Vanguard Heating VMH26PRA installation manual Troubleshooting, Observed Problem Possible Cause

Page 22

® VMH26PRA

COMPACT CLASSIC HEARTH FIREPLACE

TROUBLESHOOTING

Note: For additional help, visit DESA International’s technical service web site at www.desatech.com.

Note: All troubleshooting items are listed in order of operation.

WARNING: Turn off heater and let cool before servicing. Only a qualified service person should service and repair heater.

CAUTION: Never use a wire, needle, or similar object to clean ODS/pilot. This can damage ODS/ pilot unit.

OBSERVED PROBLEM

POSSIBLE CAUSE

REMEDY

When ignitor button is pressed, there is no spark at ODS/pilot

1.Ignitor electrode not connected to igni- tor cable

2.Ignitor cable pinched or wet

3.Piezo ignitor nut is loose

4.Broken ignitor cable

5.Bad piezo ignitor

6.Ignitor electrode broken

7.Ignitor electrode positioned wrong

1.Reconnect ignitor cable

2.Free ignitor cable if pinched by any metal or tubing. Keep ignitor cable dry

3.Tighten nut holding piezo ignitor to base panel of log set. Nut is located behind base panel

4.Replace ignitor cable

5.Replace piezo ignitor

6.Replace piezo ignitor

7.Replace piezo ignitor

When ignitor button is pressed, there is spark at ODS/pilot but no ignition

1.Gas supply turned off or equipment shutoff valve closed

2.Control knob not in PILOT position

3.Control knob not pressed in while in PILOT position

4.Air in gas lines when installed

5.Depleted gas supply

6.ODS/pilot is clogged

7.Gas regulator setting is not correct

1.Turn on gas supply or open equipment shutoff valve

2.Turn control knob to PILOT position

3.Press in control knob while in PILOT position

4.Continue holding down control knob. Re- peat igniting operation until air is removed

5.Contact local propane/LP gas company

6.Clean ODS/pilot (see Cleaning and Maintenance, page 21) or replace ODS/ pilot assembly

7.Replace gas control

ODS/pilot lights but flame goes out when control knob is released

1.Control knob not fully pressed in

2.Control knob not pressed in long enough

3.Equipment shutoff valve not fully open

4.Pilot flame not touching thermocouple, which allows thermocouple to cool, causing pilot flame to go out. This prob- lem could be caused by one or both of the following:

A)Low gas pressure

B)Dirty or partially clogged ODS/pilot

5.Thermocouple connection loose at con- trol valve

6.Thermocouple damaged

7.Control valve damaged

1.Press in control knob fully

2.After ODS/pilot lights, keep control knob pressed in 30 seconds

3.Fully open manual shut-off valve

4.A) Contact local propane/LP gas company

B) Clean ODS/pilot (see Cleaning and Maintenance, page 21) or replace ODS/ pilot assembly

5.Hand tighten until snug, then tighten 1/4 turn more

6.Replace thermocouple

7.Replace control valve

www.desatech.com

For more information, visit www.desatech.com

22

107034

Image 22
Contents VENT-FREE PROPANE/LP GAS What to do if YOU Smell GASSafety Information Compact Classic Hearth FireplaceLocal Codes Product FeaturesRemote Control Accessories UnpackingAssembling Fireplace AssemblyInstalling Log Assembling HoodUnusually Tight Construction AIR for Combustion and VentilationProviding Adequate Ventilation Confined and Unconfined SpaceDetermining FRESH-AIR Flow for Fireplace Location AIR for Combustion VentilationDetermining if You Have a Confined or Unconfined Space Ventilation Air From Inside Building Ventilation AIRVentilation Air From Outdoors Check GAS Type InstallationInstallation Items Locating FireplaceBUILT-IN Fireplace Installation Rough Opening for Installing in WallMantel Clearances for Built-In Installation Optional Mantel InstallationAssembling Brass Trim Brass trim shipped with mantel Installing Blower Assembly Installing Blower Accessory GA3400TRemoving Upper Louver Assembly For Built-In Installation Extension CordAttaching Wood Base to Solid Floor Connecting to GAS SupplyFor attaching base to solid floors concrete or masonry Connecting Fireplace to GAS Supply Installation Items NeededPressure Testing Gas Supply Piping System Pressure Testing Fireplace Gas ConnectionsChecking GAS Connections Installing 9-Volt Battery in Hand- Held Remote Control Unit Optional Wireless HAND- Held Remote Control AccessoriesInstalling Receiver Wire harness provided in the fireplace hardware packOptional Wall Switch GWMS2 Operating Fireplace For Your Safety Read Before LightingLighting Instructions To Turn OFF GAS To Appliance Manual Lighting ProcedureOptional Remote Operation GWMT1 Wall Mounted Thermostat Optional GWMS2 Wall Mounted Switch OptionalInspecting Burners Operating BlowerInspecting Burner Cleaning and MaintenanceCleaning Burner Injector Holder and Pilot AIR Inlet Hole Burner Flame PatternTroubleshooting Observed Problem Possible CauseLation requirements Pane/LP gas companyCarpet, etc. See Important state Is running Ment above Gas odor even when control knob is in OFFVice person PositionService Hints SpecificationsReplacement Parts Technical ServiceIllustrated Parts Breakdown VMH26PRA4Parts List VMH26PRAAccessories Cleaning KIT CCK Wall Mounted Switch KIT GWMS2Wall Mounted Thermostat KIT GWMT1 Warranty Information International