17. Alternate materials worksheet

How to determine if alternate floor protection materials are acceptable:

All floor protection must be non-combustible (i.e., metals, brick, stone, mineral fiber boards, etc.). Any organic materials (i.e., plastics, wood paper products, etc.) are combustible and must not be used. The floor protection specified includes some form of thermal designation such as R-value (thermal resistance) or k-factor (thermal conductivity).

PROCEDURE:

1. Convert specification to R-value:

 

 

 

 

1

x T

R-value given - no conversion needed.

 

 

K-factor is given with a required thickness (T) in inches:

R =

 

 

 

K x 12

k-factor is given with a required thickness (T) in inches: R =

1

x T

r-factor is given with a required thickness (T) in inches: R = r x T

k

 

 

 

 

 

 

2.Determine the R-value of the proposed alternate floor protector.

i.Use the formula in step (1) to convert values not expressed as “R”.

ii.For multiple layers, add R-values of each layer to determine overall R-value.

3.If the overall R-value of the system is greater than the R-value of the specified floor protector, the alternate is acceptable.

EXAMPLE: The specified floor protector should be 3/4 inch thick material with a k-factor of 0.84. The proposed alternate is 4” brick with an r-factor of 0.2 over 1/8” mineral board with a k-factor of 0.29.

 

 

1

 

=

1

 

x 0.75 = 0.893

Step (a): Use formula above to convert specification to R-value.

R = k x T

.84

 

 

 

 

 

 

Step (b): Calculate R of proposed system. 4" brick of r = 0.2, therefore:

1/8" mineral board of k = 0.29, therefore:

Rbrick = 0.2 x 4 = 0.431

Rmineral board

=

1

x 0.125 = 0.431

0.29

 

 

 

 

 

 

 

 

 

Rtotal = Rbrick + Rmineral board = 0.8 + 0.431 = 1.231

Step (c): Compare proposed system Rtotal of 1.231 to specified R of 0.893. Since proposed system Rtotal is greater than required, the system is acceptable.

DEFINITIONS

 

(ft2)(hr)(oF)

k = Btu(in) = K x 12

K =

Btu(ft)

2

o

F)=

1

=

Btu

 

2

(hr)(oF)

r = (ft

)(hr)(

k

 

 

2

o

F)

 

ft

(Btu)(in)

 

 

 

 

ft

(hr)(

 

 

 

 

18. Position the Hearth Extension

 

 

 

 

 

 

 

Position and secure the hearth extension over the

 

 

 

 

 

protective metal strips that have been placed partially

 

 

 

 

 

under the fireplace front. These strips should be

 

 

 

 

 

protruding approximately 2” from under the fireplace

 

 

 

 

 

front and 2” on both sides of the fireplace opening.

 

 

 

 

 

See Figure 13A on page 13. Seal the crack between

 

 

 

 

 

the hearth extension and fireplace with a bead of

 

 

 

 

 

noncombustible sealant. See Figure 18A. Apply a

 

 

 

 

 

noncombustible finishing material of your choice to the

 

 

 

 

 

hearth extension.

 

 

 

 

 

 

 

 

 

 

 

NOTE: SEE PAGE 5 “CLEARANCES TO COM-

 

 

 

 

 

BUSTILES, HEARTH EXTENSIONS / FLOOR PROTEC-

 

 

 

 

 

TION” FOR CLEARANCES REQUIRED FOR DIFFER-

 

 

 

 

 

ENT HEARTH EXTENSION INSTALLATIONS. THE

 

 

 

 

 

CLEARANCES MUST BE STRICTLY ADHERED TO.

 

 

 

 

 

 

 

 

 

WARNING!

 

 

 

 

 

 

 

 

 

Hearth extensions are to be installed only as illustrated to

 

 

 

 

 

 

prevent high temperatures from occurring on concealed

 

 

Seal with non-

combustible materials. Hearth sealing strips prevent

 

 

 

 

combustible sealant

burning or hot particles from inadvertently falling directly

 

 

 

 

 

 

 

 

on combustible surfaces in the event the building should

 

 

Figure 18A - Position the Hearth Extension

settle and disturb the original construction.

 

 

 

480-1081

 

 

 

 

 

 

 

18

 

 

 

4-03

Image 18
Contents Kensington Blvd Installation & Operating InstructionsHearth & Home Technologies Lakeville, MNTable of Contents Safety PrecautionsFireplace system consists of the following Listings and Code ApprovalsDescription of the Fireplace System Required Components IncludeInstallation and Draft Considerations Outside AIR KIT InstallationHearth Extension / Floor Protection Fireplace and Hearth Extension are flush on the floorChimney Components Catalog No DescriptionCatalog No 27-3/815-3/4 PRE-INSTALLATION Preparation Fireplace Locations and Space RequirementsElectrical Access and Wiring Diagram Chimney RequirementsFraming the Fireplace Using Offsets and Returns Offset ChartDimensions reflect effective height Chimney Height Requirements above roof lineNumber of Sections Required Placing the Protective Metal Hearth Strips Installation of FireplacePositioning the Fireplace Leveling the FireplaceInstalling the Firestop Spacer Installing Firestop SpacersDouble-checking the Chimney Assembly Installing an Attic Insulation Shield Mobile home installation SL-300 Series MH842 Celing/Roof ThimbleMarking the Exit Point of the Roof SL-300 MH842 Celing/Roof Thimble Cont’dSecuring the Chimney System Cutting out the Hole in the RoofInstalling the Roof Flashing Completion of the EnclosureHearth Extension Alternate materials worksheet Position the Hearth ExtensionMantel Constructing a ChaseFinishing Material MaterialsChase Top Termination CapGeneral Information Outside Air Automatic Combustion Control Burning ProcessAir Control Kindling or 1st stageHeat Zone Operating Instructions Burning GuidelinesFan Operating Instructions BTU / Hr Slide ControlStarting a Fire Burn RatesOpacity Moisture content Wood Fuel Hardwood vs. SoftwoodSeasoning Draft Problems Storing WoodMaintenance Instructions Care and Cleaning of Glass Glass Replacement Care and Cleaning of Plated SurfacesFirebrick Replacement Brick PatternFan Replacement Fan Cord LocationBaffle Removal & Installation Door & Door GasketDoor Assembly Fascia Assembly Exploded ViewService Parts List Index Lifetime Warranty Please Return