Napoleon Fireplaces BGD42, BGP42 Horizontal Termination, Definitions, Elbow Vent Length Values

Page 10

10

DEFINITIONS

for the following symbols used in the venting calculations and examples are:

>- greater than

>- equal to or greater than < - less than

< - equal to or less than

HT - total of both horizontal vent lengths (HR) and offsets (HO) in feet

HR - combined horizontal vent lengths in feet

HO - offset factor: .03(total degrees of offset - 135°*) in feet

VT - combined vertical vent lengths in feet

ELBOW VENT LENGTH VALUES

 

feet

inches

0.03

0.5

15°

0.45

6.0

30°

0.9

11.0

45°*

1.35

16.0

90°*

2.7

32.0

*the fi rst 45º and 90° offset has a zero value and is shown in the formula as -45°and -90ºrespectively or -135ºwhen combined.

HORIZONTAL TERMINATION

when (HT) < (VT)

Simple venting confi guration (only one 45º and 90° elbow)

90°

FIGURE6

For vent confi gurations requiring more than one 45º and 90° elbow, the following formulas apply:

Formula 1: HT < VT

Formula 2: HT + VT < 40 feet

Example 1:

90° H2

FIGURE 7

V1

45º

45º

H1

90°

REQUIRED

VERTICAL

R I S E I N

FEET (VT)

CALCULATED HORIZONTAL VENT RUN PLUS OFFSETS IN FEET (HT)

The shaded area within the lines represents acceptable values for HT and VT .

V1

=

8 ft

VT

= V1 = 8 ft

H1

=

2.5 ft

H2

=

2 ft

HR

= H1 + H2 = 2.5 + 2 = 4.5 ft

HO

= .03(one 45º elbow + two 90º elbows - 135º)

=0.3(225-135º) = 2.7ft

HT

=

HR + HO = 4.5 + 2.7 = 7.2 ft

HT + VT = 7.2 +8 =15.2ft

Formula 1: HT < VT

7.2< 8

Formula 2: HT + VT < 40 feet 15.2 < 40

Since both formulas are met, this vent configuration is acceptable.

W415-0381 / H / 12.07.07

Image 10
Contents W415-0381 / H $10.00 BGD42 Table of Contents Napoleon GAS Fireplace Presidents Lifetime Limited Warranty General Information General InstructionsCare of GLASS, and Plated Parts Installation Overview Venting Venting LengthsMinimum AIR Terminal Location Clearances Typical Vent Installations Special Vent InstallationsVenting Application Flow Chart Vertical TerminationDefinitions Horizontal TerminationElbow Vent Length Values Formula 1 HT 4.2 VT Formula 2 HT + VT 24.75 feet Vertical Termination Simple venting confi gurationsFormula 1 HT 3VT Formula 2 HT + VT 40 feet Installation Wall and Ceiling Protection Horizontal InstallationUsing Flexible Vent Components See FigureUsing Rigid Vent Components Fireplace Vent ConnectionOptional Wall Switch Installation Vertical Venting InstallationGAS Installation Restricting Vertical VentsMobile Home Installation FramingNailing TAB Installation TABL42 Louvre Installation FinishingLogo Placement Porcelain Reflective PanelsCharcoal Embers Optional Blower InstallationOptional FAN Installation VermiculiteGD36 Thermostatic Sensor Control Operation / MaintenanceMaintenance Operating InstructionsFlame Characteristics AdjustmentsPilot Burner Adjustment Venturi AdjustmentReplacement Parts ReplacementsAccessories W415-0381 / H Trouble Shooting Guide Symptom Problem Test SolutionFlames are very ag Door is ajar