Napoleon Fireplaces BGD42, BGP42 manual Venting Lengths

Page 6

6

VENTING

VENTING LENGTHS

Use only Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp or

American Metal Amerivent venting components. Minimum and

maximum vent lengths, for both horizontal and vertical installations,

and air terminal locations for either system are set out in this manual and must be adhered to. For Simpson Dura-Vent, Selkirk Direct Temp and American Metal Amerivent, follow the installation procedure provided with the venting components.

All outer pipe joints of these venting systems must be sealed using Red RTV Hight Temperature Sealant.

Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp and American Metal Amerivent venting systems must not be combined.

A starter adaptor must be used and may be purchased from the cor- responding supplier:

Supplier

4&7 ZC 5&8 ZC GAS STOVE

 

Dura-Vent

W175-0053

W175-0170

GDS924N

Amerivent

4DSC-N2

5DSC-N

4DSCB-N1

Direct Temp

4DT-AAN

5DT-AA

4DT-AAN

For Simpon Dura-Vent, Selkirk Direct Temp and American Metal Amerivent, follow the installation procedure found on the website for

your venting supplier:

 

VENTING SUPPLIER

WEBSITE ADDRESS

Simpson Dura-Vent

www.duravent.com

Selkirk Direct Temp

www.selkirkcorp.com

American Metal Amerivent

www.americanmetalproducts.com

For vent systems that provide seals on the inner exhaust flue, only the outer air intake joints must be sealed using a red high temperature silicone (RTV). This same sealant maybe used on both the inner exhaust and outer intake vent pipe joints of all other approved vent systems except for the exhaust vent pipe connection to the fi replace

ue collar which must be sealed using the black high temperature sealant W573-0007 (not supplied) Mill Pac.

When using Wolf Steel venting components, use only approved Wolf Steel rigid / fl exible components with the following termination kits: WALL TERMINAL KIT GD422, or 1/12 TO 7/12 PITCH ROOF TER- MINAL KIT GD410, 8/12 TO 12/12 ROOF TERMINAL KIT GD411, FLAT ROOF TERMINAL KIT GD412 or PERISCOPE KIT GD401 (for wall penetration below grade). With fl exible venting, in conjunction with the various terminations, use either the 5 foot vent kit GD420 or the 10 foot vent kit GD430.

These vent kits allow for either horizontal or vertical venting of the

replace. FIGURES 3 & 5. The maximum allowable horizontal run is 20 feet. The maximum allowable vertical vent length is 40 feet. The maximum number of 5" vent

The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year to verify that it is unob- structed and undamaged.

Purge all gas lines with the glass door of the fireplace removed. Assure that a continuous gas flow is at the burner before re- installing the door.

Under extreme vent configurations, allow several minutes (5-15) for the flame to stabilize after ignition.

A terminal shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings. Local codes or regulations may require different clearances.

Do not allow the inside liner to bunch up on horizontal or ver- tical runs and elbows. Keep it pulled tight. A 1¼" air gap all around between the inner liner and outer liner is required for safe operation. Use a firestop when penetrating interior walls, floor or ceiling.

Minimum clearance to combustible con- struction from fireplace and vent sur- faces:

Sides, back, bottom and

0"

top of the unit

 

Recessed depth

22"

All around the vent pipe*

2"

Enclosure top

45 1/2"

Ceiling

72" from bottom of unit

*HORIZONTAL VENT SECTIONS: A minimum clearance of 2" all around the vent pipe on all horizontal runs to combustibles is required. Use fi restop spacer W010-1778 (supplied).

VERTICAL VENT SECTIONS: A minimum of 1" all around the vent pipe on all vertical runs to combustibles is required except for clear- ances in fi replace enclosures. Use fi restop spacer W500-0367 (not supplied).

Horizontal runs may have a 0" rise per foot in all cases using

SIMPSON DURA-VENT, SELKIRK DIRECT TEMP, AMERICAN METAL AMERIVENT or NAPOLEON RIGID OR FLEXIBLE venting components when venting as illustrated in Figures 3, and 4.

For optimum performance it is recommended that all horizontal runs have a 1" rise per foot when using Napoleon® flexible vent components.

W415-0381 / H / 12.07.07

Image 6
Contents W415-0381 / H $10.00 BGD42 Table of Contents Napoleon GAS Fireplace Presidents Lifetime Limited Warranty General Instructions General InformationCare of GLASS, and Plated Parts Installation Overview Venting Venting LengthsMinimum AIR Terminal Location Clearances Typical Vent Installations Special Vent InstallationsVenting Application Flow Chart Vertical TerminationHorizontal Termination DefinitionsElbow Vent Length Values Formula 1 HT 4.2 VT Formula 2 HT + VT 24.75 feet Vertical Termination Simple venting confi gurationsFormula 1 HT 3VT Formula 2 HT + VT 40 feet Installation Wall and Ceiling Protection Horizontal InstallationUsing Flexible Vent Components See FigureUsing Rigid Vent Components Fireplace Vent ConnectionOptional Wall Switch Installation Vertical Venting InstallationGAS Installation Restricting Vertical VentsMobile Home Installation FramingNailing TAB Installation TABL42 Louvre Installation FinishingLogo Placement Porcelain Reflective PanelsCharcoal Embers Optional Blower InstallationOptional FAN Installation VermiculiteGD36 Thermostatic Sensor Control Operation / MaintenanceMaintenance Operating InstructionsFlame Characteristics AdjustmentsPilot Burner Adjustment Venturi AdjustmentReplacements Replacement PartsAccessories W415-0381 / H Trouble Shooting Guide Symptom Problem Test SolutionFlames are very ag Door is ajar