Performance
Data
Table
|
|
|
|
|
|
|
| External Static Pressure (Pascals) |
|
|
|
|
|
|
|
|
| ||||
|
| 25 |
| 50 |
| 75 | 100 | 125 | 150 | 175 | 200 | 225 | 250 | ||||||||
m3/h | RPM | kW | RPM | kW | RPM | kW | RPM | kW | RPM | kW | RPM | kW | RPM | kW | RPM | kW |
| RPM | kW | RPM | kW |
| 1.50 Nom kW Std Mtr & Low Static Drive |
|
|
|
| 1.50 Nom kW Standard Motor & Drive |
|
|
|
|
| ||||||||||
4080 | — | — | 686 | 0.43 | 737 | 0.49 | 787 | 0.57 | 831 | 0.64 | 870 | 0.70 | 908 | 0.76 | 944 | 0.84 | 980 | 0.92 | 1015 | 0.99 | |
4590 | 718 | 0.53 | 753 | 0.59 | 792 | 0.65 | 839 | 0.72 | 882 | 0.80 | 922 | 0.88 | 958 | 0.95 | 992 | 1.02 | 1026 | 1.10 | 1058 | 1.18 | |
5100 | 789 | 0.71 | 822 | 0.78 | 853 | 0.84 | 892 | 0.91 | 935 | 0.99 | 974 | 1.08 | 1011 | 1.18 | 1044 | 1.25 |
| 1076 | 1.33 | 1106 | 1.41 |
5610 | 862 | 0.93 | 892 | 1.01 | 921 | 1.08 | 951 | 1.15 | 988 | 1.22 | 1026 | 1.31 | 1062 | 1.42 | 1096 | 1.52 |
| 1129 | 1.61 | 1158 | 1.69 |
6120 | 934 | 1.20 | 963 | 1.28 | 990 | 1.35 | 1016 | 1.43 | 1045 | 1.51 | 1079 | 1.59 | 1115 | 1.69 | 1148 | 1.80 | 1180 | 1.91 | 1210 | 2.02 | |
|
|
|
|
|
|
|
|
|
| 1.50 Nom kW Standard Motor & |
|
|
| 2.24 Nom kW OS |
| ||||||
|
|
|
|
|
|
|
|
|
|
| Hi Static Drive |
|
|
| Motor & Hi Static Drive |
|
External Static Pressure (Pascals)
275300325350375 m3/h RPM kW RPM kW RPM kW RPM kW RPM kW
4080 | 1051 | 1.50 Nom kW Standard Motor & Hi Static Drive | 1185 | 1.39 | ||||||
1.07 | 1085 | 1.15 | 1118 | 1.23 | 1152 | 1.31 | ||||
4590 | 1090 | 1.27 | 1122 | 1.36 | 1153 | 1.45 | 1185 | 1.53 | 1216 | 1.62 |
5100 | 1136 | 1.49 | 1165 | 1.59 | 1194 | 1.68 | 1223 | 1.78 | 1251 | 1.88 |
5610 | 1187 | 1.78 | 1214 | 1.86 | 1242 | 1.96 | 1269 | 2.06 | 1296 | 2.17 |
6120 | 1239 | 2.12 | 1266 | 2.21 | 1291 | 2.30 | 1317 | 2.39 | 1343 | 2.49 |
2.24 Nom kW Over-Sized Motor & Hi Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters
1.50kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464
2.24kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected.
Table
|
|
|
|
|
|
|
|
|
| External Static Pressure (Inches of Water) |
|
|
|
|
|
|
|
|
| ||||||
|
| 0.10 | 0.20 | 0.30 | 0.40 | 0.50 | 0.60 |
| 0.70 | 0.80 | 0.90 | 1.00 |
| ||||||||||||
CFM | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP |
| RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | ||||
|
| 2 HP Standard Motor & Low Static Drive |
|
|
|
| 2 HP Standard Motor & Drive |
|
|
|
|
|
|
|
| ||||||||||
2400 |
| — | — | 686 | 0.58 | 737 | 0.66 | 787 |
| 0.76 | 831 | 0.85 | 870 | 0.93 |
| 908 | 1.02 | 944 | 1.12 | 980 | 1.23 | 1015 | 1.33 |
| |
2700 |
| 718 | 0.71 | 753 | 0.79 | 792 | 0.87 | 839 |
| 0.96 | 882 | 1.08 | 922 | 1.18 |
| 958 | 1.27 | 992 | 1.36 | 1026 | 1.47 | 1058 | 1.59 |
| |
3000 |
| 789 | 0.96 | 822 | 1.04 | 853 | 1.13 | 892 |
| 1.22 | 935 | 1.33 | 974 | 1.45 |
| 1011 | 1.58 | 1044 | 1.68 | 1076 | 1.78 | 1106 | 1.88 |
| |
3300 |
| 862 | 1.25 | 892 | 1.35 | 921 | 1.44 | 951 |
| 1.54 | 988 | 1.64 | 1026 | 1.76 |
| 1062 | 1.90 | 1096 | 2.04 | 1129 | 2.16 | 1158 | 2.27 |
| |
3600 |
| 934 | 1.61 | 963 | 1.71 | 990 | 1.81 | 1016 |
| 1.92 | 1045 | 2.02 | 1079 | 2.13 |
| 1115 | 2.27 | 1148 | 2.41 | 1180 | 2.57 | 1210 | 2.71 |
| |
|
| 2 HP Standard Motor & Static Drive |
|
|
|
| 2 HP Std Motor & Hi Static Drive |
|
|
|
|
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
| External Static Pressure (Inches of Water) |
|
|
|
|
|
|
|
|
|
| 3 HP |
|
| ||||||||
|
| 1.10 | 1.20 | 1.30 | 1.40 | 1.50 |
|
|
|
|
|
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
| & Hi Static Drive |
|
|
| |||||||||||||
CFM | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP |
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||
2400 |
| 1051 | 1.44 | 2 HP Standard Motor & Hi Static Drive | 1.75 | 1185 | 1.86 |
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
| 1085 | 1.54 | 1118 | 1.64 | 1152 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
2700 |
| 1090 | 1.70 | 1122 | 1.82 | 1153 | 1.94 | 1185 |
| 2.06 | 1216 | 2.18 |
|
|
|
|
|
|
|
|
|
|
|
|
|
3000 |
| 1136 | 2.00 | 1165 | 2.13 | 1194 | 2.26 | 1223 |
| 2.39 | 1251 | 2.52 |
|
|
|
|
|
|
|
|
|
|
|
|
|
3300 |
| 1187 | 2.39 | 1214 | 2.50 | 1242 | 2.63 | 1269 |
| 2.76 | 1296 | 2.90 |
|
|
|
|
|
|
|
|
|
|
|
|
|
3600 |
| 1239 | 2.84 | 1266 | 2.96 | 1291 | 3.08 | 1317 |
| 3.20 | 1343 | 3.34 |
|
|
|
|
|
|
|
|
|
|
|
|
|
3 HP Over-Sized Motor & Hi Static Drive
Notes: | Factory Supplied Motors, In Commercial Equipment Are Definite | |
Data Includes Pressure Drop Due To Wet Coils And Filters. | ||
Purpose Motors, Specifically Designed And Tested To Operate | ||
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500 | ||
Reliably And Continuously At All Cataloged Conditions. Using The | ||
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475 | ||
Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular | ||
| ||
| Data Will Not Result In Nuisance Tripping Or Premature Motor | |
| Failure. Our Product’s Warranty Will Not Be Affected. |
27 |