — | — | — | |||
16.0 | 2 | 14.0 |
| — | — | — | |||
16.9 | 2 | — | 12.4 |
| 9.9 |
| 7.4 |
| |
17.2 | 2 | 15.1 |
| — | — | — | |||
18.8 | 2 | — | 13.8 |
| 11.0 |
| 8.3 |
| |
20.2 | 2 | — | 14.8 |
| 11.8 |
| 8.9 |
| |
22.6 | 2 | — | 16.5 |
| 13.2 |
| 9.9 |
| |
25.0 | 2 | — | 18.3 |
| 14.6 |
| 11.0 |
| |
26.9 | 2 | — | 19.7 |
| 15.7 |
| 11.8 |
| |
33.9 | 2 | — | — | — | 14.9 |
| |||
37.5 | 2 | — | — | — | 16.5 |
| |||
40.4 | 2 | — | — | — | 17.7 |
| |||
|
|
|
|
|
|
|
|
|
|
Note: |
|
|
|
|
|
|
|
|
|
For minimum design airflow, see performance table for each unit.
To calculate temp rise at differrent airflow, use following formula:
Temp. Rise (C0) across Elect Htr = (kW x 2985) / (M3/H)
Table
|
| 5 Ton | 6 Ton | 7.5 Ton | 10 Ton | ||||
|
| 2000 CFM |
| 2400 CFM |
| 3000 CFM |
| 4000 CFM |
|
kW | Stages | WSC060AD, T | WSC072AD, T | WSC090AD, T | WSC120AD, T | ||||
|
|
|
|
|
|
|
|
|
|
7.5 | 2 | 11.9 |
| — | — | — | |||
8.3 | 2 | 13.1 |
| — | — | — | |||
9.0 | 2 | 14.2 |
| — | — | — | |||
10.9 | 2 | 17.2 |
| — | — | — | |||
11.3 | 1 | — | 14.9 |
| 11.9 |
| — | ||
12.1 | 2 | 19.1 |
| — | — | — | |||
12.5 | 1 | — | 16.5 |
| 13.2 |
| — | ||
13.0 | 2 | 20.5 |
| — | — | — | |||
13.5 | 1 | — | 17.8 |
| 14.2 |
| — | ||
14.4 | 2 | 22.8 |
| — | — | — | |||
16.0 | 2 | 25.3 |
| — | — | — | |||
16.9 | 2 | — | 22.3 |
| 17.8 |
| 13.4 |
| |
17.2 | 2 | 27.2 |
| — | — | — | |||
18.8 | 2 | — | 24.8 |
| 19.8 |
| 14.9 |
| |
20.2 | 2 | — | 26.6 |
| 21.3 |
| 16.0 |
| |
22.6 | 2 | — | 29.8 |
| 23.8 |
| 17.9 |
| |
25.0 | 2 | — | 32.9 |
| 26.3 |
| 19.8 |
| |
26.9 | 2 | — | 35.4 |
| 28.3 |
| 21.3 |
| |
33.9 | 2 | — | — | — | 26.8 |
| |||
37.5 | 2 | — | — | — | 29.6 |
| |||
40.4 | 2 | — | — | — | 31.9 |
| |||
|
|
|
|
|
|
|
|
|
|
NOTE: |
|
|
|
|
|
|
|
|
|
For minimum design airflow, see performance table for each unit.
To calculate temp rise at differrent airflow, use following formula:
Temp. Rise (F0) across Elect Htr = (kW x 3414) / ( 1.08 x CFM)
Table
% Variation From Nominal Airflow – 20 | – 15 | – 10 | – 5 | 0 | + 5 | + 10 | + 15 | + 20 | |
Temperature Rise Multiplier | 1.25 | 1.17 | 1.11 | 1.05 | 1 | 0.95 | 0.91 | 0.87 | 0.83 |
|
|
|
|
|
|
|
|
|
|